Optimization Method for Twin-Tunnel Complementary Ventilation Design and Its Energy Saving Effect

Table 3

Required air volumes (m3/s).

Design conditionsShort term (2025)Long term (2033)
UphillDownhillSumU/ D UphillDownhillSumU/ D

Pollutants dilutionCO181.47176.05357.521.03300.10291.13591.231.03
Smoke377.42107.1484.523.52598.18169.74767.923.52
Fire emergency188.37188.37376.741188.37188.37376.741
Minimum air exchange311.65285.9597.551.09415.53381.21796.741.09
Maximum value377.42285.9663.321.32598.18381.21979.391.57

Note: the item marked with indicates the maximum required air volume for tunnels; “U/D” indicates the required air flow ratio of the uphill and downhill tunnel.