Optimal Allocation of DG and DSTATCOM in Radial Distribution System Using Cuckoo Search Optimization Algorithm
Table 2
Result of 34-bus system.
| Cases | ā | PSO [12] | Proposed method |
| Only DG case (II) | DG (size and location) | 0.1996 (21) | 2.3278 (23) | Power loss (kW) | 203.98 | 98.42 | (p.u) | NA | 0.9740 | VSI (p.u) | NA | 0.8999 | TOC ($) | NA | 12032.6 | Average computation time (s) | NA | 11.41 |
| Only DSTATCOM (Case III) | DSTATCOM (size and location) | 0.1606 (21) | 1.3705 (23) | Power loss (kW) | 212.96 | 175.01 | (p.u) | NA | 0.9488 | VSI (p.u) | NA | 0.8105 | TOC ($) | NA | 7552.5 | Average computation time (s) | NA | 11.52 |
| Both DG and DSTATCOM placed simultaneously (Case IV) | DG & DSTATCOM (size and location) | 0.1371 (21), 0.1634 (21) | 2.3905 (23), 1.3419 (23) | Power loss (kW) | 177.10 | 55.03 | (p.u) | 0.9483 | 0.9771 | VSI (p.u) | NA | 0.9115 | TOC ($) | NA | 18882.1 | Average computation time (s) | NA | 11.69 |
|
|