Optimal Allocation of DG and DSTATCOM in Radial Distribution System Using Cuckoo Search Optimization Algorithm

Table 3

(a) Result of 69-bus system

CasesPSO [12]Proposed method

Only DG (Case II)DG (location)1.8761 (61)1.8727 (61)
Power loss (kW)83.2283.21
(p.u)NA0.9682
VSI (p.u)NA0.8788
TOC ($)NA9696.3
Average computation time (s)NA12.54

Only DSTATCOM (Case III) DSTATCOM (size and location)0.9011 (61)1.200 (61)
Power loss (kW)159.38152.95
(p.u)NA0.9285
VSI (p.u)NA0.7375
TOC ($)NA6611.8
Average computation time (s)NA12.84

Both DG and DSTATCOM placed simultaneously (Case IV) DG & DSTATCOM (size and location)0.1223 (61),
0.9045 (61)
1.7500 (61),
1.15 (61)
Power loss (kW)32.5624.15
(p.u)NA0.9715
VSI (p.u)NA0.8908
TOC ($)NA14596.6
Average computation time (s)NA12.35

(b) Result of multiple DG and DSTATCOM placement (Case  V)

12-bus system34-bus system69-bus system

DG size in MW (location)0.075 (),
0.09 (),
0.065 ()
1.90 ()
0.77 ()
0.10 (34)
0.49 (),
1.40 (61),
0.25 (63)

DSTATCOM size in MVAr (location)0.11 (),
0.075 (),
0.10 ()
0.65 ()
0.85 ()
0.75 (25)
0.27 (25),
0.98 (61),
0.20 (63)

Power loss (kW)1.3419.328.07
(p.u)0.99470.99190.9925
VSI (p.u)0.97780.96820.9587
TOC ($)2580.42632717982
Average computational time (s)11.9812.1212.56