Combined DFT and Fuzzy Based Faulty Phase Selection and Classification in a Series Compensated Transmission Line
Table 12
Effect of fault resistance, fault inception angle, and fault location.
| Simulated system data | Results obtained from the proposed CDFTF-based scheme | FL (km) | Fault type | FR (ohm) | FIA (degree) | Response time (ms) | Fault type | Phase A | Phase B | Phase C | Ground G |
| 20 | CG | 100 | 0 | — | — | 8 | 3 | CG | ABG | 80 | 90 | 5 | 7 | — | 2 | ABG | ABC | 20 | 225 | 3.5 | 4.5 | 5.5 | — | ABC |
| 120 | CAG | 0.001 | 45 | 4.5 | — | 6.5 | 2.5 | CAG | AG | 40 | 90 | 6 | — | — | 4 | AG | AB | 60 | 135 | 9.5 | 7.5 | — | — | AB |
| 160 | AC | 0.001 | 90 | 3 | — | 4 | — | AC | BG | 60 | 180 | — | 6 | — | 4 | BG | BCG | 100 | 45 | — | 10.5 | 7.5 | 3.5 | BCG |
| 240 | CG | 0.001 | 0 | — | — | 11 | 4 | CG | BC | 80 | 45 | — | 10.5 | 12.5 | — | BC | ABC | 100 | 90 | 12 | 10 | 7 | — | ABC |
| 290 | AG | 20 | 135 | 11.5 | — | — | 8.5 | AG | AC | 40 | 180 | 18 | — | 10 | — | AC | ABG | 0.001 | 45 | 5.5 | 12.5 | — | 6.5 | ABG |
|
|