Research Article

Combined DFT and Fuzzy Based Faulty Phase Selection and Classification in a Series Compensated Transmission Line

Table 9

Simulation results for different compensation levels (BCG fault, FR = 10 Ω, and FL = 165 km).

Simulated system dataResults obtained from the proposed CDFTF-based scheme
Fault type%XcFIA (degree)Response time (ms)Fault type
Phase APhase BPhase CGround G

BCGWithout capacitor05.010.85.0BCG
BCG1005.010.85.0BCG
BCG2005.010.05.0BCG
BCG3004.110.05.0BCG
BCG5003.38.34.1BCG
BCG6003.34.14.1BCG
BCG6502.52.54.1BCG