Research Article

Delayed Station Blackout Event and Nuclear Safety

Table 6

Probability of nonrecovery of AC power within given time.

Basic eventRestoration time [s]Probability of nonrecovery of AC

NRAC-SGDR 043004,74E − 01
NRAC-PRZBV 0136201,67E − 01
NRAC-OFFSITE 0336205,46E − 02
NRAC-ONSITE 0336205,76E − 04
NRAC-SGDR 1587702,65E − 01
NRAC-PRZBV 15139801,62E − 01
NRAC-OFFSITE 15339005,41E − 02
NRAC-ONSITE 15339005,67E − 04
NRAC-SGDR 30]92002,53E − 01
NRAC-PRZBV 30140201,61E − 01
NRAC-OFFSITE 30343005,33E − 02
NRAC-ONSITE 30343005,53E − 04
NRAC-SGDR 60100502,31E − 01
NRAC-PRZBV 60140201,61E − 01
NRAC-OFFSITE 60346405,26E − 02
NRAC-ONSITE 60346405,42E − 04
NRAC-SGDR 75105002,21E − 01
NRAC-PRZBV 75140201,61E − 01
NRAC-OFFSITE 75350305,19E − 02
NRAC-ONSITE 75350305,29E − 04