Research Article

Experimental Evaluation for the Microvibration Performance of a Segmented PC Method Based High Technology Industrial Facility Using 1/2 Scale Test Models

Table 5

Comparison of natural frequency and response magnitude by the impact test on R/P floor.

ModeFrequency (Hz)Response (um/Ns)
Nonsegmented
Model
Segmented
Model
Ratio
(%)
Nonsegmented
Model
Segmented
Model
Ratio
(%)

1st16.315.796.413.56.346.3
2nd29.126.992.54.90.917.8
3rd38.640.5104.93.50.823.8