Shaking Table Array Tests of an Ultra-High-Voltage Cup-Type Transmission Tower-Line System
Table 9
Longitudinal peak strain responses of the middle towers of the four models.
| Test series | Single-tower model (με) | Single-tower model with suspended lumped masses (με) | Three-tower-two-line model (με) | Five-tower-four-line model (με) |
| 0.07 g artificial wave | 53.546 | 59.655 | 56.044 | 56.169 | 0.07 g El Centro wave | 28.017 | 33.378 | 33.323 | 33.819 | 0.07 g Taft wave | 33.187 | 37.373 | 33.432 | 34.995 | 0.07 g average | 38.250 | 43.469 | 40.933 | 41.661 | 0.21 g artificial wave | 148.616 | 171.750 | 167.730 | 150.257 | 0.21 g El Centro wave | 101.668 | 108.935 | 129.404 | 104.848 | 0.21 g Taft wave | 106.910 | 117.344 | 111.988 | 122.553 | 0.21 g average | 119.065 | 132.677 | 136.374 | 125.886 | 0.63 g artificial wave | 450.086 | 426.452 | 442.957 | 513.300 | 0.63 g El Centro wave | 358.235 | 359.335 | 394.204 | 347.420 | 0.63 g Taft wave | 394.345 | 347.076 | 306.438 | 377.690 | 0.63 g average | 400.888 | 377.621 | 381.200 | 412.803 |
|
|