Abstract

The tuned mass damper (TMD) can be applied to suppress earthquake, wind, and pedestrian- and machine-induced vibration in factory buildings or large span structures. However, the traditional TMD with a fixed frequency will not be able to perform effectively against the frequency variations in multiple hazards. This paper proposed a frequency-adjustable tuned mass damper (FATMD) to solve this limitation of current TMD. The FATMD presented in this paper is composed of a simple assembly consisting of a supported beam with a mass, in which the frequency of the FATMD is changed by adjusting the span of the beam. The kinematic equation of a single degree of freedom (SDOF) structure installed with an FATMD is established to analyze the effect of the damping ratio, mass ratio, and stiffness on the vibration damping. The fundamental frequency of the FATMD at different spans is verified by simulation and experiments. Forced vibration experiments with different excitation frequencies are also conducted to verify the performance of the FATMD. The results show that the proposed FATMD can effectively suppress the vertical vibration of structures at different excitation frequencies, including frequencies at a range higher than what a traditional TMD may not be able to suppress. Additionally, the proposed FATMD is applied to a long-span pedestrian bridge which vibrates frequently due to the walking of pedestrians, the running of escalators, and earthquakes. The numerical results indicate that the FATMD can effectively reduce the vertical vibration of the pedestrian bridge under the excitations of pedestrians, escalators, and earthquakes.

1. Introduction

The rapid development of mechanical automation has given rise to the increasing presence of large equipment in factories and the construction of large span structures. Factory buildings and large span structures often house high-power equipment, which can generate strong vibrations that can affect the integrity of the surrounding structures. If the structural vibration exceeds a certain level, it will negatively affect the function and performance of other devices in the building [1, 2]. The vibration can also lead to a reduced level of comfort for the working personnel [3, 4]. In extreme cases, the vibration can even cause structural damage [5]. There are numerous ways to reduce the vibration of a structure within comfortable levels. One way is to increase the stiffness of the structure, thereby increasing the natural frequency of the structure and shifting it from the range in which it can be easily reached [6, 7]. Wang et al. [8] strengthened the floor slab and secondary beams to increase the natural frequency of the floor, thereby reducing floor vibrations caused by wheat bran finishers and flour purifiers. However, increasing stiffness may waste the performance of the material and can become expensive. Another method is to utilize vibration-control technologies. Since the concept of vibration control was first proposed by Yao [9] in 1972, numerous vibration-control techniques have been developed and applied to enhance the functionality and safety of structures. Lee et al. [10] utilized multiple viscoelastic dampers to suppress microvibrations in the floor induced by automated guided vehicles in thin-film transistor liquid crystal display factories. The dampers effectively suppressed the dynamic responses to a desired vibration criterion level. Zordan et al. [11] proposed an active micromachined vibration isolator to isolate high-frequency mechanical vibrations in low-pressure environments, which is suitable for use in or as packaging for sensitive electronic and microelectromechanical systems (MEMS). Setareh et al. [12] proposed a pendulum tuned mass damper to control the excessive vibrations of building floors.

As one of the most popular and flexible vibration control devices, the tuned mass damper (TMD) boasts the advantages of a simple set up, effective vibration suppression, and not needing an energy source (i.e., passive control). TMDs are widely applied in the engineering community, such as in the Condo tower in San Francisco and the Citicorp Building in New York City. Sun et al. [13] analyzed the vibration control effect of TMDs installed on the Chongqing Bridge under Typhoon Chan-hom and demonstrated the effectiveness of the TMDs and their ability to suppress vibrations under a wide range of wind conditions. Caetano et al. [14, 15] evaluated the efficiency of the lateral and vertical TMDs on the Pedro e Inês footbridge in Portugal. Carpineto et al. [16] simulated the dynamic response of suspension footbridges with and without multiple TMDs (MTMDs) under pedestrian-induced excitations. The simulation indicated that MTMDs can effectively reduce vibrations of suspension footbridges. Considering uncertainties present in the structural parameters and the MTMD design, Vellar et al. [17] proposed a new methodology for simultaneous optimization of parameters and positions of MTMDs in buildings that may be subjected to earthquakes. They applied the proposed methodology in a 10-story building to confirm its effectiveness. Elias et al. [18] applied different TMD schemes to reduce structural dynamics under wind and earthquake excitations and found that, for the purposes of multihazard response control, distributed TMDs with equal stiffnesses are preferable compared to those with equal masses. Gerges and Vickery [19] demonstrated the superiority a wire rope spring TMD over a normal TMD and verified the vibration control performance of the new TMD through shaking table tests. He et al. [20] set up TMDs in a cabin to restrain large vibration displacements caused by loads from offshore floating wind turbines, which often face harsh marine conditions. The researchers also simulated the dynamic responses of the wind turbine with and without TMDs under different combined wind and wave loads. Their analyses showed that TMDs can effectively reduce vibration responses for offshore floating wind turbines. Wu et al. [21] proposed a magnetic TMD which is reliable and robust in controlling the vibrations of structures. Bakre and Jangid [22] derived optimum parameters for a TMD system attached to a viscous damped main system. The TMD was able to be tuned for various combinations of excitation and response parameters. Kang and Peng [23] determined the optimal parameters for large mass ratio TMDs subjected to harmonic loads and random, stationary white noise loads and studied the control effect of large mass ratio TMDs. Lu et al. [24] proposed a particle TMD and evaluated its damping performance through aeroelastic wind tunnel tests on a benchmark high-rise building. The results showed that the particle TMD can effectively suppress the wind-induced vibration of the structure. Lu et al. [25] evaluated the effectiveness of the eddy-current TMD (EC-TMD) in suppressing the vibration of the structure through shaking table tests, and the results showed that the EC-TMD can effectively reduce the displacement response, acceleration response, interstory drift ratio, and maximum strain of the columns under different earthquake excitations. Zhang et al. [26] proposed a pounding TMD (PTMD) and numerically simulated the PTMD on a 55 m tower model to verify the effectiveness of the pounding TMD. The results demonstrated that the PTMD is able to suppress vibrations faster and more strongly than the normal TMD. Xue et al. [27] examined the application of the PTMD in reducing the vibration of offshore jacket-type platforms and showed that the PTMD performed better than the traditional TMD in the desired frequency bandwidth. He et al. [28] proposed a TMD with poles and torsional pendulums (TMDPP). The TMDPP can simultaneously control the translational responses and the torsional angle of asymmetric structures. Santos et al. [29] tested a TMD control system to reduce the excessive vibrations of a gym floor in a commercial building in Brasilia, Brazil. Nguyen [30] optimized the parameters of a symmetric TMD using an analytical method that considers specific vibration duration and stability criteria. Tarng et al. [31] mounted a piezoelectric inertia actuator on the cutting tool, which can suppress the vibration and improve cutting stability in turning operations. Yang et al. [32] designed and optimized MTMDs to increase the chatter resistance of machine tool structures.

However, a major drawback of the conventional TMD is that if the TMD is detuned form the natural frequency, a significant loss of vibration control performance can occur. Therefore, the conventional TMD with a fixed frequency cannot perform effectively against the frequency variations in multiple hazards. To overcome this issue, many semiactive or active methods have been proposed. Chang et al. [33] reported the use of an adjustable, vertically moving TMD (VTMD) to suppress machine-induced vertical vibration of structures. Abdel-Rohman et al. [34] studied the influence of the time delay on the performance of a semiactive TMD and proposed two methods to compensate for the time delay and ensure the vibration suppression effect. Jiang and Hanagan [35] proposed a semiactive variable damping TMD (SAVDTMD) with piezoelectric friction dampers as an alternative to existing methods to control floor vibrations, especially vibrations induced by pedestrian traffic. Esteki et al. [36] described the use of a magnetorheological fluid-based semiactive TMD to suppress the seismic response of a 40-story steel-frame building in Vancouver. The new semiactive suppressed structural vibrations more effectively than the classic passive TMD. Nagarajaiah et al. [37, 38] developed a semiactive or smart TMD (STMD) using a semiactive variable stiffness system, which is robust against changes in the natural frequency of the host structure since the STMD always stays tuned. Ryan et al. [39] proposed an adaptive passive vibration absorber and experimentally validated the effectiveness through experiments. The results demonstrated that the adaptive absorber is able to achieve 25 dB of attenuation in the vibration of a model building. Contreras et al. [40, 41] proposed an adaptive length pendulum smart TMD (ALP-STMD) in which natural frequencies are time invariant. They experimentally validated the ability of an ALP-STMD to adequately control a structural system. Similar devices were applied towards bridge vibration control [42]. Shi et al. [43] proposed a self-adjustable variable mass TMD (SAVM-TMD) and experimentally validated the effectiveness under different pedestrian excitations. The results demonstrated that the SAVM-TMD is able to suppress pedestrian vibrations better than the normal TMD. Venanzi et al. [44] proposed an active TMD to mitigate wind-induced vibrations of tall buildings and optimized the number and positions of active TMDs. Rahman et al. [45] investigated the seismic performance of a 10-story building and demonstrated the efficiency of using multiple adaptive TMD to dampen seismic-induced structural vibrations.

The traditional TMD is a type of frequency sensitive control device. Thus, the potential for unintended detuning of the TMD’s natural frequency is a major drawback of the traditional TMD. When the frequency of the TMD is not matched with the frequency of the host structure, the TMD can suffer a significant loss of vibration control performance. The vibration frequencies of structures are often varied due to the degradation of structural parameters in multiple hazard scenarios, which requires that the frequency of TMD should be easily tuned to better respond to this variation. The natural frequency of the TMD is determined partially by its stiffness, which, in current TMDs, is usually provided by springs. The stiffness of the spring is difficult to be set precisely due to unavoidable errors in the manufacturing process, and thus, it is difficult to guarantee the exact frequency of the vibration control system. Therefore, the TMD is usually adjusted by changing the mass of the system after the spring is fabricated. However, doing so means that there is a very narrow tuning range for setting the frequency of the TMD. Furthermore, the traditional TMD is only suitable for mitigating low-frequency vibrations and has trouble of controlling high frequency vibrations often generated by mechanical equipment. To overcome these issues, a frequency-adjustable tuned mass damper (FATMD) is proposed in this study. The FATMD utilizes a beam instead of a spring to provide the stiffness to the control device and can effectively suppress high-frequency vibrations. The frequency of the FATMD can be adjusted by adjusting the span of the beam. In this paper, the kinematic equations of the structure with a FATMD are established to analyze the effect of damping ratio, mass ratio, and stiffness on its ability to dampen vibrations. Subsequently, the fundamental frequencies of the FATMD with different adjusted spans are verified by simulation and experiments. To verify the vibration suppression performance of the FATMD, the FATMD is subjected to forced vibrations at different excitation frequencies.

2. The FATMD

The schematic of the FATMD is shown in Figure 1. The FATMD consists of an easy-to-implement assembly of a bottom plate, vertical columns, a weighted steel plate, and a beam. As shown in Figure 1(b), the pedestals of columns (3) are bolted between the bottom plate (1) and the pressure plate (2). Before the columns are fixed, the span of the beam (6) can be adjusted by moving the pedestals of the columns (3) along the length of the bottom plate (1) and, thereby, allow the continuous adjustment of the natural frequency of the FATMD. The beam (6) is installed on the rectangular platform of formed by the columns (3) and is fixed via the bolted column fastener (7). The weighted box (4) is fixed to the beam (6) through a set of fasteners. The beam (6) is clamped between the weighted box (4) and the fastener, and a gasket placed between the beam and the weighted box prevents the weighted box from sliding along the beam’s axis. The bolt holes are set to straight notches, which are perpendicular to the axial direction. The weighted box (4) can be finely adjusted along the length of the beam to avoid any eccentricity of the FATMD caused by the weight box. The counterweight steel plate (5) hangs from the weighted box and, thus, reduces the footprint of the FATMD. The frequency of the FATMD can be finely adjusted by changing the mass of the plates.

3. Control Equations of an SDOF Structure with the FATMD

The TMD is one of the earliest passive control devices used in structural vibration control. When the main structure vibrates under external excitation, the TMD control system is driven to vibrate together with the structure. Then, inertial forces generated by the relative motion of the TMD acts against the motions of the structure and, thus, can reduce the dynamic response of the structure. To illustrate the working principle, a single degree of freedom (SODF) primary structure installed with the FATMD is illustrated in Figure 2, where m1, c1, and k1 are, respectively, the mass, damping, and stiffness of the SDOF structure. m2, c2, and k2 are the mass, damping, and stiffness of the FATMD, respectively.

According to D’Alembert’s principle, the kinematic equations of the SDOF structure with the FATMD are as follows:where x1, , and are the displacement, velocity, and acceleration of the structure relative to the ground, respectively. x2, , and are the displacement, velocity, and acceleration of the FATMD relative to the ground, respectively.

The equations can be solved by expressing them in the form of a transfer function. Thus, after applying the Laplace transform,where s represents the independent variable after the Laplace transform of the original function.

Equation (5) can be organized as follows:where ω1 and ξ1 are, respectively, the frequency and the damping ratio of the structure. μ is the ratio of the mass of the TMD to the total mass of the structure.

Thus, the overall transfer function for the primary structure is as follows:

4. Parametric Analysis of the FATMD

The previous section considered the SDOF structure coupled with an FATMD (Figure 2) as an analytical model and established the control equations for the whole system. In this section, a parametric analysis for the system under the sinusoidal excitation is provided to verify the influences of parameters of the FATMD on its effectiveness, which can provide useful information for designing the FATMD. The parameters of the FATMD are as follows based on practicality:(1)λ: the ratio of the frequency of the FATMD to the fundamental frequency of the structure(2)μ: the ratio of the mass of the FATMD to the total mass of the structure(3)ξ: the damping ratio of the FATMD

As shown in Figure 3, the logarithmic amplitude-frequency characteristic curves of the structure with and without the FATMD are plotted for different values of λ when μ = 0.01. The curves can illustrate the trend of changes on the amplitude of the structural response at different frequencies. By comparing the amplitudes of the uncontrolled and controlled structural vibrations, it is noted that the vibration of the structure can be effectively reduced by the FATMD. When the frequency of the external excitation is 15.7 Hz, the vibration of the structure without control peaks is due to resonance. The vibration suppression effect of the FATMD is stable between λ = 0.9–1.1, with λ = 1.0 being a relatively optimal value according to the curves. Additionally, the vibration suppression effect of the FATMD is pronounced when the frequency of the FATMD matches the excitation frequency.

In Figure 4, the logarithmic amplitude-frequency characteristic curves of the system are plotted for different values of μ when λ = 1.0. A comparison of the seven curves with and without control reveals the obvious vibration mitigation effect of the FATMD. By increasing the mass of the FATMD, the effective bandwidth of the FATMD widens and the vibration suppression effect on the structural vibrations also increases. Furthermore, in Figure 5, the logarithmic amplitude-frequency characteristic curves of the system are plotted for different values of ξ when λ = 1.0 and μ = 0.01. The figure shows that the greater the damping ratio, the weaker the vibration reduction effect of the FATMD becomes. Thus, the damping ratio of the FATMD should be minimized in the cases that the frequencies of excitation deviate far from the one of the structure.

5. Vibration Control Experiments of the FATMD

5.1. Experimental Setup

To verify the vibration suppression performance of the FATMD, the FATMD and the structure are subjected to forced vibrations at different excitation frequencies. The primary structure is a model steel floor elevated on four steel legs. The size of the steel floor is 100 × 20 × 1.5 cm. The height of the structure is 40 cm, and the total weight of the structure is 32.52 kg. The natural frequency of the structure is 25.8 Hz. As shown in Figure 6, the FATMD mainly consists of a bottom plate, vertical columns, a steel weight, and a beam, similar to the schematic shown in Figure 1. The beam is a steel pipe with a length of 1 m and 1 mm thick steel walls. Two kinds of steel pipes with different diameters are tested for the verification experiment. One pipe has a line inner radius of 5 mm, and the other has a line inner radius of 6 mm. The rubber gaskets are installed between the column and the beam to prevent the beam from sliding in the axial direction between the platform and fastener of the column. A mass of 0.5 kg is fixed in the middle of the beam and the frequency of FATMD can be fine-tuned by changing the mass.

As shown in Figure 7, the shaker is installed at the bottom of the primary structure and is used to excite the vertical vibration of the primary structure during the test. The shaker (model: JZK-20) can be controlled by a signal generator and can continuously output a sinusoidal signal with a frequency between 1–10000 Hz. Without any loads, the maximum displacement is 10 mm, and the maximum output force is 200 N. Two accelerometers (model: Lance LC0101) are mounted to measure the absolute acceleration. One is fixed onto the primary structure, and the other is fixed onto the FATMD. Data are collected by using an acquisition device (Model: NI 6366) connected to a laptop installed with LabVIEW.

To demonstrate that the frequency of the FATMD is adjustable, the first-order frequency of the FATMD under different spans is measured by the knocking method [46]. Then, the FATMD is tested with forced vibrations at different excitation frequencies and configurations. The direction of the applied excitation is vertical. The vibrations of the structure and the FATMD are also vertical.

5.2. Experimental Results

The first-order frequency of the FATMD at different adjusted spans is plotted in Figures 8 and 9, and the values of the frequency are listed in Table 1. L is length of the beam span in the FATMD. The figures show that the frequency of the FATMD decreases when the beam span increases. As shown in Table 1, when the beam has a radius (r) of 5 mm and a span of 0.5 m, the first-order frequency of FATMD is 38 Hz. When the span of the beam increases to 1 m, the first-order frequency of FATMD is 17.3 Hz. As shown in Table 1, when the beam has a radius of 6 mm and a span of 0.5 m, the first-order frequency of FATMD is 42.7 Hz. When the span of the beam increases to 1 m, the first-order frequency of FATMD is 20.1 Hz. The data, therefore, demonstrates that by changing of the beam span, the frequency of the FATMD can be adjusted.

To evaluate the vibration control performance of the FATMD, the vibration reduction ratio (J) is defined as described in equation (8).where a1 and a0 are the maximum vertical acceleration of the structure with and without the FATMD, respectively.

As shown in Figure 10, the vertical accelerations of the primary structure with and without the FATMD are plotted against time for the tested excitation frequencies. Table 2 lists the vibration reduction ratios of the FATMD under different excitation frequencies. In the experiment, the span was adjusted to make the frequency of the FATMD match the excitation frequency. When frequencies of the excitation and FATMD are both 26.5 Hz, the vibration reduction ratio of the FATMD is 96.1%, thus effectively suppressing the forced vibration of the structure. As shown in Figures 10(g)10(n), the FATMD can still effectively suppress the structural vibration at other high frequency excitations. For example, when the excitation frequency increases to 38.0 Hz, the vibration reduction ratio is 64.7%. In case where the frequency of the external excitation or structure changes, the beam span can be changed to adjust the frequency of the FATMD accordingly to preserve highly effective vibration suppression.

6. Vibration Control of a Long-Span Pedestrian Bridge with the FATMD

There is a pedestrian bridge in Shenyang, China, with the span of 49 m. The main structure of the bridge is a single-span steel box girder with the simple support at both ends. The deck width of the bridge is 3 m, and the linear density of the bridge is 1.179136 kg/m. The moment of inertia of the girder section is 0.0694 m4, and the elastic modulus is 200 GPa. The first frequency of the structure on the vertical direction is 2.2 Hz, which is close to the one of pedestrian walking. As a result, the large vibration can be felt when people walk through the bridge. In addition, the running of escalators connected to the bridge can also excite the vibration of the bridge. The vibration of bridge due to the walking of pedestrians and running of escalators can cause the uncomfortableness of people on the bridge and even result the fatigue damage of the structure. An FATMD is installed on the midspan of the pedestrian bridge to reduce the vertical vibrations under the excitations of pedestrians, escalators, and earthquakes. As shown in Figure 11, the FATMD can be installed under the guardrails of the pedestrian bridge, which will not affect the normal use of the bridge. The ratio of the total mass of the FATMD to the one of the bridge is 2%. Considering that the counterweight steel plates of the FATMD are relatively large, the stiffness and the span of the beam on the FATMD should be designed reasonably.

Figure 12 shows the simplified analysis model of the pedestrian bridge installed with an FATMD. The kinematic equations of the bridge with the FATMD are as follows:where EI is the flexural stiffness of the bridge. is the linear density of the bridge. m, c, and k are the mass, damping, and stiffness of the FATMD, respectively. y is the displacement of the bridge in the vertical direction. y0 is the vertical displacement of the midspan of the bridge. y1 is the displacement of the FATMD in the vertical direction. F is the external excitation. f is the control force exerted on the structure by the FATMD.

According to the mode analysis method, the vertical responses of the bridge can be expressed as follows:where Yn(t) is the generalized coordinate; ϕn(x) is the mode function.

Thus, the kinematic equations of the bridge with the FATMD can be simplified as follows:where

According to research by Poovarodom et al. [47], the effect of the crowd dynamic load on the pedestrian bridge can be converted into a concentration force at the midspan of the bridge as follows:where W is the average weight of pedestrians on the bridge and taken as 700 N in this paper; np is the number of people walking on the bridge at the same time, and the maximum value can be about 265 based on the area of the bridge deck; and fp is the frequency of pedestrian loads.

The vertical responses of the bridge with and without the FATMD are computed under different frequencies of the pedestrian load. The frequency of the FATMD is set to match the excitation frequency. Figure 13 shows the acceleration time history in the midspan of the bridge under the frequency of the pedestrian load is 2.2 Hz. The first 10 s is the forced vibration of the bridge under the pedestrian load, and the last 5 s is the free vibration of the bridge. It can be seen that the FATMD can effectively reduce the forced and the free vibration of the bridge. Figure 14 shows the acceleration envelope diagram of the bridge. A comparison of the two curves reveals the obvious vibration mitigation effect of the FATMD on the peak acceleration of the whole bridge. Table 3 lists the dynamic responses of the bridge with and without the FATMD under different frequencies of the pedestrian load. The results show that the FATMD can effectively suppress the maximum responses of the bridge under various frequencies of the pedestrian load, especially at the excitation frequency of 2.2 Hz, in which the vibration reduction rate is over 75%.

According to the code for design of antimicrovibration of a multistory factory floor (GB 50190-93) [48], the disturbing force of the escalators can be computed as follows:where m0 is the total mass of the escalators; e0 is the eccentricity; and ω0 is the working circular frequency of the escalators.

In this section, the frequency of external excitation generated by the escalator is 21 Hz and the amplitude of the excitation is 3216.3 N. The frequency of the FATMD is set to match the excitation frequency. Figure 15 shows the time history of the vertical acceleration in the midspan of the bridge under the action of escalators. Figure 16 shows the acceleration envelope diagram of the bridge. The results show that the FATMD can effectively reduce the vertical vibration of the bridge. The vibration reduction rate of the peak acceleration is 70.4%.

Furthermore, the vertical responses of the bridge with and without the FATMD are computed under three different seismic records (Table 4), including the Imperial Valley earthquake, the Kobe earthquake, and the Borrego earthquake. The frequency of the FATMD is set to match the natural frequency of the bridge. The peak ground accelerations (PGA) of each seismic record are, respectively, adjusted to be 0.2 g. Figure 17 shows the time history of the vertical acceleration in the midspan of the bridge under the three earthquakes. Table 5 lists the dynamic responses of the bridge with and without the FATMD under different earthquakes. It is concluded that the FATMD can effectively suppress the vertical accelerations and displacements in the midspan of the bridge under the three earthquakes.

7. Conclusions

In this paper, an FATMD composed of a simple supported beam with a mass is proposed to suppress high-frequency vibrations that can be generated by heavy machinery. Forced vibration experiments are conducted to verify the vibration suppression capabilities of the FATMD. Numerical and experimental analysis verified that the natural frequency of the FATMD can be adjusted and that the FATMD frequency decreases with the increased beam span. The FATMD can effectively reduce the structural vibrations at different tested high frequencies. The vibration suppression effect of the FATMD is stable between λ = 0.9–1.1, with λ = 1.0 being a relatively optimal value according to the curves. The vibration control effect of the FATMD increases with increased mass ratio and decreased damping ratio. Furthermore, the FATMD is an easily assembled structure that can be quickly adjusted for various natural frequencies, thus enabling the FATMD to be simpler to use than the normal TMD. The numerical results of the pedestrian bridge with an FATMD indicate that the FATMD has a significant effect on reducing the vibration of the pedestrian bridge under the excitations of pedestrians, escalators, and earthquakes.

However, the beam needs to remain in its elastic range for the FATMD to be effective, which limits the allowable range of stiffness that the FATMD can be tuned. Therefore, the FATMD may be detuned under high-intensity excitations, and its effectiveness may be significantly degraded. In the future work, the proposed FATMD will be optimally designed to improve its vibration control performance. The multiple FATMDs will be numerical and experimentally studied for the vibration control of structures with the consideration of multiple hazards, including the machine-, pedestrian-, earthquake-, and wind-induced vibrations.