Research Article
The Effect Analysis of Strain Rate on Power Transmission Tower-Line System under Seismic Excitation
Table 6
Maximum responses of the ground line.
|
Seismic wave |
Peak acceleration (m/s2) | Tension force (kN) | Vertical displacement (m) | Without considering strain rate | Considering strain rate | Without considering strain rate | Considering strain rate |
| El Centro | 6.0 | 17.239 | 17.292 | 3.509 | 3.513 | 8.0 | 17.847 | 17.851 | 3.501 | 3.494 | 10.0 | 18.651 | 18.589 | 4.428 | 4.377 | 12.0 | 19.282 | 19.496 | 4.546 | 4.608 | 14.0 | 19.183 | 19.512 | 4.276 | 4.315 | 15.0 | Collapse | 19.965 | Collapse | 4.716 | 16.0 | Collapse | Collapse | Collapse | Collapse |
| Kobe | 6.0 | 17.292 | 17.292 | 3.484 | 3.484 | 8.0 | 17.292 | 17.291 | 3.485 | 3.484 | 10.0 | 17.291 | 17.289 | 3.614 | 3.612 | 12.0 | 17.292 | 17.290 | 3.586 | 3.579 | 13.0 | 17.305 | 17.412 | 3.968 | 4.012 | 14.0 | Collapse | 17.460 | Collapse | 4.163 | 15.0 | Collapse | Collapse | Collapse | Collapse |
| Northbridge | 10.0 | 17.296 | 17.296 | 5.358 | 5.358 | 15.0 | 22.424 | 22.423 | 5.487 | 5.487 | 20.0 | 17.539 | 17.611 | 5.739 | 5.742 | 23.0 | 20.882 | 20.870 | 5.253 | 5.258 | 25.0 | 20.115 | 21.310 | 5.623 | 5.635 | 27.0 | 20.790 | 20.053 | 5.152 | 5.161 | 29.0 | Collapse | 21.136 | Collapse | 7.519 | 30.0 | Collapse | Collapse | Collapse | Collapse |
|
|