Power Quality Investigation of Distribution Networks Embedded Wind Turbines

Table 6

Average short-term flicker at buses 9, 11, 13, and 15 for different connection points of the considered DGs.

Bus numberWithout DGFSIGDFIG PMSG Synch
UPF

DG connected at bus 9
90.9380.6870.7270.7530.7450.487
111.2890.9901.0171.0511.0410.726
131.7361.3851.3911.4331.4211.045
151.7351.3841.3901.4321.4201.044

DG connected at bus 11
90.9380.6290.7010.7230.7180.439
111.2890.8920.9781.0141.0010.613
131.7361.2681.3431.3911.3750.906
151.7351.2661.3421.3901.3740.904

DG connected at bus 13
90.9380.5700.6700.6910.685 0.392
111.2890.8080.9350.9680.956 0.547
131.7361.1301.2861.3371.313 0.752
151.7351.1291.2851.3361.3120.751

DG connected at bus 15
90.9380.5790.664 0.6920.677 0.407
111.2890.8210.9280.9700.947 0.569
131.7361.1491.2791.3391.3040.783
151.7351.1001.2821.3471.2990.674