Abstract
This paper describes a new approach for power transformer differential protection which is based on the wave-shape recognition technique. An algorithm based on neural network principal component analysis (NNPCA) with back-propagation learning is proposed for digital differential protection of power transformer. The principal component analysis is used to preprocess the data from power system in order to eliminate redundant information and enhance hidden pattern of differential current to discriminate between internal faults from inrush and overexcitation conditions. This algorithm has been developed by considering optimal number of neurons in hidden layer and optimal number of neurons at output layer. The proposed algorithm makes use of ratio of voltage to frequency and amplitude of differential current for transformer operating condition detection. This paper presents a comparative study of power transformer differential protection algorithms based on harmonic restraint method, NNPCA, feed forward back propagation neural network (FFBPNN), space vector analysis of the differential signal, and their time characteristic shapes in Parkβs plane. The algorithms are compared as to their speed of response, computational burden, and the capability to distinguish between a magnetizing inrush and power transformer internal fault. The mathematical basis for each algorithm is briefly described. All the algorithms are evaluated using simulation performed with PSCAD/EMTDC and MATLAB.
1. Introduction
Power transformer is one of the most important components in power system, for which various types of protective and monitoring schemes have been developed for many years. Differential protection is one of the most widely used methods for protecting power transformer against internal faults. The technique is based on the measurement and comparison of currents at both side of transformer: primary and secondary lines. The differential relay trips whenever the difference of the currents in both sides exceeds a predetermined threshold. This technique is accurate in most of the cases of transformer internal faults however mal-operation of differential relay is possible due to inrush currents, which result from transients in transformer magnetic flux. The transients in transformer magnetic flux may occur due to energization of transformer, voltage recovery after fault clearance or connection of parallel transformers.
The existence of such current disturbances has made the protection of power transformers a challenging problem for protection engineers. Therefore, accurate classification of currents in a power transformer is need of this challenging problem, in preventing maloperation of the differential relay under different nonfault conditions including magnetizing inrush, over-excitation, external fault, and saturation of current transformers [1].
Since last 1960s, researchers have considerable interest in the area of digital protection of power apparatus [1]. The main features which have attracted researchers to investigate the feasibility of designing digital relays for power system protection are its speed of operation, dependability, stability, economy, flexibility, and possibility of integrating a digital relay into the hierarchical computer system within the substation and with the grid. Further the digital relay not only provides protection, but also is used for status monitoring of power apparatus. Moreover, with the application of artificial intelligence in protective devices, the decision-making capability of the relays is enhanced.
Early methods were based on desensitizing or delaying the relay to overcome the transients [2]. These methods are unsatisfactory nevertheless, since the transformer were exposed to long unprotected times. Improved security and dependability then was appreciated when the second harmonic content with respect to the fundamental one was introduced as an identification criterion, known as harmonic restraint differential protection [3]. However, some researchers reported the existence of a significant amount of the second harmonic in some winding faults [4, 5]. In addition, the new generations of power transformers use low-loss amorphous material in their core, which can produce inrush currents with lower harmonics contents and higher magnitudes [5]. In such cases, some authors have modified the ratio of second harmonic to fundamental restraining criterion by using other ratios defined at a higher frequency [6]. While other researchers proposed hidden Markovβs model [7], fuzzy-logic-based techniques [4, 8], wave shaped recognition technique [1, 9], and also artificial neural networks- (ANNs-) [10, 11] based learning pattern approach to get better classification accuracy, low computational burden, and fast response of the relay. However, these techniques depend on fixed threshold index (either in time domain or in frequency domain) and these may require large computational burden. Moreover, the performance of an ANN very much depends on its generalization capability, which in turn is dependent upon the data representation. One important characteristic of data representation is uncorrelated. In other words, a set of data presented to an ANN ought not to consist of correlated information. This is because correlated data reduce the distinctiveness of data representation and thus introduce confusion to the ANN model during learning process and hence, producing one that has low generalization capability to resolve unseen data. This suggests a need for eliminating correlation in the sample data before they are being presented to an ANN. This can be achieved by applying the principal Component Analysis (PCA) technique [12] onto input data sets prior to the ANN training as well as testing process and hence the neural network model becomes neural network principal component Analysis (NNPCA) model.
In this paper, a simple decision-making method based on the NNPCA is proposed for discriminating internal faults from inrush currents. The algorithm has been developed by considering different behaviors of the differential currents under internal fault and inrush condition. The NNPCA method extracts the relevant features from the differential current and reduces a training dataset to a lower dimension. The algorithm uses a data window of 12 samples per cycle. The algorithm also considers CT saturation and distinct scenarios such as changes in transformer load, source impedance, and remanent flux. All the mentioned conditions are simulated in PSCAD/EMTDC.
The accuracy in classification, speed of response, and computational burden of the harmonic restraint method, NNPCA, feed-forward back-propagation neural network (FFBPNN), and symmetrical component based method are compared in the presented work.
2. Neural Network Principal Component Analysis
Neural network principal component analysis (NNPCA) is basically an adaptive nonparametric method of extracting relevant information from confusing datasets [13]. It expresses data set in such a way as to highlight their similarities and differences. In 1982, Oja found a simple linear neuron model with a constrained Hebbian learning rule [13, 14]. For this work Hebbian learning is used. Generally, NNPCA is used for data reduction in statistical pattern recognition, signal processing, and image compression [13].
A typical architecture of NNPCA is shown in Figure 1. This network architecture has multilayer structure that is one input layer, one hidden layer, and one output layer. In back-propagation method a bounded and differentiable activation function is required. The sigmoid type activation function has all these properties making it popular in this training. In the present work due to these reasons, the hidden unit and output units use sigmoid-type of activation function. The architecture is defined by corresponding weights and connection scheme.
For a -dimensional input data vectors to , output of neural network is given by (1) as where Connecting weight, ,β Nonlinear sigmoid activation function.
The weight adapting (2) for neurons is as following: whereβ = learning rate,β and .
3. Simulation and Training Cases
Power transformer operating conditions may be classified as(i)normal condition,(ii)magnetizing inrush/sympathetic inrush condition,(iii)over-excitation condition,(iv)internal fault condition,(v)external fault condition.
In the normal condition, rated or less current flows through the transformer. In this condition normalized differential current is almost zero (only no load component of current). Whenever there is large and sudden change in the input terminal voltage of transformer, either due to switching-in or due to recovery from external fault getting, a large current is drawn by the transformer from the supply. As a result, the core of transformer gets saturated. This phenomenon is known as magnetizing inrush, or in other words, inrush can be described by a condition of large differential current occurring when either the transformer is just switched on or the system recovers from an external fault. Similar condition occurs when transformer is energized in parallel with another transformer that is already in service; it is known as βsympathetic inrushβ condition. Among the various faults in transformer, phase-to-ground fault occurs most frequently. On the basis of fault current, phase-to-ground fault, for protective device operation view point, may be further classified as(i)heavy faults,(ii)medium level fault and,(iii)low level fault.
In all the cases, the abnormality nature is almost same but the magnitudes of currents resulting due to that are quite different. If the level of fault can be detected and accordingly protective action is taken, then the major damage to the protected element can be prevented.
A simulation software PSCAD/EMTDC is used to generate the training and testing signals under different operating conditions of transformer that are normal, overexcitation, magnetizing inrush, sympathetic inrush, and fault (phase-to-phase, phase-to-ground, and external fault) conditions. While simulating different operating conditions of transformer, energization angle, remanent flux in the core and load condition are considered as the magnitude and the wave-shape of differential current depends on these factors. Energization angle is varied from 0 to 360 degrees in interval of 30 degrees and remanent flux varying from 0% to 80% of the peak flux linkages generated at rated voltage with no-load and full-load conditions to generate training signals while, in case of testing signals energization angle is varied in interval of 15 degrees. The desired remanence can be set in unenergized transformer with controlled DC current sources in PSCAD/EMTDC model [15]. As transformers are not expected to be subjected to more than 15% overvoltage hence, overexcitation condition is simulated by applying 115% of the rated voltage at full load.
Three-phase transformers of 315βMVA at 400/220βkV, 200βMVA at 220/110βkV and 160βMVA at 132/220βkV, are modeled by using PSCAD/EMTDC. For the simulation of these transformers through PSCAD/EMTDC, the realistic data obtained from the M P State Electricity Board, Jabalpur India, is used. Typical connection of a 3-phase transformer of 315βMVA, 400/220βkV, 50βHz, delta-star grounded connection is shown in Figure 2. In the high side, there is a source 200βMVA, 400βkV, and 10 as internal impedance; in low side, there is a three-phase load of 285βMW and 137.28βMVAR. In case of internal fault condition, training and testing relaying signal is obtained by simulating fault varying from 1% to 99% of the power transformer winding turns, whereas in case of phase-to-ground fault condition, the fault is simulated at different location as 5%, 15%, 25%, 40%, 50%, and 100% (i.e., terminal fault) of the winding. Figure 3 shows a typical PSCAD/EMTDC transformer model required to simulate internal faults (turn to turn, phase to ground, and phase to phase) at different location of transformer winding from the neutral end of the windings. In this model MVA rating, voltage rating, base frequency, leakage reactance, magnetizing current, fault location (in %), and so forth can be defined.
(a)
(b)
In [16] (3) is proposed to avoid saturation in CT and reduce the impact over the protective relays. However, in this work a reduced CT ratio as 600β:β5 and 1200β:β5 is selected to allow distortion in the waveform of the differential current as part of the stable state operation.
Consider where , is maximum fault current per unit of CT rating, is CT burden per unit of standard burden, and is the reactance/resistance ratio of power system, respectively.
The test signals (typical magnetizing inrush and internal fault conditions) obtained by simulation of transformer are shown in Figures 4 to 5. The simulation was done at the rate of 12 samples per cycle of 50βHz AC supply in view of reported experience on different digital relay deigns [17]. The developed fault detection algorithm was implemented in MATLAB on Intel P-IV processor-based desktop with front-side bus (FSB) speed of 400βMHz.
4. Implementation of NNPCA-Based Algorithm, Results and Analysis
The differential current is typically represented in discrete form as a set of 12 uniformly distributed samples obtained over a data window of one cycle of fundamental frequency signal, that is, the sampling rate is 12 samples per cycle. These 12 samples are called a βpattern.β The sliding data window, consisting, one most recent and other of previous windows is used to generate patterns under above-mentioned power transformer operating conditions.
Each row of the input training matrix represents one pattern while corresponding row of target matrix represents desired output. Suppose that the inrush condition signal is characterized by the following sequence:
The first row of inrush matrix takes 12 samples of (i.e., to ), and then second row elements are from to and so on until all the elements of are completed. In a similar fashion, the internal fault condition matrix elements are also arranged for training and testing. The complete training matrix contains both inrush and fault patterns.
Two types of principal component analysis (PCA) data processors had been used for the purpose. The first one is called the preprocessor PCA, which is responsible for preprocessing input training data, to eliminate correlation in training patterns. The second is called postprocessor PCA, used to transform the validation and test datasets according to their principal components. The implementation was carried out with aid of built-in function supported by MATLAB Neural Network Toolbox.
In proposed NNPCA architecture three-layered structure is used. The input layer has 12 neurons. The hidden layer consists of 11 neurons, as the number of neurons in hidden layer increases, the error decreases but after certain number of neurons it increases again, and in this case the minimum error is obtained for 11 neurons in the hidden layer. Therefore, the number of neurons in the hidden layer is optimal for this application. As only single output (trip or not) is required, the output layer consists of just one neuron. After much experimentation on various neural network architectures, the presented model is proposed which has lesser neurons in all three layers.
To differentiate between the fault and inrush conditions, the inrush condition is indicated by β0β and β1β indicates the fault condition. Out of 925 sets of data (patterns), 777 pattern sets are used to train the proposed NNPCA model. Out of these 777 pattern sets, 444 pattern sets are for the inrush (including sympathetic inrush patterns) and 333 are for the internal fault. The remaining 148 sets (which are not made part of training sets) are used to test the networkβs generalization ability. These 148 test exemplar pattern sets contain internal fault and inrush condition only as these two conditions are very difficult to discriminate as compared to other operating conditions such as external fault, overexcitation, and normal condition. Out of 148 test patterns, 74 test sets were inrush patterns and remaining 74 test sets were internal fault patterns. The inrush test patterns consist of sympathetic inrush patterns and magnetizing inrush patterns at different switching-in angles, while internal fault test patterns are made up of phase-to-ground fault and phase-to-phase fault at different locations.
After the NNPCA model had been trained, their generalization performances were calculated based on the mean absolute error (MAE) given by where is the total number of test patterns, is the actual output, and is the NNPCAβs estimated output for the th test pattern.
Flow chart of the proposed algorithm (Figure 6) clearly indicates the steps for discriminating different operating conditions of power transformer. The external fault and normal operating condition are ruled out based on amplitude of two consecutive peaks of the operating signal. The over-excitation condition is determined by comparing voltage-to-frequency ratio with the rated voltage-to-frequency ratio. If this condition does not exist, then inrush and internal fault conditions are checked by NNPCA model. It gives tripping signal only if internal fault condition is detected.
For different conditions of the test set, fault current magnitude, load condition, remanent flux, and switching angle are changed to investigate the effects of these factors on the performance of the proposed algorithm. Since the wave-shape of inrush current changes with variation of switching-in instant of transformer, hence it is varied between 0 to 360 degrees. Similarly, due to the presence of the remanence flux, magnitude of inrush current may be as high as 2 to 6 times of inrush current without that, although the wave-shape remains same. It is found that the NNPCA classifier-based relay is stable even with such high magnitude of inrush current caused by remanence flux whereas, the conventional harmonic-based relay may maloperate due to such high magnitude of inrush current [4, 18]. A rigorous experimentation has been made to evaluate performance of the NNPCA model. The proposed NNPCA model is successfully tested using relaying signals obtained by modeling the transformer on PSCAD/EMTDC and simulating various operating conditions as mentioned in the previous section. The results of proposed algorithm are shown in Table 1 (Tables 1 and 1). All the test patterns were accurately classified by the NNPCA model (i.e., 100% accuracy in classification). This detection is without any false positive or negative (as given in (6)); thus NNPCA has good generalization capability to distinguish between magnetizing inrush and internal fault condition of transformer. From Table 1, it is clear that the accuracy in classification of NNPCA is better than the FFBPNN based classifier in spite of using the same topology, same tuning parameter, and training algorithm as used in case of NNPCA method.
We halve the following: Table 2 presents the number of postdisturbance samples required for decision making by the proposed NNPCA-based transformer differential protection algorithm. In internal fault cases, it requires 6 samples (and 9 samples for light internal fault case) after the fault occurrence that means about 10β15βms are required for the fault detection while in case of inrush condition only 8 samples are required, that is, 13.33βms. However, it is observed that the relay operation is independent from the harmonic present in the operating signal, and therefore no filtering is required in this method. In addition to that it does not require any threshold index to discriminate between the inrush and internal fault condition of transformer.
The same power transformers are tested with symmetrical component method and harmonic restraint (HR) method based on discrete fourier transform (DFT) (see the section Appendix).
Parkβs vector is a function of positive-, negative-sequence currents and independent of zero-sequence currents. When plotting vectors in Parkβs space, is represented in the horizontal axis, while component is plotted in the vertical axis. The secondary winding currents are not affected by the fault or inrush if the vector is plotted in Parkβs space. Internal faults and inrush currents may be characterized by particular plot shape of . When Parkβs vector is plotted in Parkβs space, transformer internal fault and inrush currents are clearly distinguished from their plot shape as shown in Figures 7 and 8. From Figures 7 and 8, it is observed that the plots are symmetrical for internal fault condition and asymmetrical for inrush condition. The shape characterizations in two groups are not dependent on the type of differential signal (fault or inrush). The use of Parkβs vectors reduces appreciably the computation requirements, since their values are directly calculated from a scalar matrix product.
(a)
(b)
(c)
(a)
(b)
(c)
Discrete fourier-transform- (DFT-) based harmonic restraint method is implemented, to compare performance of the proposed optimal NNPCA-based algorithm in power transformer differential protection. Figure 9 shows the ratio of second harmonic to fundamental of the differential current under typical magnetizing inrush and internal fault conditions, respectively. During one cycle under internal fault condition, the ratio of the second harmonic is quite high and in the same range as in case of magnetizing inrush condition. Therefore, it is difficult to discriminate between internal fault and inrush conditions merely setting a preset threshold. From Figure 9, it is also clear that the ratio values are fluctuating, which create problem to decide a preset threshold. Moreover, due to the presence of second harmonic during internal fault condition, digital relay will take longer time to make trip decision (one cycle or more than one cycle). In contrast, the optimal NNPCA based method is able to detect such a fault in 6βms (half cycle or with in half cycle) and in light internal fault cases, it requires 9 samples after the fault occurrence that means about 15βms are required for the fault detection while in case of inrush condition only 8 samples are required, that is, 13.33βms. However, it is observed that the relay operation is independent from the harmonic present in the operating signal, and therefore no filtering is required in this method.
However, the harmonic restraint method and symmetrical component method are capable to discriminate between these two conditions but do not seem to be intelligent to take decision in case of fluctuating ratio of second harmonic to fundamental of the differential current due to different loading conditions, severity of internal faults, switching-in angles, and so forth, and hence maloperation of relay will occur. In case of symmetrical component method, Parkβs space plot is to be analyzed for its symmetry than only relay can take decision. Moreover, these methods take more time to take decision as compared to NNPCA-based transformer differential method and depend on the harmonic contain present in the relaying signal.
5. Conclusion
This paper presents a novel intelligent approach based on neural network principal component analysis (NNPCA) model to solve the problem of distinguishing between transformer internal fault and magnetizing inrush condition. The performance of NNPCA-based method is compared with feed-forward back-propagation neural network (FFBPNN), harmonic restraint method, and Parkβs plot method.
The proposed NNPCA algorithm is based on waveform identification technique which is more accurate than traditional harmonic-restraint-based technique, especially in case of modern power transformers which use high-permeability low-coercion core materials. The conventional harmonic restraint technique may fail because high second harmonic components may be generated during internal faults and low second harmonic components during magnetizing inrush with such core materials.
However, the harmonic restraint method and symmetrical component method are capable to discriminate between these two conditions but do not seem to be intelligent to take decision in case of fluctuating ratio of second harmonic to fundamental of the differential current. Moreover, these methods take more time to take decision as compared to NNPCA-based transformer differential method.
The proposed optimised NNPCA technique is simple in architecture, fast in operation, and robust. The present neural network model issues tripping signal in the event of internal fault within 6β15βms of fault occurrence. The method is also immune from the DC offset in relaying signals due to saturation of CT core in the event of internal or external fault. Moreover, the NNPCA-based algorithm has 100% accuracy in classification which is not possible to achieve by using FFBPNN in the application of power transformer differential application.
Appendix
A. Discrete Fourier Transform (DFT) Algorithm
Any continuous waveform , having a finite energy in the interval , can be represented in the interval as a Fourier series: with coefficients where is the dc component (average value) and and are the sine and cosine components of the Fourier coefficients, respectively. If the waveform is sampled at time , space apart, so that there are samples, then for samples 1 to N, the coefficients and in (A.2) can be rewritten as where are the discrete sampled current signals and .
Hence, for 12 samples per data window, 12 Fourier coefficients will have an array size of . Both sine and cosine terms will have an array size of . The differential current is analyzed in terms of its Fourier series, and amplitude of each harmonic can be found as follows: where = Fourier coefficients and .
For power transformers protection, , , and represent the Fourier coefficients of the fundamental, the second harmonic, and the fifth harmonic component, respectively, of current waveform. For a three-phase transformer, the combined harmonic components of the differential currents are where , and 5.
B. Symmetrical Component Approach [6]
A function of instantaneous line currents , the current Parkβs vector components are obtained as follows: where the transformation matrix is defined as
Parkβs vector is defined as the vector difference between Parkβs vectors obtained by means of (B.1) and (B.3) is used. And it is analytically demonstrated that the parkβs vector is related to the time-dependent symmetrical components as follows: where is the instantaneous rms value (i.e., since the rms of the current changes over the time during transients and this values is considered to be recalculated for every instant) of the positive sequence current for the differential current, is the instantaneous rms value of the negative sequence current for the differential current, is the phase angle of the positive sequence current in line is the phase angle of the negative sequence current in line , the time, ββis the supply fundamental frequency, ββis the order of the considered harmonic, and superscript () refers to the th order harmonic value.
Parkβs vectors are obtained from the instantaneous line currents by means of the [C] matrix of (B.2). Thus, the transformation of th-order harmonic time-dependent symmetrical components into Parkβs vector components is achieved as follows:
The plot in Parkβs plane of the Ξ± and Ξ² components accounting for all the harmonics is then
In Parkβs space, is represented in the horizontal axis, while component is plotted in the vertical axis.