Table of Contents
Advances in Electrical Engineering
Volume 2015, Article ID 685943, 15 pages
http://dx.doi.org/10.1155/2015/685943
Research Article

Effect of DC Link Control Strategies on Multiterminal AC-DC Power Flow

Department of Electrical Engineering, Delhi Technological University, Delhi 110042, India

Received 20 September 2014; Accepted 18 March 2015

Academic Editor: George E. Tsekouras

Copyright © 2015 Shagufta Khan and Suman Bhowmick. This is an open access article distributed under the Creative Commons Attribution License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.

Abstract

For power-flow solution of power systems incorporating multiterminal DC (MTDC) network(s), five quantities are required to be solved per converter. On the other hand, only three independent equations comprising two basic converter equations and one DC network equation exist per converter. Thus, for solution, two additional equations are required. These two equations are derived from the control specifications adopted for the DC links. Depending on the application, several combinations of valid control specifications are possible. Each combination of a set of valid control specifications is known as a control strategy. The number of control strategies increases with an increase in the number of the DC terminals or converters. It is observed that the power-flow convergence of integrated AC-MTDC power systems is strongly affected by the control strategy adopted for the DC links. This work investigates the mechanism by which different control strategies affect the power-flow convergence pattern of AC-MTDC power systems. To solve the DC variables in the Newton-Raphson (NR) power-flow model, sequential method is considered in this paper. Numerous case studies carried out on a three-terminal DC network incorporated in the IEEE-300 bus test system validate this.