Siting and Sizing of DG in Medium Primary Radial Distribution System with Enhanced Voltage Stability
Table 2
Estimation of power loss if the substation and DG are scheduled for different values.
| Case | DGcapacity, MW | Total load (MW) | S.S.supply, MW | Power Loss, MW | Power loss reduction (%) | Voltage profile | As per TVD | Scheduled | As per TVD | Scheduled | Min | Max |
| Case 1 | 25 | 25 |
50 | 25 | 25 | 2.08 | 60 | 0.97 @ 3 | 1.000 @ 6 | 30 | 20 | 2.22 | 55 | 0.94 @ 3 | 1.000 @ 6 | 20 | 30 | 2.19 | 52 | 0.94 @ 3 | 1.002 @ 6 |
| Case 2 | 28 | 28 |
50 | 22 | 22 | 3.52 | 68 | 0.96 @ 3 | 1.001 @ 6 | 35 | 15 | 3.8 | 58 | 0.94 @ 2 | 1.005 @ 6 | 15 | 35 | 3.75 | 57 | 0.93 @ 3 | 1.008 @ 5 |
| Case 3 | 22 | 22 |
50 | 28 | 28 | 2.072 | 61 | 0.95 @ 3 | 1.000 @ 6 | 32 | 18 | 2.12 | 56 | 0.93 @ 3 | 1.051 @ 5 | 18 | 32 | 2.23 | 56 | 0.93 @ 3 | 1.038 @ 5 |
|
|