Research Article

Introducing MRAC-PSS-VI to Increase Small-Signal Stability of the Power System after Wind Power Integration

Table 2

The eigenvalues of the system.

ModeWithout the DFIGWith the DFIGDominant states
λf/Hzξ (%)λf/Hzξ (%)

1−0.651 ± j6.5471.0429.898−0.651 ± j6.5471.0429.897G1, G2
2−0.619 ± j6.3921.0179.645−0.620 ± j6.3931.0179.658G3, G4
3−0.299 ± j3.1350.4999.526−0.300 ± j3.1350.4999.532G1–G4
4−0.513 ± j3.0590.48716.539G1–G4, DFIG