Research Article

Introducing MRAC-PSS-VI to Increase Small-Signal Stability of the Power System after Wind Power Integration

Table 3

The eigenvalues of the system with different controllers.

ModeWithout the controllerWith the PSSDominant states
λf (Hz)ξ (%)λf (Hz)ξ (%)

1−0.651 ± j6.5471.0429.897−0.651 ± j6.5471.0429.897G1, G2
2−0.620 ± j6.3931.0179.658−0.615 ± j6.3901.0179.580G3, G4
3−0.300 ± j3.1350.4999.532−0.368 ± j3.1800.50611.521G1–G4
4−0.513 ± j3.0590.48716.539−0.396 ± j3.3590.53511.710G1–G4, DFIG

ModeWith the PSS-VIWith MRAC-PSS-VIDominant states
Λf/Hzξ (%)λf/Hzξ (%)

1−0.651 ± j6.5471.0429.897−0.670 ± j6.3591.01210.479G1, G2
2−0.620 ± j6.3931.0179.658−1.778 ± j6.1060.97227.954G3, G4
3−0.298 ± j3.1370.4999.464−0.304 ± j3.0330.4839.968G1–G4
4−0.689 ± j3.4820.55419.417−0.967 ± j3.5460.56426.305G1–G4, DFIG