| Mode | Without the controller | With the PSS | Dominant states | λ | f (Hz) | ξ (%) | λ | f (Hz) | ξ (%) |
| 1 | −0.651 ± j6.547 | 1.042 | 9.897 | −0.651 ± j6.547 | 1.042 | 9.897 | G1, G2 | 2 | −0.620 ± j6.393 | 1.017 | 9.658 | −0.615 ± j6.390 | 1.017 | 9.580 | G3, G4 | 3 | −0.300 ± j3.135 | 0.499 | 9.532 | −0.368 ± j3.180 | 0.506 | 11.521 | G1–G4 | 4 | −0.513 ± j3.059 | 0.487 | 16.539 | −0.396 ± j3.359 | 0.535 | 11.710 | G1–G4, DFIG |
| Mode | With the PSS-VI | With MRAC-PSS-VI | Dominant states | Λ | f/Hz | ξ (%) | λ | f/Hz | ξ (%) |
| 1 | −0.651 ± j6.547 | 1.042 | 9.897 | −0.670 ± j6.359 | 1.012 | 10.479 | G1, G2 | 2 | −0.620 ± j6.393 | 1.017 | 9.658 | −1.778 ± j6.106 | 0.972 | 27.954 | G3, G4 | 3 | −0.298 ± j3.137 | 0.499 | 9.464 | −0.304 ± j3.033 | 0.483 | 9.968 | G1–G4 | 4 | −0.689 ± j3.482 | 0.554 | 19.417 | −0.967 ± j3.546 | 0.564 | 26.305 | G1–G4, DFIG |
|
|