Research Article

Effect of Condenser Fouling on Performance of Vapor Compression Refrigeration System

Table 3

Comparison of present model with work of Qureshi and Zubair [9] for condenser fouling of refrigerant R134a (Te = 0°C).

Reduction in (%)Change in (%)Change in (%) Change in COP (%)Error (%) in COP with reference to Qureshi and Zubair [9]
Qureshi and Zubair [9]Current modelQureshi and Zubair [9]Current modelQureshi and Zubair [9]Current model

00000000
10−0.901−0.9070.7310.714−1.620−1.609−0.67
20−2.065−2.0701.6651.650−3.669−3.659−0.27
30−3.611−3.6112.8802.873−6.309−6.303−0.09
40−5.725−5.7484.4794.447−9.782−9.761−0.21
50−8.761−8.7676.7106.690−14.499−14.49−0.06