Research Article
Power Quality Investigation of Distribution Networks Embedded Wind Turbines
Table 3
DGs connection point and penetration ratio effect on the distribution system steady state voltages.
| DG PCC | Number of DG units | FSIG | with DFIG | UPF with PMSG | | At bus | | At bus | | At bus |
| Bus 3 | 1 | 0.948 | 15 | 0.947 | 15 | 0.949 | 15 | 2 | 0.950 | 15 | 0.948 | 15 | 0.953 | 15 | 3 | 0.952 | 15 | 0.948 | 15 | 0.956 | 15 | 4 | 0.954 | 15 | 0.948 | 15 | 0.959 | 15 |
| Bus 5 | 1 | 0.951 | 15 | 0.961 | 15 | 0.954 | 15 | 2 | 0.955 | 15 | 0.968 | 15 | 0.961 | 15 | 3 | 0.959 | 15 | 0.971 | 15 | 0.968 | 15 | 4 | 0.962 | 15 | 0.973 | 15 | 0.973 | 15 |
| Bus 7 | 1 | 0.951 | 15 | 0.966 | 15 | 0.955 | 15 | 2 | 0.956 | 15 | 0.973 | 15 | 0.963 | 15 | 3 | 0.960 | 15 | 0.977 | 15 | 0.971 | 15 | 4 | 0.963 | 15 | 0.979 | 15 | 0.977 | 15 |
| Bus 9 | 1 | 0.952 | 15 | 0.970 | 15 | 0.957 | 15 | 2 | 0.959 | 15 | 0.979 | 15 | 0.966 | 15 | 3 | 0.962 | 15 | 0.983 | 15 | 0.975 | 15 | 4 | 0.965 | 15 | 0.985 | 15 | 0.982 | 15 |
| Bus 11 | 1 | 0.953 | 15 | 0.975 | 15 | 0.959 | 15 | 2 | 0.960 | 15 | 0.984 | 15 | 0.970 | 15 | 3 | 0.964 | 15 | 0.988 | 15 | 0.979 | 15 | 4 | 0.966 | 15 | 0.990 | 15 | 0.987 | 15 |
| Bus 13 | 1 | 0.954 | 15 | 0.979 | 15 | 0.961 | 15 | 2 | 0.961 | 15 | 0.987 | 13 | 0.973 | 15 | 3 | 0.965 | 15 | 0.989 | 12 | 0.982 | 10 | 4 | 0.965 | 15 | 0.989 | 12 | 0.986 | 9 |
| Bus 15 | 1 | 0.955 | 14 | 0.977 | 11 | 0.962 | 13 | 2 | 0.959 | 13 | 0.981 | 11 | 0.972 | 12 | 3 | 0.959 | 13 | 0.982 | 10 | 0.977 | 11 | 4 | 0.948 | 13 | 0.979 | 10 | 0.978 | 10 |
|
|