Power Transformer Fault Severity Estimation Based on Dissolved Gas Analysis and Energy of Fault Formation Technique
Table 6
Comparison of different fault detecting diagnostic approaches with respect to fault type.
| Fault type | Total faulty cases | Fuzzy Duval-EWR method [22] | Fuzzy IEC-EWR method [20] | Proposed fuzzy key gas-TFE method | Correct diagnosis | % accuracy | Correct diagnosis | % accuracy | Correct diagnosis | % accuracy |
| Partial discharges | 7 | 7 | 100 | 7 | 100 | 7 | 100 | Discharges of low energy | 11 | 10 | 91.9 | 10 | 91.9 | 9 | 81.8 | Discharges of high energy | 22 | 21 | 95.9 | 21 | 95.9 | 20 | 90.9 | Low-level thermal faults | 13 | 12 | 92.3 | 13 | 100 | 13 | 100 | Medium-level thermal faults | 19 | 16 | 84.2 | 16 | 84.2 | 15 | 78.9 | High-level thermal faults | 12 | 10 | 83.3 | 10 | 83.3 | 9 | 75 |
|
|