Research Article

Calculation of a Health Index of Oil-Paper Transformers Insulation with Binary Logistic Regression

Table 13

Data in [1].

Number
(ppm)

(mgKOH/g)

(kV)

(%)

(ppm)

(mg/L)

121.70.02432.50.0754830.86
226.90.09840.50.8942540.65
314.50.033580.14780.26
421.20.22648.70.4242155.53
5100.01750.1111260.06
615.50.075710.143380.53
716.80.16770.10.2551490.78
8150.09267.80.211280.69
9170.03562.70.11390.21
10300.08837.60.3531970.31
1116.20.18125.50.201358.76
12150.15537.50.182537.29
1316.80.11525.60.174789.6
14150.2157.20.22536.69
1527.60.08930.40.1283365.12
1623.50.10645.80.207300.24
1724.80.01229.90.0685041.68
1823.60.0739.20.203220.5
1930.50.07328.7673015.7
2018.40.06364.50.243690.15
2121.10.01928.40.0251440.02
228.10.0166.90.042710.05
2319.60.21641.10.264487.54
2460.0167.60.1264270.08
2518.40.15237.20.299811.14
2611.10.03267.20.0891190.04
2721.50.14760.80.9381680.92
287.50.1670.10.448100.06
29130.09151.60.36980.32
3035.70.22941.40.639241.07

, , , , , and represent water content in oil, total acidity of oil, oil breakdown voltage, dissipation factor, DCG, and 2-Furfuraldehyde content, respectively.