Tab 1
/
Research Article
Area-Based COI-Referred Rotor Angle Index for Transient Stability Assessment and Control of Power Systems
Table 1
Typical time limits for the operation of generators at frequencies below their rated frequency.
Percentage of rated frequency at full load (%)
Maximum permissible time (minutes)
99.0
Continuous
97.3
90
97.0
10
96.0
1