Research Article

Case Study of Remaining Service Life Assessment of a Cooling Water Intake Concrete Structure in Indonesia

Table 9

Corrosion initiation time and concrete deterioration rate.

TrainA/BC/DE/FG/H
ScenariosWorst caseAverage caseWorst caseAverage caseWorst caseAverage caseWorst caseAverage case

Built (year)1977198219871995
Operated (year)1979198419891997
Compressive strength (MPa)22.224.937.839.635.137.441.141.1
Cover thickness (mm)508332.56553744461.7
Corrosion initiation (year)1.8213.915.7335.5610.2526.136.9926.13
Corrosion rate (mm/year)0.2290.1000.1180.0560.0810.0530.0790.056
Remaining capacity at 2013 (%)44%83%77%100%90%100%94%100%
Remaining capacity in 20 year (%)21%67%59%93%77%92%80%92%