Improved Thermally Activated Building System Design Method Considering Integration of Air Systems

Table 2

Average cooling power comparison of standard and simulation.

Simulation casesTABS average cooling power from ISO 11855 (W/m2)TABS average cooling power from simulation (W/m2)

TABS 24 hrs (21.3°C)TABS only2018.3
TABS with CAV10.1
TABS with VAV14.4
TABS with DOAS16.3

TABS 12 hrs (19.4°C)TABS only3849.3
TABS with CAV33.6
TABS with VAV42.4
TABS with DOAS45.8

TABS 8 hrs (17.8°C)TABS only5868.4
TABS with CAV53.0
TABS with VAV61.7
TABS with DOAS65.0