Research Article
Improved Thermally Activated Building System Design Method Considering Integration of Air Systems
Table 4
Comparison of supply water temperature and average cooling power with the proposed method.
| Simulation cases | Supply water temperature in standards (°C) | Supply water temperature with proposed adjustment coefficient (°C) | Expected average cooling power (W/m2) | Average cooling power with supply water temperature calculation in standards (W/m2) | Average cooling power with proposed adjustment coefficient (W/m2) |
| TABS 24 hrs | TABS with DOAS office space | 20.6 | 19.4 | 16.8 | 13.1 | 15.7 | TABS with DOAS lecture room | 16.7 | 14.6 | 28.9 | 24.9 | 30.2 |
|
|