Research Article

Improved Thermally Activated Building System Design Method Considering Integration of Air Systems

Table 4

Comparison of supply water temperature and average cooling power with the proposed method.

Simulation casesSupply water temperature in standards (°C)Supply water temperature with proposed adjustment coefficient (°C)Expected average cooling power (W/m2)Average cooling power with supply water temperature calculation in standards (W/m2)Average cooling power with proposed adjustment coefficient (W/m2)

TABS 24 hrsTABS with DOAS office space20.619.416.813.115.7
TABS with DOAS lecture room16.714.628.924.930.2