Research Article

Semiautomatic Generation of Code Ontology Using ifcOWL in Compliance Checking

Table 2

Code clauses in experiment.

ClausesContentDomainProcessing method

7.1.3The design service life of the main structure of the ballastless track and the concrete track sleepers should not be less than 100 years.TrackAttribute value and property extension
8.2.5The subgrade bed shall be divided into surface layer and bottom layer. The thickness of surface layer shall not be less than 0.5 m, and that of bottom layer shall not be less than 1.5 m.SubgradeEntity extension
9.4.4Signs for guidance, accident evacuation, and passenger service should be set up inside the station.Station architectureEntity extension
13.2.31The room with gas fire extinguishing should be equipped with mechanical ventilation system, and the exhausted gas must be directly discharged to the groundVentilation and air conditioningAttribute value and property extension
14.2.5.5The water supply pipe shall not pass through the substation, communication signal room, control room, distribution room and other electrical rooms.Water supply and drainageAttribute value extension
19.4.5Fire detectors should be installed in the public area of station hall floor, public area of platform floor, public area of transfer, various equipment rooms, warehouses, duty rooms, offices, entrance and exit, power distribution rooms in underground stations.Automatic fire alarmAttribute value extension
22.6.3The data line shall be halogen-free, low smoke and flame-retardant shielded cable.Passenger information systemAttribute value and property extension
24.8.1The control center should be equipped with automatic fire alarm, building automation system, fire accident broadcast, automatic fire extinguishing, water firefighting, smoke control systems.Operation control centerAttribute value extension
25.1.15When the rated speed of elevator is 0.5 m/s and the lifting height is not more than 6 m, the number of upper and lower horizontal steps shall not be less than 2; when the rated speed is 0.5 m/s and the lifting height is greater than 6 m, the number of upper and lower horizontal steps shall not be less than 3; when the rated speed is greater than 0.65 m/s, the number of upper and lower horizontal steps shall not be less than 3.Passenger transport equipmentProperty extension
28.2.5Two fire compartments should be separated by a firewall with a fire resistance rating of not less than 3 h and a class A fire door. When the firewall is equipped with an observation window, a class a fire window should be used. The slab in the fire compartment should have a fire resistance rating of not less than 1.5 h.Disaster preventionAttribute value and property extension