Research Article

Monitoring and Prediction Analysis of Settlement for the Substation on Soft Clay Foundation

Table 2

Differential settlement between any two adjacent measuring points.

Two adjacent measuring pointsDistance (m)Measured differential settlement (mm)Allowable differential settlement (mm)

S1 and S2263.3478
S2 and S3265.4478
S3 and S4269.3678
S5 and S6267.6878
S6 and S7262.8378
S7 and S8266.1478
S1 and S8131.6839
S2 and S7131.1239
S3 and S6131.4939
S4 and S5130.1939