Research Article

Investigations on Incipient Fault Diagnosis of Power Transformer Using Neural Networks and Adaptive Neurofuzzy Inference System

Table 2

Fault diagnosis based on Rogers ratio codes.

ijklDiagnosis

0000Normal deterioration
5000Partial discharge
1-2000Slight overheating <150°C
1-2100Overheating 150°–200°C
0100Overheating 200°–300°C
0010General conductor overheating
1010Winding circulating currents
1020Core and tank circulating currents, overhead joints
0001Flashover without power following through
001-21-2Arc with power following through
0022Continuous sparking to floating potential
5001-2Partial discharge with tracking