Research Article
Improved Coyote Optimization Algorithm for Optimally Installing Solar Photovoltaic Distribution Generation Units in Radial Distribution Power Systems
Table 19
The best solutions and the total capacity of PVDGUs found by nine implemented methods for the IEEE 69-bus distribution network in Case
4.
| Method | The best solution | THD/IHD (max) with PVDGUs (%) | Volt (min/max) with PVDGUs (pu) | Total power losses with PVDGUs (kW) |
| BBO | Bus: 18; size: 0.2705 MW Bus: 23; size: 1.4079 MW Bus: 63; size: 1.5097 MW Bus: 55; size: 0.6023 MW | 2.778/1.795 | 0.984/1.044 | 135.120 | GA | Bus: 66; size: 0.0256 MW Bus: 09; size: 1.0095 MW Bus: 60; size: 1.9590 MW Bus: 17; size: 0.1785 MW | 2.899/1.873 | 0.982/1.000 | 82.736 | PSO | Bus: 17; size: 0.1639 MW Bus: 09; size: 0.9271 MW Bus: 69; size: 0.0089 MW Bus: 60; size: 2.0000 MW | 3.011/1.945 | 0.982/1.000 | 83.398 | SFO | Bus: 63; size: 1.7029 MW Bus: 21; size: 0.0497 MW Bus: 10; size: 1.3583 MW Bus: 19; size: 0.4482 MW | 4.648/3.000 | 0.986/1.005 | 81.975 | SSA | Bus: 24; size: 0.6126 MW Bus: 61; size: 0.8376 MW Bus: 60; size: 1.6438 MW Bus: 02; size: 0.0067 MW | 4.599/2.961 | 0.994/1.005 | 89.803 | COA | Bus: 18; size: 0.2706 MW Bus: 23; size: 1.4078 MW Bus: 63; size: 1.5098 MW Bus: 55; size: 0.6024 MW | 2.777/1.795 | 0.984/1.044 | 135.121 | ICOA1 | Bus: 65; size: 1.6407 MW Bus: 55; size: 0.6677 MW Bus: 23; size: 1.2326 MW Bus: 17; size: 0.2436 MW | 2.633/1.701 | 0.988/1.036 | 144.027 | ICOA2 | Bus: 23; size: 1.4105 MW Bus: 18; size: 0.2700 MW Bus: 63; size: 1.5370 MW Bus: 55; size: 0.6570 MW | 2.685/1.735 | 0.986/1.044 | 136.356 | ICOA | Bus: 18; size: 0.2475 MW Bus: 65; size: 1.5442 MW Bus: 55; size: 0.6293 MW Bus: 25; size: 1.3124 MW | 2.709/1.750 | 0.985/1.047 | 156.052 |
|
|