Improved Coyote Optimization Algorithm for Optimally Installing Solar Photovoltaic Distribution Generation Units in Radial Distribution Power Systems

Table 19

The best solutions and the total capacity of PVDGUs found by nine implemented methods for the IEEE 69-bus distribution network in Case 4.

MethodThe best solutionTHD/IHD (max) with PVDGUs (%)Volt (min/max) with PVDGUs (pu)Total power losses with PVDGUs (kW)

BBOBus: 18; size: 0.2705 MW
Bus: 23; size: 1.4079 MW
Bus: 63; size: 1.5097 MW
Bus: 55; size: 0.6023 MW
2.778/1.7950.984/1.044135.120
GABus: 66; size: 0.0256 MW
Bus: 09; size: 1.0095 MW
Bus: 60; size: 1.9590 MW
Bus: 17; size: 0.1785 MW
2.899/1.8730.982/1.00082.736
PSOBus: 17; size: 0.1639 MW
Bus: 09; size: 0.9271 MW
Bus: 69; size: 0.0089 MW
Bus: 60; size: 2.0000 MW
3.011/1.9450.982/1.00083.398
SFOBus: 63; size: 1.7029 MW
Bus: 21; size: 0.0497 MW
Bus: 10; size: 1.3583 MW
Bus: 19; size: 0.4482 MW
4.648/3.0000.986/1.00581.975
SSABus: 24; size: 0.6126 MW
Bus: 61; size: 0.8376 MW
Bus: 60; size: 1.6438 MW
Bus: 02; size: 0.0067 MW
4.599/2.9610.994/1.00589.803
COABus: 18; size: 0.2706 MW
Bus: 23; size: 1.4078 MW
Bus: 63; size: 1.5098 MW
Bus: 55; size: 0.6024 MW
2.777/1.7950.984/1.044135.121
ICOA1Bus: 65; size: 1.6407 MW
Bus: 55; size: 0.6677 MW
Bus: 23; size: 1.2326 MW
Bus: 17; size: 0.2436 MW
2.633/1.7010.988/1.036144.027
ICOA2Bus: 23; size: 1.4105 MW
Bus: 18; size: 0.2700 MW
Bus: 63; size: 1.5370 MW
Bus: 55; size: 0.6570 MW
2.685/1.7350.986/1.044136.356
ICOABus: 18; size: 0.2475 MW
Bus: 65; size: 1.5442 MW
Bus: 55; size: 0.6293 MW
Bus: 25; size: 1.3124 MW
2.709/1.7500.985/1.047156.052