| Load level | Method | Optimal siting and sizing in kVAr | Total kVAr | Total kVAr demand |
| Light 50% | SOSc | (13, 191.51); (25, 200.72); (30, 516.28) | 908.51 | 1150 | SQI-SOSc | (13, 191.48); (25, 200.85); (30, 516.33) | 908.67 | | SOS | (14, 200); (25, 200); (30, 500) | 900 | | SQI-SOS | (14, 200); (25, 200); (30, 500) | 900 | |
| Medium 75% | SOSc | (13, 295.44); (25, 200.72); (30, 789.82) | 1285.99 | 1725 | SQI-SOSc | (13, 295.42); (25, 200.85); (30, 789.84) | 1286.11 | | SOS | (14, 300); (25, 200); (30, 800) | 1300 | | SQI-SOS | (14, 300); (25, 200); (30, 800) | 1300 | |
| Full 100% | SOSc | (13, 325.37); (25, 200.72); (30, 900.73) | 1426.84 | 2300 | SQI-SOSc | (13, 325.37); (25, 200.85); (30, 900.75) | 1426.97 | | SOS | (14, 300); (25, 200); (30, 900) | 1400 | | SQI-SOS | (14, 300); (25, 200); (30, 900) | 1400 | |
| Final optimal ratings (location and size) by proposed approach | SOS | Fixed: (14, 200); (25, 200); (30, 500) Switched: (14, 100); (30, 400) | SQI-SOS | Fixed: (14, 200); (25, 200); (30, 500) Switched: (14, 100); (30, 400) |
|
|