Research Article

An Innovatory Method Based on Continuation Power Flow to Analyze Power System Voltage Stability with Distributed Generation Penetration

Table 2

Comparisons between CCPF and MCPF of the IEEE 14-bus test system.

Output parameterWithout DGsWith DGs
CCPFMCPFCCPFMCPF

Predictor-corrector steps41323725
Computational time (ms)811.62730.61868.93750.92
Maximum loading factor 2.74372.81783.63973.7412
Stability margin (MW)451.62470.81683.68709.97
Weakest bus14141414