Research Article
Finding Radial Network Configuration of Distribution System Based on Modified Symbiotic Organisms Search
Table 10
Comparison results between the MSOS and the SOS for the 69-node system over 50 independent runs.
| Item | MSOS | SOS |
| Optimal solution | 14, 57, 61, 69, 70 | 14, 57, 61, 69, 70 | Power loss (kW) | 98.5875 | 98.5875 | Minimum voltage (p.u.) | 0.9495 | 0.9495 | Maximum fitness value | 106.5732 | 105.6075 | Minimum fitness value | 99.1169 | 99.1169 | Average fitness value | 99.7868 | 100.7601 | STD of fitness | 1.8434 | 2.5010 | Success rate (%) | 70 | 46 | Number of average convergence iterations | 33.62 | 34.46 | STD of number of average convergence iterations | 10.548 | 10.1824 | Running time (second) | 15.3756 | 13.3928 |
|
|