The problem of preventing firebox off system (source: author).
Functional items
Specific problem performance
General control functions
Fire detectors are not set on both sides of the fire roller shutter used on the evacuation passage, and manual control buttons are not set on both sides. The feedback signal after the action of the fire shutter cannot be displayed in the fire control room
Control requirements for fire separation
The fire shutter used as a fire separation in the same fire compartment did not fall to the bottom after the fire detector acted, and the commissioning was not carried out according to the requirements of simultaneous action of the fire layer and the upper and lower layers
Fire power supply
The fire shutter control device is not powered by the fire power supply
Fire resistance
Single piece roller shutter without water curtain protection
Fire-proof door
When the fire door is under linkage control, the fire door cannot be closed automatically and the action signal cannot be fed back to the fire control device. Normally open fire doors are not equipped with sequencers