Effectiveness Study of Artificial Intelligent Facility System in Maintaining Building Fire Safety (Case Study: Typical Public Building Cases of Fire-Fighting Facilities Management in China)
Table 11
The conclusion of summarized findings.
Items
Whether it supports the hypotheses
Findings
1
Yes Yes Yes
(1) The initial installation does not meet the requirements (2) The equipment is damaged, the maintenance is not in place, and some alarm functions cannot function normally (3) The products have not been tested, the responsibilities of management personnel are unclear, and the management is not in place
2
Yes Yes Yes
(1) There is a lack of technical measures for fire protection, and the equipment startup process is obsolete (2) The operation and maintenance personnel are derelict, fail to test and operate the equipment in time, and the cleaning and sanitation management is not in place, which affects the service life of the equipment (3) Manual management is negligent, and false alarms occur frequently when there is no management
3
Yes Yes
(1) The fire extinguishing system cannot flexibly respond to emergencies (2) The maintenance structure was not replaced in time
4
Yes Yes
(1) The monitoring and management on the evacuation exit are not in place (2) The fire-fighting facility system is not separated from other systems