Abstract

Borehole thermal energy storage (BTES) exploits the high volumetric heat capacity of rock-forming minerals and pore water to store large quantities of heat (or cold) on a seasonal basis in the geological environment. The BTES is a volume of rock or sediment accessed via an array of borehole heat exchangers (BHE). Even well-designed BTES arrays will lose a significant quantity of heat to the adjacent and subjacent rocks/sediments and to the surface; both theoretical calculations and empirical observations suggest that seasonal thermal recovery factors in excess of 50% are difficult to obtain. Storage efficiency may be dramatically reduced in cases where (i) natural groundwater advection through the BTES removes stored heat, (ii) extensive free convection cells (thermosiphons) are allowed to form, and (iii) poor BTES design results in a high surface area/volume ratio of the array shape, allowing high conductive heat losses. The most efficient array shape will typically be a cylinder with similar dimensions of diameter and depth, preferably with an insulated top surface. Despite the potential for moderate thermal recovery, the sheer volume of thermal storage that the natural geological environment offers can still make BTES a very attractive strategy for seasonal thermal energy storage within a “smart” district heat network, especially when coupled with more efficient surficial engineered dynamic thermal energy stores (DTES).

1. Introduction and Terminology

The term “thermogeology” [1, 2] has been applied to the science of the occurrence, movement, and exploitation of heat in the earth’s subsurface. The ground can be used as a sink or source of heat to provide heating, cooling, or dehumidification to residential and commercial spaces or to industrial or horticultural processes—a technological practice known as ground source heating and cooling (GSHC). This is often, but not always, achieved by the use of ground source heat pumps (GSHP).

Most rocks and saturated sediments have rather high volumetric heat capacities—typically around 2 MJ m-3 K-1. That of water is even higher—c. 4.19 MJ m-3 K-1. Because of these high values, the ground, and the groundwater it contains, can be used as thermal store or “accumulator.” Because the ground beneath a development site has a huge volume and thermal capacity, and because accessing it requires capital-intensive drilling and geoengineering, underground thermal energy storage (UTES) is typically used for the large-scale seasonal storage of heat that is difficult to achieve using conventional surface technologies. UTES can be subdivided into two categories: (1)Borehole thermal energy storage (BTES), where a field of borehole heat exchangers (BHE) exchanges heat with the surrounding rock or sediment mass, predominantly by processes of conduction. In typical cases, the surplus heat stored during the summer months is extracted for space heating usage in winter (and/or vice versa in the case of “coolth”). One of the earliest BTES pilot projects was the Luleåvärme Project, in Luleå, Sweden, which operated from 1983 to 1989. Here, surplus industrial heat from a steel plant, supplied at temperatures of 70-80°C, was seasonally stored in a BTES array of 120 number 65 m deep boreholes ( array) in granitic gneisses, spaced at c. 4 m and with an array volume of c. 115 000 m3 [37]. The annual recharge of heat was some 2.3 GWh, with around 1 GWh recovered annually. The temperature within the BTES rock mass was in excess of 50°C, reaching as high as 65°C(2)Aquifer thermal energy storage (ATES), which typically involves paired doublets of extraction and reinjection wells, and where warm or cold water is introduced (via the reinjection wells) under excess head [810]. Heat is thus largely manipulated within the aquifer volume by means of “forced (head driven) convection” or “advection.” Early trials of high-temperature storage of hot (80-90°C) water took place in an interbedded sand/clay aquifer sequence at Mobile, Alabama, USA [11, 12]. A well-publicised, recent, lower-temperature example of ATES is at Arlanda Airport, Sweden [13, 14].

This paper will focus predominantly on seasonal storage of heat via BTES. Such heat storage is especially attractive in strongly seasonal climates, and the paper will particularly focus on BTES in the fractured crystalline rock terrain prevalent in Fennoscandia and Canada, although the general principles also apply to porous medium aquifers and more temperate climates. Comprehensive analyses and reports on the theory and practice of UTES and BTES were produced in the 1980s and 1990s, which are still regarded as key literature on the topic today, notably (i)Gerardus van Meurs’ thesis on seasonal heat storage in conventional porous sediments [15](ii)Claesson et al.’s report on analytical solutions to ground source heat problems, including seasonal storage in BTES [16](iii)Göran Hellström’s analysis of the thermophysics of borehole heat exchangers and their application to subsurface heat storage [17](iv)Bo Nordell’s thesis on the design and optimisation of BTES systems [3]

Documented examples of established BTES include (i)the summer harvesting of solar heat (by solar thermal rooftop collectors) at a housing development in Drake Landing, Canada [1820]. The BTES array comprises a cylindrical array of 144 boreholes to 35 m depth (volume 34,000 m3).(ii)A similar district heating system, relying on summer harvesting of solar heat and storage in a BTES array comprising 100 boreholes to 65 m depth, spaced at 3 m, (volume 65,000 m3) in crystalline bedrock at Anneberg, near Stockholm, Sweden [21](iii)Another district heating system at Neckarsulm, Germany, storing summer solar thermal energy at temperatures of up to 80°C in a rock mass, via a BTES system of volume 63,360 m3 comprising (as of 2006) 528 borehole heat exchangers to depth 30 m [22]. The borehole spacing is as little as 2 m [23](iv)Richard Stockton College, New Jersey, USA, where a 1.2 million m3 BTES system services loads of up to 5 MW and reportedly comprised an array of 400 boreholes of 135 m depth [24](v)The Kemicentrum, Lund, Sweden [25], which utilises an array of 153 boreholes to 230 m deep to support a heating load of 6790 MWh (peak load c. 5 MW) and a cooling load of 5400 MWh (peak load c. 3 MW).(vi)Avantor, Nydalen Industry Park, Oslo, Norway [26, 27], utilises a BTES system of 180 boreholes to 200 m depth in crystalline bedrock, spaced at 7 m, to deliver c. 6 MW heating effect and 9.5 MW cooling effect(vii)An archive building in Shanghai, which operates a GSHC system of up to 1 MW capacity, with a strong element of BTES, utilising 280 boreholes of 80 m depth [28].(viii)The high-temperature BTES at Emmaboda, Sweden [7, 29, 30], which has, since its initiation in 2010, stored around 10 GWh of industrial waste heat (with source temperatures ranging from 58 to 90°C, but supplied to the BTES at up to 55°C) in a array of 140 boreholes, spaced at c. 4 m, drilled to 150 m deep in bedrock predominantly comprising granodiorite. The BTES storage volume was some 323,000 m3, while the ground temperature within the BTES array had reached 40-45°C by 2015. The BTES is divided into 7 quasi-concentric sections that can be individually operated

Further reviews of the state of the art of BTES have been extensively published by [3143].

A borehole heat exchanger (BHE) is typically based on a borehole drilled at between 100 and 150 mm diameter. Depths can be anything up to 350 m: 35 to 150 m is typical for continental Europe, but depths in excess of 200 m are rather common in the crystalline rock terrain of Fennoscandia and the Faroes. The borehole accommodates some form of heat exchange pipe. This often takes the form of a U-shaped tube (i.e., upflow and downflow shanks). Alternatively, coaxial pipes or double-U pipes can be installed. A heat transfer fluid is circulated (by pumping) around the borehole heat exchanger. The heat transfer fluid is often based on a solution of antifreeze (ethanol is common in Fennoscandia; ethylene or propylene glycol are commoner in the UK), together with additives, such as biocides and corrosion inhibitors. In high-temperature BTES, where the temperature of the fluid never approaches 0°C, then simple water (possibly with additives) can be utilised. If the heat transfer fluid is warmer than the surrounding rocks, heat is rejected to the geological environment; if the heat transfer fluid is cooler, then heat will be extracted. The heat transfer fluid circulates to a heat exchanger or heat pump at the surface, by means of which space cooling, space heating, or industrial/agricultural cooling are performed.

A BHE U-tube is commonly constructed of high-density polyethylene (HDPE) or cross-linked polyethylene (PEX) and is of 40 mm (or sometimes 32 mm) outside diameter (OD). For higher-temperature BTES applications, the choice of material can be important as some polyethylene types lose strength as temperature increases. In high-temperature BTES systems, PEX, PE-RT (polyethylene of raised temperature resistance) materials may be preferred [38] and steel pipes may also become attractive. In high-temperature BTES systems, the thermal expansion of the ground in the BTES may become significant and ground heave will need to be considered in any operational risk assessment [2].

In Fennoscandian “hard” crystalline rocks (e.g., gneisses, granites, schists), the BHE borehole is typically unlined (although a limited length of surface casing is typically installed for stability). In such low-permeability rocks, in a wet climate, the water table is often close to the surface and the boreholes are naturally groundwater-filled. It is this groundwater that provides the thermal contact between the heat exchange pipe and the rocks in the borehole walls.

In low-permeability crystalline Fennoscandian rock terrains, an “open coaxial” arrangement is sometimes used, employing a single pipe down the centre of the borehole, and using the surrounding borehole space as the outer coaxial conduit: in this case, the heat exchange fluid is in direct contact with the borehole wall, leading to very efficient heat exchange [29].

In other geological environments (e.g., where the rocks are not fully lithified and self-supporting) or where the water table is low, then the borehole can be backfilled with a low-permeability thermally enhanced grout, which provides a thermally conductive contact between the heat exchange pipe and the geological environment. The borehole structure itself thus possesses a “thermal resistance” () to heat flow.

2. Defining Thermal Efficiency: Ambient and High-Temperature BTES

“Heat” is a mathematical concept (unlike water, whose molecules can be isotopically labelled, or which can be marked with a chemical tracer), and the recovery of “particles” of heat cannot be empirically measured. We must thus be very careful when defining exactly what we mean by thermal storage or recovery efficiency.

Where a high-temperature source of waste heat exists, which is producing heat even at times of low demand (waste incinerator, combined heat and power (CHP) plant, and metallurgical industry), it is possible to store this waste heat underground via a BTES array. During the initial years of operation, the BTES store (and the rock it encloses) is “charged up” with heat to the operating temperature (Figure 1), a process which often involves recharging significantly more heat to the ground than is extracted. During this phase, the temperature field around the BTES evolves; the ground surrounding the BTES warms up, and the temperature contrast between the BTES and the surrounding ground decreases. At some stage, typically after 3-6 years, some kind of quasi-steady state will be achieved, where the operating temperature is reached and the annual heat loss to the surface and surrounding rocks becomes stable; this marks the start of the operational (steady-state phase). In fact, however, it will typically take many decades for a true steady state to be achieved in the far temperature field. During an annual cycle (assuming it is a seasonal heat store), a quantity of heat is recharged to the BTES, and a quantity of heat is extracted (normally, during winter). If the system has entered a quasi-steady state and the long-term average temperature of the BTES is stable (it will, of course, vary over an annual cycle), then the difference between the annual recharge and annual extraction can be taken to be the heat loss to the surrounding ground or the surface. This heat loss will intuitively be (i)proportional to the temperature difference between the edge of the BTES array and the ambient ground temperature(ii)roughly proportional to the thermal conductivity of the ground(iii)related to the geometry of the BTES array (e.g., the surface area to volume ratio) and to any insulation applied to the BTES

In such a case, the thermal recovery factor is relatively easy to define: it is the ratio of the heat recovered to the heat recharged over an annual cycle (or longer period).

However, there is another type of BTES, operating at less extreme—approximately ambient—temperatures. Such a scheme is usually used at a business or building that has predominantly cooling (heat rejection needs) in summer, balanced with a similar heating demand in winter; e.g., many office buildings, hospitals, and greenhouse complexes. In such schemes, a heat pump will draw heat from the building in summer via a chiller circuit and reinject it, via the heat pump condenser, to the ground, at maybe 25°C. In winter, the BTES will be coupled to the heat pump’s evaporator and a chilled heat transfer fluid (maybe a few degrees above 0°C) will extract heat from the ground. Thus, the average temperature of the heat store will be around the ambient ground temperature, extreme temperatures are avoided, and the heat pump operates very efficiently. The ground is thus prechilled for the summer cooling season and preheated (by rejected summer waste heat) for the winter heating season. In this case, the simple thermal recovery factor is difficult to apply as heat is not, in a sense, “lost.” In these cases, it is perhaps more meaningful to compare the ambient BTES with the performance of a similar scheme where no seasonal storage is practiced, but where heat is solely extracted from the ground in winter, but not replenished in summer. This paper thus defines (i)the thermal recovery advantage as the additional amount of heat extracted from a BTES, relative to the amount that can be extracted in a base case where “recharge” of heat is not practised

Finally, in this paper we will also consider the rise in temperature of a BTES if heat is simply charged into the BTES year on year, with no extraction. where is the volumetric heat capacity of the rock .

The thermal accumulation is the amount of heat that has been retained within the BTES during the period in question. As the temperature of the BTES increases, the heat loss to the surrounding environment will also increase; the rate of heat accumulation will decrease and the rate of temperature rise will decline. We will discuss a rather crude parameter: (i)The thermal accumulation efficiency, defined as the estimated year on year accumulation of heat in a BTES array, calculated from the slope of the temperature evolution under heat injection only conditions, divided by the total amount recharged

We will begin our consideration of BTES by examining borehole heat exchangers and ambient BTES.

3. Heat Extraction and Storage via Borehole Heat Exchangers (BHE)

The temperature field around a borehole heat exchanger can be simulated as a line source (or sink) of heat [44, 45]. In the short-medium term, this is adequately represented by the “line source” heat equation (equation (2)), apparently first deduced by Whitehead in 1927 [46] and later utilised in the context of groundwater abstraction by Clarence Lubin and Charles Theis [47]: where (i) is the average temperature at a given radial distance () from the borehole axis at any time () following commencement of heat rejection or extraction (°C or K)(ii) is the average temperature of the rock mass along the length of the borehole, prior to commencement of heat rejection or extraction (°C or K)(iii) is the rate of heat rejection (positive) or extraction (negative) in watts per metre of borehole (W m-1)(iv) is the thermal conductivity of the rock (W m-1 K-1)(v) is the exponential integral function(vi) (dimensionless)(vii)α is the thermal diffusivity of the (m2 s-1)

The average temperature of the heat transfer fluid (i.e., the average of the flow and return temperatures to/from the ) is given by simply calculating the temperature at the borehole wall (radius ) and adding a constant term to account for the borehole thermal resistance (): where (i) is the average temperature of the heat transfer fluid at any time () following commencement of heat rejection or extraction (°C or K)(ii) is the borehole thermal resistance (km W-1)(iii) (dimensionless)(iv) is the radius of the borehole into which the BHE is installed (m)

Let us imagine a single borehole heat exchanger, installed in a borehole 100 m deep and 120 mm diameter, with a borehole thermal resistance of 0.08 km W-1 (quite typical figures for a well-constructed, thermally efficient BHE). Let us further assume that the rock has a thermal conductivity of 2.48 W m-1 K-1 and a volumetric heat capacity of 2.4 MJ m-3 K-1 and that the average initial rock temperature along the borehole length is 11°C (reasonably typical for an acidic igneous rock or sandstone in temperate Europe). Let us further assume a thermal load scenario (Scenario 1) as follows: (i)For four months in summer (May-August), 9000 kWh (32400 MJ) of surplus heat is rejected to the BHE. This works out at an average rate of 3.08 kW, or . Days 0 to 122(ii)For the next two months (Sept.-Oct.), the borehole does not extract or reject heat. Days 122 to 183(iii)For four months of winter (November-February), 9000 kWh (32400 MJ) of heat is extracted from the borehole (presumably by means of a heat pump, given the low temperatures involved). This works out at an average rate of -3.08 kW, or . Days 183 to 304(iv)Thereafter, the borehole remains inoperative

This will be compared in the following discussion with a second scenario (scenario 2—no heat recharge), where there is no initial heat rejection phase, but merely (i)9000 kWh (32400 MJ) of heat extraction at a constant rate from November to February. This works out at an average rate of -3.08 kW, or . Days 183 to 304

Application of equations (2) and (3) in a spreadsheet environment allows us to calculate the temperature of the heat transfer fluid and the temperature at the borehole wall and at various radial distances into the rock mass from the borehole axis (Figure 2). Figure 3 plots this data against radial distance for various times, and it can be seen that temperature decays approximately with the logarithm of radial distance from the borehole.

It will also be noted that the difference in average heat transfer fluid temperature between scenario 1 (with the initial injection of 9000 kWh of heat in months 1-4) and scenario 2 (no heat recharge; only heat extraction in months 6-10) is typically only a little over 0.5°C. In other words, the benefit of recharging 9000 kWh of heat to a single borehole during summer months is typically a slightly elevated heat transfer fluid temperature during the subsequent heat extraction phase, to the tune of some 0.5 to 1°C. This would result in a slightly improved heat pump performance, and one can thus argue that the recharged heat has been recovered, but not in an especially noticeable or economically advantageous manner. In Figure 4, the temperature difference between the scenarios with and without heat recharge is shown as a function of distance at the end of the heat extraction season (day 304). It can be seen that the temperature difference becomes very small (<0.1°C) beyond 12 m, and in the immediate vicinity of the borehole, it is around 0.5°C. One can calculate the “stored” heat that this temperature difference () represents by multiplying the volume of successive radial sections by the volumetric heat capacity and the temperature difference (). This calculation verifies that almost all the 9000 kWh recharged heat is stored in the rock around the borehole within the zone to 20 m. The bulk of the heat is, however, stored in the zone 3-10 m, with the maximum quantity of stored heat at around -7 m (Figure 4).

4. Thermal Recovery Advantage—Single Borehole

To attempt to quantify the utility of the heat recharge in scenario 1, one can compare the operational heat transfer fluid temperature during scenario 2 without heat injection (-0.18°C at day 304) and then increase the heat extraction rate in scenario 1 (with heat recharge) until a similar heat transfer fluid temperature is achieved—i.e., our previously defined thermal recovery advantage (see above). It is found that a heat injection (months 1-4) of 9000 kWh, followed by a heat extraction (months 6-10) of 9500 kWh, gives a similar heat transfer fluid temperature profile to that achieved by the extraction of 9000 kWh heat (no heat recharge). Thus, one can say that the effect of recharging 9000 kWh of heat to a single BHE in summer is to allow the equivalent of an additional extraction of 500 kWh of heat during winter: a thermal recovery advantage of only 5.6%.

One could reasonably argue that this is unduly pessimistic. In the scenario where balanced heat recharge and extraction are practised year on year, there is no long-term downwards “drift” in temperatures. In the scenario with winter heat extraction only, temperatures will progressively (though slowly) decline year upon year. In fact, one can calculate that at the end of the 15th heat extraction season, the average heat transfer fluid temperature would be -1.44°C. In the scenario with heat recharge of 9000 kWh during summer, one could extract 10650 kWh during winter to yield a similar fluid temperature—a thermal recovery advantage of 1650 kWh (18.3%).

5. Larger BHE Arrays for Thermal Storage

However, due to the relatively modest improvements in operating temperature, it is not normally considered efficient to use single BHEs or small arrays of BHE to store heat (although it may arguably still be worthwhile if the surplus injected heat has little or no alternative value and can be recharged to the ground for little additional cost). This conclusion concurs with that of Kjellsson et al. [48], who also found that summer solar heat recharged to a single borehole “leaks” away rapidly—small thermal advantages might accrue, but these might easily be counterbalanced by the additional costs of circulation pumps, etc., involved in the summer recharge operation. To store heat efficiently, it is common to use large arrays of boreholes drilled in square, hexagonal, or cylindrical array shapes (Figure 5), at distances of a few metres (3–7 m are typical) such that, as demonstrated above, the heat storage fields of each borehole overlap and are intercepted efficiently by adjacent boreholes. It is, moreover, important that the overall array volume is as “closed” as possible, meaning that the array’s surface-area-to-volume ratio is minimised. Thus, a long line of 36 boreholes will not be efficient at storing heat, as each borehole will be exposed on two sides to unexploited rock, through which heat can conduct away. A square array of boreholes (dimension , if boreholes spaced at 6 m) will be far more efficient at storing heat. The perimeter of the square array, through which heat can be lost to unexploited rock, is only 120 m, compared with 420 m for the linear array (spaced at 6 m).

Figure 6 compares the performance of a array of deep boreholes, spaced at 6 m, with heat extraction and rejection loads comparable to those in Figures 13 above (i.e., ), evenly distributed over a 4-month heat rejection season (“summer”) and a 4-month heat extraction season (“winter”) separated by a 2-month nonoperational period. The borehole constructions are also identical to those described for Figures 2 and 3 (above), and the scenario is simulated in the software Earth Energy Designer (EED) version 3 [49].

Figure 6(a) plots four scenarios: (i)A balanced heat rejection/extraction scenario for the 36 boreholes, with heat loads of 324 MWh per annum. The maximum summer and minimum winter average heat transfer fluid temperatures are plotted, and these are typically around +22°C and just below 0°C, respectively (and hence fully compatible with Figure 2)(ii)A “heat rejection only” scenario for the 36 boreholes, with a heat rejection of 324 MWh per annum, spread over 4 months. The temperatures climb rapidly year on year, with a maximum summer heat transfer fluid temperature of around +36°C in year 15 and + 38.6°C in year 25(iii)A “heat extraction only” scenario for the 36 boreholes, with a heat out-take of 324 MWh per annum, spread over 4 months. The temperatures drop rapidly year on year, with a minimum winter heat transfer fluid temperature of around -14°C in year 15 and -16.6°C in year 25. It should here be noted that these temperatures are far lower than would be experienced in real GSHC schemes—at such temperatures, the ground and heat transfer fluid would freeze, latent heat of freezing would be released, and geotechnical (frost heave, or U-tube compression) issues might be experienced. As EED does not consider latent heat of freezing, these scenarios can only be considered “hypothetical” and representative of sensible heat balance(iv)The plot also shows the summer maximum and winter minimum temperatures for a single borehole in “rejection only” and “extraction only” modes

Although the single borehole curves do show a year-on-year trend (as noted above), the trend is very shallow compared with the 36-borehole array “rejection only” and “extraction only” curves, immediately demonstrating that the 36-borehole array is far more efficient at “accumulating” or storing heat and “coolth” than the single borehole. Indeed, while in the 36-borehole “extraction only” scenario, the fluid temperature reaches just below -2°C in the first winter; in the heat “storage” scenario, one could extract 400 kWh (following the rejection of 324 kWh) to bring the temperature down to -2°C. This additional 76 MWh represents a first-year thermal recovery advantage of 23% (compare with 5.6% for the single borehole).

6. Effect of Array Geometry

One could argue that the array of 36 boreholes is still an inefficient shape in terms of heat storage, as the depth (100 m) is still far greater than the lateral dimension (30 m). The volume of the array is thus 90,000 m3, and the surface area 13,800 m2, giving a surface area-to-volume ratio of 0.153 m-1. By designing the array as a more evenly dimensioned shape (lateral dimension approximately equal to depth), the surface area/volume ratio could be reduced to 0.124 m-1 for a cylinder of radius 24 m and depth 49 m or to 0.134 m-1 for a cubic configuration of depth and width c. 45 m (all have volume 90,000 m2). Figure 7 plots the surface area-to-volume ratio, versus volume for a variety of bulk BTES shapes. A spherical shape is effectively impossible to achieve in the context of a BTES array comprising linear boreholes. The next most efficient common array shape is a cylindrical array, where the depth is equal to the diameter. In this context, it can be noted that the Canadian Drake Landing scheme comprises a cylindrical array of 144 boreholes, spaced at 2.25 m and drilled to 37 m deep. The array has a diameter of around 35 m, approximately equal to depth, thus minimising surface area-to-volume ratio [20].

To test the effect of array geometry, the Earth Energy Designer simulation (Figure 6(a)) has been rerun for the same heat loads, but applied to an array comprising a cubic array of 81 boreholes, 44.4 m deep on a grid, spaced at 5.6 m (44.8 m array width), giving a total drilled length of 3596 m, an array volume of 89,100 m3 (almost identical to the array simulated in Figure 6(a)), and an array surface area of 11,970 m2. This gives a significantly reduced surface area-to-volume ratio of 0.134 m-1. The results of the simulation are plotted in Figure 6(b) and are superficially rather similar to Figure 6(a). The main difference is (i)that, in the early years, the temperature gradient of the “heat rejection only” curve is steeper than Figure 6(a), representing heat accumulation rates of 80-100 MWh/a (thermal accumulation efficiency of 25-30%).(ii)In later years, however, the rate of temperature and heat accumulation flattens out (thermal accumulation efficiency of <10%) to a greater degree than Figure 6(a)

The first observation is as one would expect: the lower surface area-to-volume ratio of the cubic array leads to more efficient accumulation of heat. The second observation suggests that not all forms of array surface area are equal and that the ground-surface interface (which is much larger in Figure 5(b): 2007 m2 for the array, as opposed to 900 m2 for the array) is particularly effective at losing heat. Indeed, in Earth Energy Designer [49], while the rock mass is simulated as an infinite conductive medium, the ground surface is effectively simulated as a constant temperature (Dirichlet) boundary condition. Thus, depending on the time perspective of thermal energy storage, modelling suggests that particular attention should be paid to the ground surface above the BTES array and that, in some cases, it may be desirable to minimise the area of the surface footprint through which heat can be lost, or to insulate the surface footprint. Some authors [33] explicitly recommend insulating the ground surface above the BTES array and, in this case, identify a cylindrical array, where the depth is equal to the radius, as the most thermally efficient solution (in terms of surface area-to-volume ratio, provided that the upper thermal insulation is “ideal”). This solution is also shown in Figure 7 as “Cylinder (depth = radius) top surface insulated.” Indeed, the BTES system at Neckarsulm in SW Germany [22, 33] closely approaches an idealised geometry and the top surface of the BTES is insulated with a 20 cm layer of extruded polystyrene and then backfilled to a depth of 3-4 m [23]. The top surface of the BTES at Emmaboda, Sweden, is insulated by 0.4 m of foam glass [30].

7. Effect of Borehole Spacing

As a final experiment in the Earth Energy Designer [49] modelling environment, another BTES of 90,000 m3 has been simulated, but this time with 289 boreholes ( grid) to 44.4 m spaced at 2.8 m. The BTES thus has the same overall dimension as Figure 5(b), but the borehole spacing has been halved and the number of boreholes (and total drilled metres) has been increased by a factor of 3.56. Applying exactly the same heat extraction and rejection loads as Figures 6(a) and 6(b) (324 MWh per 4-month heat extraction or rejection season) results in the temperature evolution curves shown in Figure 8. The average heat transfer per metre of borehole has thus dropped from 30.8 W m-1 to 8.6 W m-1.

It will be noted, in the case of heat rejection only, that the temperature of the BTES increases (Figure 8) at almost the same rate as in Figure 6(b): i.e., the dotted green line has an almost identical trajectory, with around 100 MWh of heat being added per year in the early years and < 10 MWh per year being added after year 20. The main difference is that, because the heat loads are being distributed across larger numbers of boreholes, the heat transfer fluid temperatures in each borehole are far less extreme than in Figure 6(b). In the case with balanced rejection and abstraction, the operating temperatures are just over +5°C in the winter and around +16°C in the summer (compare with -0.5°C and +23°C, respectively, in the case of Figure 5(b)). This will result in a very significant difference in the efficiency of operation of any heat pump and may even permit the use of free cooling (as opposed to compressor-powered cooling) in the summer. The importance of achieving a thermal balance between heat rejection and extraction is well recognised: actually achieving this balance in real large buildings, whose needs are often dominated by cooling, is considerably more difficult. Various ways have been considered [50] of utilising excess rejected heat directed towards Haukeland Hospital’s GSHC system (165 boreholes on a grid spaced at 6 m) in Bergen. In other words, decreasing the borehole spacing from, say, 6 m to 3 m, does not make any great difference to the total storage efficiency of the BTES (all other things, including overall BTES dimension) being equal, but it has a significant impact on how efficiently that thermal storage can be accessed.

Amongst the forest of BTES theory, it is important to remember practical considerations. One major factor, when drilling closely spaced boreholes, is to remember that boreholes are not always vertical. Indeed, the quick and cheap drilling method (down the hole hammer drilling) favoured by many BHE practitioners can result in very substantial deviations. At Emmaboda, Sweden [30], the deviation of 21 (randomly selected) boreholes of the total of 140 boreholes in the granodiorite rock was measured. At 150 m depth, the horizontal “drift” of borehole trajectory varied from 4 m to 26 m, with an average of 16 m (i.e., over 1 m horizontal drift for every 10 m drilled). Thus, if one drills on a tidy rectangular grid at 4 m spacing, one must realise that the true situation at depth may be very different, and there is always the risk of drilling through an adjacent borehole.

8. High-Temperature Heat Storage by BTES

As we have already noted, in many larger BTES schemes, heat is not stored around the ambient ground temperature, but rather at high temperatures characteristic of waste heat from industrial, combustion, or incineration processes. The general principles of borehole spacing and array geometry discussed above apply to high-temperature BTES arrays. However, determining the efficiency of heat storage is somewhat simpler.

In such schemes, the first few years of BTES operation are typically dedicated to “charging up” the BTES with surplus heat, with little or no extraction. As the temperature within the BTES increases, the rate of heat loss to the surrounding rocks also increases and eventually a steady-state heat loss () is approached where the bulk temperature of the BTES ceases to increase sharply (this can be observed in the “heat rejection only” curves of Figures 6(a) and 6(b)). It is commonly claimed in the literature [51] that the recovery efficiency of a BTES increases over the first year of operation (the transient phase) as the rock volume in and around the BTES increases towards an operational temperature. As the rock around the BTES begins to warm up, relative conductive heat losses from the BTES decrease. However, an “honest” account of storage efficiency should ideally recognise the quantities of heat that have had to be “dispersed” into the surrounding rock mass to achieve this effect. For example, it is claimed that the “BTES efficiency” of the Canadian Drake Landing BTES scheme increased from 9% to 40% over the first four years of operation [19].

At steady state, cyclical seasonal storage and extraction can commence. The amount of heat charged to the BTES store will typically exceed the amount of heat discharged by a quantity over an annual cycle, thus ensuring that the average temperature of the BTES is maintained. In this case, the thermal recovery factor () is defined [17] as

To achieve a high thermal recovery factor, the steady-state heat loss (which is a function of temperature, BTES geometry, rock thermal conductivity, and insulation) should be as low as possible, while the seasonal transfer should be as high as possible. Hellström [17] argues that heat transfer in a BTES can be analysed in terms of three components: (i)An initial transient thermal build-up of the temperature field around the BTES(ii)A steady-state heat loss () from the BTES(iii)A superimposed periodic variation on an annual (or other) cycle. In idealised analysis, this may be approximated as a sinusoidal function

Hellström [17] provides an idealised case study where the heat recharged to a BTES at any given time is equal to the sum of and a sinusoidal storage recharge and recovery component of amplitude . where is a phase lag and is the period of the recharge-discharge cycle (typically annual, but potentially diurnal). It is possible to demonstrate [17] that, to achieve a recovery factor , then should exceed 3.7. To achieve greater >50% requires to exceed 4.5. To put these figures into perspective, analytical methods are also published [16, 17] for estimating for a range of cylindrical and rectangular BTES geometries (Table 1). Using these methods, we can estimate that, for a 50°C heat store in a cylindrical top-insulated BTES of radius 60 m and depth 60 m, in a granite of thermal conductivity 2.2 W m-1 K-1, one might expect a steady-state heat loss of over 130 kW. This in turn implies, that to get a thermal recovery factor of over 30%, we require a peak discharge rate of over 0.5 MW of heat.

It is noteworthy that, even in the Neckarsulm BTES system, which is regarded [33] as approaching an ideal geometry, thermal losses were relatively high, with only 20% of the charged solar heat (187 of 979 MWh) being usefully recovered [22]. It may seem that commonly cited seasonal thermal storage efficiencies of 20-40% would not be especially attractive. The new Swedish Emmaboda BTES, operating at temperatures over 40°C, is believed to be on target to achieve a thermal recovery factor of over 60% [30], however. The attractiveness of such an approach depends, however, on the value that is placed on surplus summer heat. In reality, this is often very low, to the extent that, in most major cities in temperate and southern Europe, surplus heat is regarded as a waste product and considerable sums are spent on disposing of it.

Nordell [3] has also analysed the optimisation of BTES design, in terms of geometry, borehole spacing, shape, etc., taking into account thermal physical factors, construction factors, and economic considerations. Amongst his findings are the following: (i)The greater the borehole thermal resistance, the greater the optimum number of boreholes and the closer their spacing(ii)The greater the rock thermal conductivity, the greater the borehole spacing and the fewer boreholes required(iii)The bigger the store, the relatively smaller the heat loss. For an optimised BTES in a given set of Swedish conditions, the thermal recovery factor (theoretically) exceeds 50% for a heat extraction capacity of 1 GWh/year

9. Free Convection within the BHE Water Column

It has already been noted that the BHE itself often comprises one (or sometimes two) U-tubes of pipe installed down the length of the borehole. The borehole itself is typically between 100 and 150 mm diameter. In incompletely lithified rocks or sediments, or where the water table is relatively deep, the borehole is commonly backfilled with a thermally enhanced grout, often based either on a mixture of bentonite (to give low hydraulic conductivity) and fine silica sand (to give high thermal conductivity) or a thermally efficient cement mix. In situations where the rock is hard and lithified and where the water table is high (due to the rock’s low permeability and/or to high rainfall), the borehole is left open and allowed to fill with natural groundwater. In this case, the groundwater provides the thermal contact between the BHE U-tube(s) and the walls of the borehole (Figure 9).

It has been shown that convection cells can start to occur in a fluid-filled vertical tube (borehole) when the temperature gradient along the length of the borehole exceeds a certain threshold [5256]: where is the acceleration due to gravity (9.81 m s-2), is the fluid’s isobaric thermal expansion coefficient (K-1), is the absolute temperature (K), is the fluid heat capacity at constant pressure (J kg-1 K-1), is the critical Rayleigh number (which may be between 69 and 216, depending on the thermal conductivity of the borehole wall), is the fluid’s thermal diffusivity (m2 s-1), is the kinematic viscosity (m2 s-1), and is the bore radius (m). The Rayleigh number is a dimensionless number for a fluid, indicating a tendency towards buoyancy-driven or convective flow.

The implication of this equation is that only small temperature gradients are needed to initiate convection in fluid-filled boreholes, e.g., in boreholes as narrow as 50 mm with axial temperature gradients as low as 0.03°C m-1 [52, 57]—i.e., natural geothermal gradients.

Thus, the application of a heating or cooling load to a polyethylene U-tube within a water-filled borehole can be assumed to be sufficient to initiate free convection in the groundwater column. This, in turn, enhances the heat transfer between the U-tube and the borehole wall. Water has a rather low thermal conductivity of 0.6 W m-1 K-1. Thus, a borehole filled with static water would be expected to exhibit a very high borehole thermal resistance (—see equation (3)). In practice, this is not the case, and we can infer that thermally driven convection is occurring within the water column. To illustrate the importance of convection as a mechanism for heat transfer within a BHE, SWECO carried out thermal response tests (TRT) in several individual groundwater-filled BHEs installed in the basalt rocks of the Faroe Islands [58]. The results are summarised in Table 2.

Very low borehole thermal resistances () of 0.066 to 0.08 km W-1 were obtained. The program Earth Energy Designer [49] can be used to simulate the theoretical , for a 140 mm borehole, installed with a 40 mm single U-tube at a shank spacing of 70 mm. A 25% ethanol heat transfer fluid has been assumed, with a flow rate designed to give a transient-turbulent Reynolds number of c. 2500. If the borehole was assumed to be filled with static water (thermal conductivity 0.6 W m K-1), resistances of around 0.2 km W-1 are calculated, over twice that actually observed. If the borehole is assumed to be filled with a thermally enhanced grout with a conductivity of 1.7 W m-1 K-1, resistances of around 0.11 km W-1 are calculated. Thus, free convection in a groundwater-filled borehole is demonstrated to be more thermally efficient than a borehole filled with a thermally conductive grout of thermal conductivity 1.7 W m K-1.

Moreover, the greater the temperature contrast between the heat transfer fluid and the borehole walls, the greater the convective heat transfer effect. This is evidenced by a decrease in the with increasing heat injection rates, from thermal response tests in an 80 m groundwater-filled BHE in crystalline, poorly fractured igneous bedrock at Göteborg, Sweden (110 mm bore, single 40 mm OD polyethylene U-tube [59]). With a heat injection rate of 28 W m-1, the borehole thermal resistance was estimated as 0.089 km W-1. At heat injection rates of 55, 70, and 142 W m-1, fell to 0.069, 0.068, and 0.051 km W-1, respectively [60]. As the rock in this test borehole was poorly fractured, the thermally driven convective effects are believed to be restricted to the borehole itself, rather than to a “thermosiphon” (see below) effect in the surrounding rock.

In order to minimise borehole thermal resistance, several BTES systems have omitted the U-tube altogether (Figure 9(c)). At Emmaboda [29], a BHE design has been developed using a single pipe coaxially mounted in a water-filled borehole. The pipe is insulated by a concentric layer of stagnant water. In operation, the heat transfer fluid is circulated down the pipe and up the annulus between the pipe and the borehole walls. To avoid fluid loss, the walls must be either cased or comprise essentially impermeable fracture-free hard rock. Testing at Emmaboda suggested values as low as 0.02 km W-1-.

10. Forced Convection through a BHE Array

For BHEs whose objective is solely to extract heat from the ground (e.g., for space heating) or to reject heat to the ground (e.g., for space cooling or industrial cooling), flow of groundwater past the BHE is generally regarded as a positive factor. This is because the flow of groundwater carries with it a “cargo” of environmental heat that can replenish heat that has been extracted from the ground or remove heat from the BHE and surrounding ground in the case of heat rejection. This stabilises ground temperatures, preventing them from reaching extreme values that would result in poor heat pump performance. In the case where groundwater flow is driven by regional topographically determined head gradients, the concomitant heat transport with the flowing water is termed forced convection or advection. The presence of regional groundwater advection implies that a “plume” of heat (or “coolth,” if heat extraction is being practiced) extends downgradient away from the BHE and increases the opportunity for downgradient thermal interference. Significant flow of groundwater in a geological stratum (or aquifer) requires two preconditions: (i)That the aquifer has sufficient hydraulic conductivity () to permit water to percolate. Hydraulic conductivity is simply the permeability of the rock mass with respect to water(ii)That there is a sufficient groundwater head gradient () to drive groundwater flow ( is dimensionless). The ultimate source of groundwater head gradient is usually different in topographic elevation (although other mechanisms, such as over-pressurisation of sedimentary basins, can result in head gradients)

The groundwater flux (which is commonly also termed the Darcy velocity or Darcy flux ()) in m3 per m2 cross section per day (i.e., m d-1) is given by Darcy’s law (assuming flow is laminar): where K = hydraulic conductivity in m d-1. In the case of a BHE operating in a permeable rock or sediment mass with flowing groundwater, the temperature of the heat transfer fluid within, and of the rock around, the BHE will initially change (increase in the case of heat rejection, decrease in the case of heat extraction) in accordance with the line source heat (equation (2) or (3)). Over time, however, the temperature will then tend to stabilise and will eventually reach a steady-state temperature (). At any point () in a Cartesian coordinate system, where groundwater flows in the + direction, the following equation can be derived [61, 62], based on equations for a moving line source of heat [63, 64]: where the thermal velocity () is related to the Darcy velocity (flux) () [62]: (i) is the bulk volumetric heat capacity of the saturated aquifer and is the volumetric heat capacity of water (c. 4.19 MJ m-3 K-1)(ii) = radial distance from heat source = (iii) is the zero-order modified Bessel function of the second kind

It is found [62] that, for typical aquifer scenarios, the impact of groundwater flow on BHE performance becomes significant at Darcy fluxes of around 0.01 m d-1(previous evaluations [65] approximately concur with this finding), while at Darcy fluxes of around 1 m d-1, the groundwater flux was sufficient to effectively maintain the BHE at close to ambient ground temperatures. Van Meurs [15] also concluded that heat losses from an underground thermal store became significant at a Darcy flux in excess of 0.05 m d-1 ( cited in [3]). It is also possible to demonstrate [62] that the greater the Darcy flux, the more rapidly the thermal effects of the flux are seen (i.e., a deviation of heat transfer fluid temperature towards a steady state): for a Darcy , some form of steady state should become apparent within a time frame of less than 3 days.

On the other hand, for a BTES scheme, where the objective is to build up a seasonal reserve of heat or “coolth,” groundwater flow is generally regarded as a negative factor, as it will tend to “wash away” the accumulated heat down the hydraulic gradient. As a general rule of thumb, it seems reasonable to suppose that, if the thermal transport velocity is large compared with the dimension of the BTES array, the effect of groundwater flow would be significant. For example, let us consider a BTES array of width 40 m, within an aquifer of bulk volumetric heat capacity () 2.4 MJ m-3 K-1. The calculations given in Table 3 apply: it will be seen that, if the Darcy flux exceeds c. 1 cm d-1 (equivalent to a hydraulic conductivity of —a fine sand or similar—coupled with a hydraulic head gradient of 1 in 100), heat can migrate several metres per year, which begins to be significant in terms of the size of the BTES array.

Application of equation (8) rapidly becomes a complex procedure when applied to BTES arrays comprising multiple boreholes. Moreover, the third dimension (upward and downward heat loss) rapidly becomes important when simulating BTES arrays. Therefore, three-dimensional coupled heat and groundwater transport numerical models (often finite element, such as FEFLOW [66]) are typically applied to simulate the effects of groundwater flow on the operation of a BTES array. A word of warning is appropriate: equations (8) and (9) assume intimate thermal contact and rapid thermal equilibration between the flowing groundwater and the aquifer mineral matrix. In other words, it assumes either a porous medium (silt, sand, and gravel) or a fractured/fissured rock with a relatively dense fracture network. If the aquifer is a fractured rock, where the hydraulic conductivity is dominated by a few conductive fractures, then equation (9) does not apply and the thermal velocity more closely approaches the hydraulic velocity (see Table 3). If the effective porosity () is low (typically <1% in fractured rock aquifers), the rate of heat migration can be very high. Most modelling techniques also make the assumptions implicit in equation (9) unless fracture flow is explicitly simulated within the modelling environment.

Where heat losses via groundwater flow are restricted to a limited number of horizons or highly permeable fractures, these can be excluded by extending casing down the borehole, or they can be grouted during drilling. Both the procedures significantly increase drilling costs. In Sweden, drilling with casing costs 3-4 times as much as drilling open hole in hard rock [30].

11. Free Convection in a BTES Store

The very act of heating or cooling a single BHE or an array of BHEs can induce convective transfer of heat, not just within the borehole itself, but within the surrounding rock or sediment (provided it is permeable). As has been seen above, for BHEs being solely used for extraction or rejection of heat, this additional convective heat exchange with the rock or sediment mass will often be beneficial. However, for a BTES aiming at seasonal heat storage, significant convective heat losses to a wider volume of rock or sediment effectively mean that heat or “coolth” is being lost from the store

Let us imagine an 80 m deep BHE, with a heat exchange pipe installed within an open borehole, completely filled with groundwater to the surface. A length of steel casing protrudes 0.5 m above the surface (Figure 10—in reality of course, a typical Scandinavian borehole would be completed below ground with a watertight well-head). Let us imagine that the water temperature within the borehole is initially at 10°C. Furthermore, suppose that we reject heat to the borehole such that the column of groundwater in the borehole is heated by 4°C.

Figure 11(a) shows the well-known dependence of water density on temperature. The density of water is at a maximum at c. +4°C. Above +4°C, the density decreases and the rate of density decrease increases as temperature increases. Thus, in our hypothetical borehole, initially at 10°C, an increase in temperature to 14°C will result in a density decrease from 999.70 to 999.24 kg m-3. The column of groundwater, initially 80 m high, will now have a height of 80.036 m (an excess height of 3.6 cm). If the temperature rise is 10°C, the new density (at 20°C) will be 998.20 kg m-3 and the excess height will be 12 cm (Figure 10(b)). In the latter case, if the steel casing is suddenly removed, the excess height of water of 12 cm will run away at the surface and the water pressure at the base of the borehole will now be , rather than the original .

If there is a hydraulically conductive fracture at the base of the borehole, groundwater will enter the borehole due to the pressure difference of c. 1.12 kPa between the aquifer and the borehole, and an equivalent amount of water will run away at the surface. As the “new” water is heated by the BHE, a convection-driven thermal “pump” will develop, with groundwater entering at the base of the borehole and running away at the surface (Figure 10(c)).

It should be possible to see that, if there is also a shallow hydraulically conductive fracture, 1 m below ground level, there is no need for surface overflow to produce a convection-driven system, whereas the initial pressure of water at the end of the fracture was equivalent to , the pressure after heating by 20°C will be . The excess pressure (c. 1.2 kPa) will thus force water into the fracture from the borehole, also removing heat (as warm water) from the borehole environment. Because of the loss of water from the top of the borehole, new cool water will be drawn into the borehole by the opposite pressure differential at the base of the borehole and free convection will have been initiated. If the upper and lower fractures are somehow hydraulically interconnected via a broader fracture network, then a convection cell will result (Figure 10(d)). If the fractures are not interconnected, the free convection will reduce after some time as excess head builds up in the upper fracture system, opposing the convective energy.

By extrapolating this thought experiment still further, it should be easy to see that in any given borehole, the components of a fracture network intersecting an open BHE above the borehole’s (admittedly somewhat loosely defined) “hydraulic centre” will lose water upon heating, and those below will gain fresh cool groundwater from the aquifer. By extending this further to an ever finer and denser network of fractures, it will be seen that such a BHE-driven convection cell could develop in an open borehole even in an ideal porous medium aquifer. This effect is well-known and is termed the “thermosiphon effect” [6973].

One would expect that the practice of grouting a BHE borehole, using a grout with high thermal conductivity (to promote efficient heat exchange) but low hydraulic conductivity, would significantly reduce the likelihood of a thermosiphon effect developing, because the open borehole forms the main axis for thermally driven convective flow. Similarly, the practice of lining a BHE borehole with a casing extending throughout any permeable rock horizons (or to the base of the borehole) would also be effective at suppressing the thermosiphon effect. Theoretically, however, with a permeable enough rock matrix outside the borehole and with a high enough heat input, it might be possible to induce some degree of convective circulation in the aquifer outside the BHE borehole. Finally, if the water table is deep, the thermosiphon effect can be avoided by keeping the thermally active section of the BHE entirely within the unsaturated zone above the water table.

It will be seen from Figure 11 that the rate of density change increases with increasing temperature, above 4°C. Thus, in the case of heat rejection: (i)The greater the temperature difference between the heat transfer fluid and the ambient rock temperature, the greater the likelihood of thermally driven convection or “thermosiphon” developing(ii)The higher the initial temperature of the rock, the greater the likelihood of thermally driven convection or “thermosiphon” developing

Theoretically, of course, a thermosiphon effect could also develop in cooling mode. However, in practice, because the density of water reaches a maximum at around +4°C, the density differences achievable by cooling the groundwater in a borehole from an original temperature of 10°C (say) are rather low (see Figure 11(b)). It is only when the original ground temperature exceeds around 15°C that significant thermosiphon effects seem likely in heat extraction mode. For this reason, the storage of “coolth” in BHE arrays in permeable fractured rocks is likely to suffer less from thermally driven convective heat losses, than the storage of heat in similar arrays.

Testing of BHEs is typically undertaken by carrying out a thermal response test (TRT) by constant injection of heat and observation of temperature rise (on the assumption that, if heat transfer is predominantly by conduction, the borehole will behave similarly in heat extraction mode). It is found, however, that the thermosiphon effect can lead to significant overestimation of rock thermal conductivity during TRT tests in groundwater-filled BHE in permeable fractured bedrock. In fact, experiments have been carried out [60] on an 80 m deep, groundwater-filled borehole in fractured rock in Göteborg, Sweden. It was found that at a heat injection rate of 55 W m-1, the TRT yielded an estimate of apparent thermal conductivity of 3.19 W m-1 K-1 (believed to be reasonably representative of the “true” conductivity). Increasing the rate to 141 W m-1 resulted in a higher apparent thermal conductivity of 3.57 W m-1 K-1, suggesting that 12% additional heat loss was due to thermally driven convective heat losses to the surrounding aquifer.

While enhanced convective heat transfer between the BHE heat exchange pipe and the borehole wall will potentially occur in any water-filled borehole (see Free Convection within the BHE Water Column), this will result in more efficient heat transfer in the borehole structure itself (i.e., lower ) and will not lead to greater heat losses from a BTES array. Similarly, a “local” thermosiphon effect, which is not laterally extensive, may have a positive impact in enhancing heat transfer between the borehole and the rocks immediately surrounding it. However, a laterally extensive thermosiphon effect will potentially lead to heat losses from a BTES, but a prerequisite is that the surrounding rock contains hydraulically connected permeable horizons or fractures [73]. Extensive permeable fractures near the top (or the base) of the water-filled section of the borehole will be particularly disadvantageous as their presence implies that the thermosiphon will affect the entire length of the borehole. In large BTES systems, multiple water-filled boreholes will themselves form vertical conduits interconnecting permeable fractures, and the chances of forming a well-connected fracture system are enhanced.

Observation clearly suggests that, in many crystalline rock terrains, fracture permeability is typically highest in the uppermost few tens of metres of a hard rock aquifer. This is partly due to the fact that fracture permeability tends to decrease with depth due to increasing loadings (increasing in situ stresses tending to close fracture apertures [74, 75]). More specifically, and especially in the case of northern Europe and Fennoscandia [76, 77], stress-relief fractures and exfoliation joints often develop in the upper few tens of metres of a lithified rock mass, typically approximately parallel to the topography. These are usually ascribed to the removal of an overburden, either by erosion or by melting of a Pleistocene ice sheet and postglacial isostatic uplift. Moreover, it has been demonstrated [78] that the stresses beneath a large ice sheet are sufficient to cause shallow shear failure of crystalline rock. It has also been noted [76] that groundwater flow pathways may often develop as “hydrofractures,” where natural fluid pressures exceed the normal compressive stresses on a fracture plane (plus the tensile strength of the rock if a new fracture is initiated). The water pressures developed below and in front of a major glacial ice sheet are sufficient to cause hydraulic fracturing of sediments and the hydraulic opening of shallow fractures within crystalline rock [78, 79]. Several authors report field evidence of periglacial hydraulic opening of shallow fractures in Fennoscandian crystalline rock [8083]. For all these reasons, one might suppose that BTES systems in recently glaciated hard-rock terrain might be particularly susceptible to heat loss by thermosiphon effects from open fractures and joints in the shallow portion of a BHE.

12. Additional Strategies for Efficient Thermal Energy Storage

Several additional strategies can be incorporated into a BTES system to improve efficiency and to increase flexibility of operation. The simulations of the BTES systems in the previous sections have assumed that all the boreholes of the BTES are connected in parallel and “see” the same heat transfer fluid temperatures and building loads. The system does not, of course, have to be designed in this way. In fact, it has become accepted practice to design cylindrical BTES arrays with two circular header pipes, one around the external circumference of the array and one within the interior of the array. BHEs are then connected in series along radials connecting the two headers. It has been demonstrated above that the optimal design of circular BTES arrays can involve relatively short boreholes, with a depth similar to the lateral extent of the array. This, in turn, implies that connection of several boreholes in series can still result in relatively short hydraulic path lengths without unduly high hydraulic head losses. This arrangement means that the BTES array can be divided into two (or more) concentric thermal zones (Figure 12). Reversing valves can be installed allowing the BTES heat transfer fluid to be directed from the outer circumferential header to the inner one, or vice versa. For example, in a BTES designed to store heat, when surplus heat is available (e.g., during hot summer days), the hot heat transfer fluid is directed towards the core of the BTES, which is warmed to the highest temperature, and then radially outwards, progressively warming the outer zones. When there is a heat demand, the cool heat transfer fluid is circulated from the outer circumferential header first and progressively inwards towards the inner header. Thus, the fluid is initially “prewarmed” by heat acquired from the BHEs in the outer zone of rock and finally is heated by the core of the BTES array to its full temperature. In this way, the core of the array is always “charged” with heat first and discharged last; the core is also always surrounded by the warm rock/sediment of the outer zones and tends to retain its heat most efficiently.

In a BTES in a warm region, where the predominant need is to store “coolth” rather than heat, a similar strategy is applied. On cold winter days, dry coolers may discharge heat to the cold air (this is effectively equivalent to harvesting “coolth” from the atmosphere); the resulting cold heat transfer fluid will be passed first to the inner header, to cool down (“charge”) the inner core of the array and then pass radially outward to the perimeter. When there is a demand for cooling, the warm heat transfer fluid will circulate first to the outside circumferential header (where heat can most efficiently be dispersed into the surrounding rock through the perimeter surface of the BTES) and flow towards the cold core, such that cold heat transfer fluid can be returned to the building [43].

The adequate simulation of such “zoned” BTES systems is beyond the capabilities of conventional BHE simulators [43] (such as Earth Energy Designer) and requires more sophisticated modelling tools such as TRNSYS [84, 85] or even finite element models such as FEFLOW [66].

13. Supplementary Strategies to BTES

BTES are particularly suited to long-term thermal energy storage, because they can access a volume and thermal capacity of rock or sediment that dramatically exceeds that available to most surface-engineered thermal stores. BTES can also be used for short-term storage of heat. However, the expense of drilling boreholes, and the fact that it is rather difficult to achieve more than 50% heat recovery from a BTES, it is often more cost-effective to use a surface-engineered structure for storage of short-term (e.g., diurnal) surpluses of heat and “coolth.” Such a store can feasibly be constructed to accommodate smaller quantities of heat and can be thermally insulated to minimise heat losses and improve recoverability. In situations where the supply of waste heat is variable in temperature or very “peaky,” a surface thermal store can be used as a “buffer” from which a more regulated supply of heat at a constant temperature can be injected to the ground for long-term storage. With BTES where there is danger of convective loss of heat via a “thermosiphon” effect, the possibility to avoid very high injection temperatures, via the use of a thermal buffer, may also reduce the intensity of convective heat loss.

The most fundamental thermal energy storage is simply a surface tank or buried pit of warm or cold water (tank or pit thermal energy storage—TTES or PTES). This can be readily insulated; water has a huge volumetric heat capacity (4.19 MJ m-3 K-1), while its fluid nature means that heat can readily be distributed to, from, and within the store. The fact that water has a low viscosity means, however, that free convection within a tank can readily occur, meaning that thermal stratification within a single tank may be difficult to maintain.

Alternative surface (or buried in the shallow subsurface) thermal energy stores can include [51] (i)phase change media (PCMs, including ice) where surplus thermal energy is stored in the form of latent heat, for example, by melting or freezing the material in question [8690](ii)Thermochemical heat storage (THS—[91, 92]), whereby heat is stored or released during the chemical interaction between two materials (often two liquids or a solid and a vapour); the nature of this interaction may be physical sorption, chemical sorption, or true chemical reaction(iii)Dynamic thermal energy storages (DTES—[93, 94]), which is aimed not only at storing heat and coolth but also at storing heat at varying temperatures simultaneously, for example, by maintaining a thermal stratification within the store. One example of a DTES is a tank of water filled with a porous medium and then saturated with water. The porous medium hinders the formation of free convection cells and allows thermal stratification in the tank

Indeed, a BTES can be considered as only one component of an integrated thermal energy network, providing long-term (seasonal) thermal storage, while a surface-engineered store provides short-term (diurnal) thermal energy storage [94] and a network of pipes of heat transfer fluid, heat exchangers, and heat pumps connect various sources or sinks of heat, e.g., (i)deliberate harvesting of solar or atmospheric heat and “coolth”—via dry coolers or thermal solar cells(ii)lakes, rivers, or the sea(iii)buildings, which may be producers (via air conditioning) or consumers of heat(iv)industrial processes(v)power stations or combined heat and power (CHP) plants(vi)waste incinerators (which may also generate electrical power)

Several of the above are heat sources that would otherwise discharge their surplus heat to waste, resulting in 100% thermal losses. Thus, large-scale BTES offers a remarkable potential to store this waste heat until a time of demand; even if the BTES is only 40% efficient, this still represents a very significant thermal gain.

Horticultural greenhouse complexes provide particularly attractive opportunities to implement integrated thermal energy networks, incorporating storage elements [95, 96]. Modern “closed” greenhouse concepts are typically kept sealed from the external atmosphere to minimise exposure to pests; as such, they may require space cooling on hot summer days, dehumidification (essentially, a cooling process removing latent heat of condensation), and space heating in the winter. They may even incorporate combined heat and power (CHP) plants to produce electricity for winter lighting, surplus heat for winter heating, and excess CO2 (from fuel combustion) to enrich the greenhouse atmosphere. In such situations, one can readily imagine that there will be seasonal heat surpluses (summer cooling and dehumidification) and winter heat deficits (winter heating) that can be satisfied by long-term seasonal heat storage in a BTES. There will also be short-term heat surpluses and deficits (e.g., spring and winter diurnal surpluses, where cold nights, requiring heating, alternate with hot days, requiring cooling); these can be satisfied by shunting heat to and from a short-term surficial dynamic thermal energy store. If heat or coolth surpluses or deficits become so large that they cannot be meaningfully stored, they can be discharged to the atmosphere (or surface waters) via heat exchangers, such as dry coolers. An example of such a greenhouse complex, employing smart controls, several sources and sinks of heat and thermal energy storage can be found at Mære, Trøndelag, Norway [73, 9699].

14. Conclusions

Borehole thermal energy storage (BTES) is a technological concept which is proven to allow seasonal storage of large quantities of heat in large volumes of rock or sediment by the use of borehole heat exchangers (BHE). Two broad conceptual types of BTES are used: (i)High-temperature (typically >40°C) BTES, where waste heat from an industrial process (e.g., metallurgical industry), waste incineration, combined heat, and power or solar thermal harvesting is deliberately stored from seasons of low demand to seasons of high demand (winter). In such schemes, the initial years of operation are typically used to «charge up» or condition the BTES to its operating temperature. When a long-term quasi-steady state has been achieved, heat is recharged and recovered on an annual cycle and long-term temperatures remain relatively constant(ii)Ambient temperature BTES, where waste heat, typically from space cooling, is rejected to the ground during summer, warming it up to 10-20°C higher than ambient temperature. During winter, this heat is extracted, typically via the use of heat pumps, for space heating, thus prechilling the ground (storing “coolth”) ready for the summer cooling season. If the recharge and extraction of heat are balanced, the BTES temperatures remain stable year on year and temperature extremes are avoided, allowing for very efficient heat pump operation

Particular attention should be paid to the design of BTES arrays; the fundamental mathematics, design principles, and optimisation of BTES arrays have already been clearly developed and documented by Swedish researchers several decades ago [3, 16, 17]. Several key design considerations should be remembered: (i)The geometric shape of the BTES should be optimised to maximise internal volume and minimise external surface areas: thus, equidimensional cylindrical and cubic arrays of BHE are especially efficient. The surface area/volume ratio (and hence heat losses) decrease as size increases. This is especially important for high-temperature BTES(ii)The top surface of the BTES is especially susceptible to losing heat; thus, consideration should be given to insulating it, especially for high-temperature BTES(iii)The more boreholes in the BTES, the more efficient the transfer of heat to and from the BTES and the more closely the average BTES temperature approaches the source/sink temperature(iv)The greater the rock thermal conductivity and the lower the borehole thermal resistance, the fewer BHE are required to achieve optimal heat transfer efficiency (and the greater the acceptable spacing between them)(v)Zonation and managed charging and discharging of large BTES can optimise efficiency [43](vi)Some drilling methods (e.g., down-the-hole hammer) can result in very significant borehole deviations (e.g., 1 m horizontal in 10 m vertical), which can lead to unpredictable borehole spacings or intersections at depth in a BTES(vii)Simple analytical methods and optimisation routines [3, 17] are adequate for the outline design of many BTES. For detailed simulation of simple systems, analytical programs such as Earth Energy Designer [49] will be valuable, but as complexity increases, more complex programs such as TRNSYS [85] or finite element codes [66] may be required

Additionally, specifically for high-temperature BTES: (viii)Thermal storage efficiency increases as the size of the BTES increases. In Sweden, thermal recovery factors exceeding 50% are only predicted a heat extraction capacity of 1 GWh/year [3](ix)For a high thermal recovery factor, the annual recharge and extraction must be significantly larger than the steady-state heat loss (for a thermal recovery , the ratio of peak discharge rate to steady state heat loss should exceed 3.7 [17])

This paper has focussed also on an understanding of convective and advective processes: (i)Where hydrogeology and geotechnical considerations allow, groundwater filled open-hole BHE allow free convection cells to develop, resulting in enhanced heat transfer within a BTES and lower borehole thermal resistance, compared with a grout-backfilled borehole. The use of single pipe coaxial borehole heat exchange can result in extremely low borehole thermal resistance(ii)The presence of natural groundwater flow through a BTES array is generally regarded as negative for the efficient recovery of heat. Darcy fluxes in excess of a few cm day-1 may lead to significant heat losses. High groundwater fluxes are typically associated with high topographic gradients, nearby groundwater pumping and high hydraulic conductivities. Casing can be extended downhole to exclude permeable horizons or fractures, or conductive fractures can be grouted during drilling, to reduce groundwater throughflow, but both of these are achieved at significant costs(iii)Heating of natural groundwater in and around a BHE can result in a convection cell forming—a so-called thermosiphon. If laterally extensive, such a thermosiphon effect can lead to loss of stored heat. If local to the BHE, it may simply result in more efficient heat transfer in the BTES array. The likelihood of thermosiphon effects increases as the ground temperature increases and as the differential between BHE and ambient ground temperature increases. The likelihood of thermosiphons developing is less likely where “coolth” is being stored (i.e., heat is being extracted)

Both experience and theoretical considerations suggest that thermal recovery advantages or efficiencies exceeding 40% are rather difficult to achieve with BTES technology. This does not mean that BTES is a compromised concept, however. A thermal advantage or recovery of even 30-40% is valuable, when the alternative is to simply throw heat away as a valueless waste product.

In many European cities, disposal of waste heat from space cooling and air conditioning can be difficult and costly. Thus, if this “waste” heat can be recharged to the ground and stored with even a modest thermal storage efficiency and/or coupled to a balanced winter thermal demand, it can secure a dynamic thermal equilibrium within a BTES, allowing summer ground sourced space cooling and winter ground sourced space heating to be performed without extreme temperatures being reached. The BTES maintains a relatively high ground temperature in winter, thus ensuring that the evaporator temperature in a heat pump used for winter space heating remains several °C higher than it would have been without BTES. This can have a significant impact on the coefficient of performance of the heat pump and can dramatically improve overall energy efficiency.

Although BTES can be used for short-term energy storage, it is especially suited to seasonal storage of heat, due the ground’s enormous thermal capacity. Short-term heat storage is arguably better accomplished via tank, phase-change, or thermochemical or dynamic thermal energy storage (DTES). Such short-term storage strategies can also complement longer-term seasonal BTES storage by acting as thermal “capacitors,” evening out peaks in supply and demand.

Most importantly, a BTES should not be regarded in isolation, but merely one component (a high-capacity seasonal accumulator) within a district heating and cooling network, where networks of heat transfer pipes connect sources of heat (industries, CHP plants, waste incinerators, space cooling, and solar thermal harvesting) and “coolth” (winter dry coolers, cold lakes, and marine environments), loci of demand for heating and cooling, and short- and long-term seasonal storage.