Table of Contents Author Guidelines Submit a Manuscript
International Journal of Antennas and Propagation
Volume 2018, Article ID 9353294, 10 pages
https://doi.org/10.1155/2018/9353294
Research Article

A New Approximate Method for Lightning-Radiated ELF/VLF Ground Wave Propagation over Intermediate Ranges

1Key Laboratory of Meteorological Disaster, Ministry of Education (KLME)/Joint International Research Laboratory of Climate and Environment Change (ILCEC)/Collaborative Innovation Center on Forecast and Evaluation of Meteorological Disaster (CIC-FEMD)/Key Laboratory for Aerosol-Cloud-Precipitation of China Meteorological Administration, Nanjing University of Information Science and Technology, Nanjing, China
2Yunnan Electric Power Test Institute (Group) Co., Ltd., Electric Power Research Institute, Kunming, China

Correspondence should be addressed to Qilin Zhang; moc.361@17niliqgnahz

Received 20 December 2017; Revised 28 April 2018; Accepted 9 May 2018; Published 11 July 2018

Academic Editor: Francesco D'Agostino

Copyright © 2018 Wenhao Hou et al. This is an open access article distributed under the Creative Commons Attribution License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.

Abstract

A new approximate method for lightning-radiated extremely low-frequency (ELF) and very low-frequency (VLF) ground wave propagation over intermediate ranges is presented in this paper. In our approximate method, the original field attenuation function is divided into two factors in frequency domain representing the propagation effect of the ground conductivity and Earth’s curvature, and both of them have clearer formulations and can more easily be calculated rather than solving a complex differential equation related to Airy functions. The comparison results show that our new approximate method can predict the lightning-radiated field peak value over the intermediate range with a satisfactory accuracy within maximum errors of 0.0%, −3.3%, and −8.7% for the earth conductivity of 4 S/m, 0.01 S/m, and 0.001 S/m, respectively. We also find that Earth’s curvature has much more effect on the field propagation at the intermediate ranges than the finite ground conductivity, and the lightning-radiated ELF/VLF electric field peak value (V/m) at the intermediate ranges yields a propagation distance (km) dependence of .

1. Introduction

Lightning-radiated very low-frequency (VLF) (3–30 kHz) and low-frequency (LF) (30–300 kHz) signals can propagate along a spherical earth with finite conductivity at an intermediate distance of hundreds to a couple of thousand kilometers, and the observed lightning-radiated electromagnetic field signal would be significantly attenuated and distorted due to the propagation effects (e.g., Wait [14], Shao and Jacobson [5], and Zhang et al. [69]). In the intermediate range (within 1500 km), a planar earth assumption will bring some obvious errors, and the propagation effect of a spherical earth should be considered.

The general problem of the radiation from an antenna and the propagation of ground wave over homogeneous earth has been studied since the 1910s (e.g., Watson [10, 11], Sommerfeld [12], Van der Pol [13], and Norton [14]) and has been discussed in detail by Wait [14]. In addition, the ground wave propagation attenuation function for spherical inhomogeneous earth has been derived by Wait [3, 4]. However, the formula of attenuation function involves the roots of a complex differential equation that is related to the highly oscillatory Airy functions, and the computation of the propagation attenuation function is very difficult and time consuming. In 1980, Hill and Wait [15] generalized the previous computation methods of the attenuation function and presented an approximate method to calculate the ground wave attenuation function for arbitrary surface impedance along the spherical earth surface. In their method, different approximate formulas were used according to the phases of normalized surface impedance and a fourth-order Runge-Kutta formula had to be used to obtain the roots of differential equations. In 1993, Maclean and Wu [16] presented a Taylor series method to compute the attenuation function, and the roots of the complex differential equation were approximated by a Taylor series in their method.

In 2009, in order to study the propagation effect of lightning-radiated VLF/LF field along the spherical earth with finite conductivity, based on the formulas presented by Wait [3, 4], Shao and Jacobson [5] made some modifications for their study. In their method, a complex Newton–Raphson’s root-finding method was used to solve the complex differential equation related to the highly oscillatory Airy functions. Although this method has high accuracy and strong applicability, the iteration process may be somewhat complicated and time consuming.

Therefore, in this paper, we will present an improved new approximate method for computing the propagation effect of lightning-produced extremely low-frequency (ELF) and very low-frequency (VLF) ground wave propagation over intermediate ranges. In our method, we will divide the ground wave attenuation function presented by Wait [3, 4] into two attenuation factors representing the propagation effects of the finite ground conductivity and Earth’s curvature, and these two attenuation factors have more clear and simple expressions in the frequency domain, which can be easily calculated by multiplying them rather than solving a complex differential equation related to Airy functions.

2. Method Introduction

2.1. General Equations

For a vertical electric dipole source located on the surface of a smooth spherical earth, the vertical electric field strength at a great circle distance can be expressed as [3, 4] where is the vertical electric field of the same dipole source located on a flat and perfectly conducting ground and is the attenuation function accounting for the Earth’s curvature () and finite ground conductivity (). For an electric dipole with current moment , the produced vertical electric field on the earth surface at a long distance can be approximately calculated by the following formula, which is derived from Uman [17]. where is the current moment, is the great circle distance between the source and the receiver, is the light speed, and is the dielectric constant.

For the electromagnetic field computation of the cloud-ground lightning, both the source and the receiver are assumed to be on the earth surface and the attenuation function in (1) can be approximately expressed as where , , the normalized earth surface impedance , and the wavenumber in the earth . is the Earth’s radius, and is the angular frequency. and are the dielectric constant and magnetic permeability of free space, respectively. and are the Earth’s relative dielectric constant and conductivity, respectively. are the roots of the complex differential equation and is expressed as where and are the Airy functions defined by Miller [18].

In order to obtain the roots , Shao and Jacobson [5] used the Newton–Raphson root-finding method, and the initial guess for the root is facilitated with the mean of the two roots from and corresponding to and , respectively. This method is very complicated because the Airy functions are highly oscillatory in the entire complex plane, and we have to iterate many times to obtain roots for different angular frequencies and different earth conductivities. However, because the Newton–Raphson root-finding method has higher accuracy, we will regard the results of this method as a “true value” to evaluate the accuracy of our proposed approximation algorithm.

2.2. Our Approximate Method

The ground conductivity and Earth’s curvature are the two factors affecting the propagation of electromagnetic wave over the earth surface; in our approximate method, the propagation attenuation function in (1) is divided into two factors where and represent the propagation attenuation factors caused by the ground conductivity () and Earth’s curvature (), respectively.

The attenuation function just describes the propagation effect of planar earth with finite conductivity, without considering the curvature of the earth, and it can be expressed as below (e.g., Wait [19], Cooray [20], Zhang et al. [8, 9]): where , is the complementary error function, is the light speed, and other symbols have the same expression and meaning as shown in (3).

Attenuation function describes the effect of Earth’s curvature; it corresponds to a perfectly conducting but spherical ground, which means in (3). Then (3) and (4) can be simplified as

The parameter in (8) is the roots of (9) and can be approximately expressed as below according to Sollfrey [21]:

The error of this approximate expression (10) is 0 for , 0.0024 for , 0.0012 for , and less than 0.0005 for all higher values of [21]. Note that we have slightly modified the original formulas in Sollfrey [21] in order to let the value of in (3), (8), (10), and (11) both start at 1.

3. Results and Analysis

3.1. Validation of Our Approximate Method

Firstly, according to (3), we compute Wait’s original formula by using the Newton–Raphson root-finding method and compare our result with that presented by Shao and Jacobson [5], as shown in Figure 1. The attenuation functions in the frequency domain ranges from 0 to 1000 kHz. The ground conductivity is assumed to be 0.02 S/m, and both source and observed sites are located on the ground. It is found that the calculated attenuation function by our Newton–Raphson root-finding codes is nearly the same as that presented in [5], which means that our Newton–Raphson root-finding codes are correct.

Figure 1: Comparison of the simulated amplitude of attenuation functions in the frequency domain calculated by our Newton–Raphson root-finding codes and that presented by Shao and Jacobson [5]. The solid lines are computed for a spherical earth with an assumed conductivity of 0.02 S/m. The dashed lines are for a planar earth with the same conductivity, and only 200 and 500 km path lengths are presented for the planar earth. Note that the attenuation function value presented here is twice as much as the calculated value by (3), because Shao and Jacobson [5] included the mirror effect of perfectly conducting ground in the attenuation function.

In the following section, in order to validate the accuracy of our approximate method for predicting the lightning-radiated field in intermediate range, we adopt a commonly used current moment for lightning electromagnetic radiation at a significant distance (e.g., Cummer [22], Hu and Cummer [23]). This current moment model was originally developed by Bruce and Golde [24] and summarized by Jones [25] and is expressed as where I0 = 20 kA, v0 = 8 × 107 m/s, γ = 3 × 104/s, a = 2 × 104/s, and b = 2 × 105/s. Figure 2 shows the waveform and spectrum of this current moment.

Figure 2: The current moment waveshape (a) in the time domain and (b) in the frequency domain used for computing the lightning VLF radiation at an intermediate distance.

Figure 3 shows the comparison results of our approximate formula in (6) with Wait’s original formula in (3) for the ocean propagation path considering the curvature of the earth. It is found that our approximate method () has the same results as Wait’s method (). For the smooth ocean path with the conductivity of 4 S/m, the finite conductivity has no effect on the lightning-radiated electromagnetic field of very low frequency with tens to hundreds of kHz, and further analysis shows that the smooth ocean path has no effect on the lightning-radiated field in high frequency of tens of MHz. However, compared with the effect of the finite conductivity, Earth’s curvature has much more attenuation effect on the propagation of lightning field, and the attenuation increases with propagation distance. Within about 200 km, the effect caused by Earth’s curvature can be nearly ignored and the ocean surface approximately can be assumed to be flat. However, Earth’s curvature causes an attenuation of about 22% and 52% at the observed distance of 500 km and 1000 km, respectively.

Figure 3: Comparison of the vertical electric field calculated by our approximate formula in (6) and Wait’s original formula in (3) for the ocean propagation path considering the earth curvature at different distances of (a) 200 km, (b) 500 km, (c) 1000 km, and (d) 1500 km. Wait’s original formula is solved by the Newton–Raphson root-finding method. The polarity of a vertical electric field pointing downward is defined to be positive.

Figures 4 and 5 further show the comparison results of the vertical electric field calculated by our approximate formula and Wait’s formula for the propagation path with the conductivity of 0.01 S/m and 0.001 S/m, respectively, considering the effect of Earth’s curvature. Table 1 and Table 2 further show the detail relative errors of our approximate method for the computing of field peak () and waveform rise time (). It is found that our approximate method can also nearly produce the same result as that calculated by Wait’s formula, including of the field peak and waveform rise time, which means that our approximate method is valid and can predict the lightning-radiated field waveform over the intermediate range. Our approximate method can predict the lightning-radiated field peak value over the intermediate range with a satisfactory accuracy within maximum errors ranging from of 0.2%, 3.3%, and 8.7% for the earth conductivity of 4 S/m, 0.01 S/m, and 0.001 S/m, respectively.

Figure 4: Similar to that of Figure 3 but for finite conductivity of 0.01 S/m at the different distances of (a) 200 km, (b) 500 km, (c) 1000 km, and (d) 1500 km.
Figure 5: Similar to that of Figure 3 but for finite conductivity of 0.001 S/m at the different distances of (a) 200 km, (b) 500 km, (c) 1000 km, and (d) 1500 km.
Table 1: Relative errors of the peak value () calculated by our approximate method for different earth conductivity () varying from 0.001 S/m to 4 S/m. The propagation distances () between lightning and observation point ranges from 200 km to 1500 km.
Table 2: Errors of the waveform rise time () of the vertical electric field calculated by our approximate method for different earth conductivity () and propagation distances ().

Also, it is shown that, for the planar earth, the field peak value decreases with the decrease of the ground conductivity, and the waveform rise times increase with the decrease of the ground conductivity, which is because the high frequencies are selectively attenuated by the finitely conducting ground, causing the amplitude of the electromagnetic fields to decrease and the rise time to increase (e.g., Cooray et al. [26], Cooray [27, 28], Delfino et al. [29, 30]). For instance, for the planar earth, at the distance of 1500 km, the peak values of the vertical electric field are 0.15 V/m and 0.11 V/m for the conductivity of 4 S/m and 0.001 S/m, respectively. However, for the spherical earth, at the same observation distance, the peak values are almost the same for different earth conductivity, which implicates that for the propagation of a lightning-radiated ELF/VLF electromagnetic wave over intermediate ranges, Earth’s curvature has more attenuation effect than the finite conductivity.

In order to further explain the validity of our approximate method, we compare the attenuation functions in the frequency domain calculated using our approximate formula in (6) and Wait’s original formula in (3); the compared results are shown in Figure 6. Figure 6(a) shows the amplitude of the attenuation functions; the black line is the attenuation function proposed by Wait () and the green line is our approximate formula (). The red line is the attenuation function only accounting for Earth’s curvature (), and the blue line is the attenuation function only accounting for the ground conductivity (). It can be seen that the amplitude of the attenuation function is very different from that of , and the total attenuation function is predominantly determined by the effect caused by Earth’s curvature (). However, for the phase angle of attenuation function (see Figure 6(b)), although the phase angles of and are much different from , the value of (our approximate formula) is very similar to that of . Therefore, in the frequency domain, we also see that our approximate formula is valid, and its amplitude and phase are both similar to those of .

Figure 6: The (a) amplitude and (b) phase angle of attenuation functions (σ = 0.01 S/m and d = 1500 km). is the attenuation function proposed by Wait [3, 4], accounting for the effect of earth conductivity and curvature. Attenuation function only accounts the effect of the earth curvature and only accounts the effect of the earth conductivity. is the attenuation function calculated using our approximate method.
3.2. Dependence of the Lightning-Radiated ELF/VLF Electric Field Value on the Propagation Distance

Figure 7 shows the field peak values within the field propagation distance of 1500 km for different ground conductivities ranging from 0.001 S/m to 4 S/m. The solid curves in Figure 7 show the fitted dependences of ground wave peak value on the propagation distance for the planar earth and the spherical earth. For the planar earth, within the distance of hundreds to thousands of kilometers from the lighting strike point, the field peak value (, V/m) nearly yields a propagation distance (, km) dependence of , which is similar to that along the perfectly conducting ground or free space. However, it is worth noting that the field value propagating along the finitely conducting ground is still smaller than that for the perfectly conducting ground, especially when the ground conductivity is lower than 0.01 S/m. For the spherical earth, the field peak value (, V/m) yields a propagation distance (, km) dependence of . It is clear that the propagation attenuation is larger for spherical earth than for planar earth. This is mainly because the electromagnetic waves are prevented by the bulge of the earth from passing directly to the observation point, and the waves must reach the observation point by a process of bending around the curved surface of the earth, which will cause some extra field attenuation [31]. Therefore, in the lightning-radiated VLF field propagation at intermediate ranges of hundreds to thousands of kilometers, we should pay more attention to the effect of Earth’s curvature.

Figure 7: The lightning-radiated vertical electric field peak value as a function of propagation distance for (a) the planar earth and (b) the spherical earth. The lightning current source shown in Figure 2 is adopted. The solid curves are the fitted results of average field peak value for earth conductivity ranges from 0.001 S/m to 4 S/m.

4. Conclusion and Discussion

Lightning discharges can radiate electromagnetic waves over a wide frequency range from a few Hz to many tens of MHz, but most of the electromagnetic energy is radiated in the ELF and VLF bands, and the higher frequency component is attenuated rapidly as the propagation distance increases [22, 23, 32]. In this paper, we present a new approximate method for lightning-produced ELF/VLF ground wave propagation over intermediate ranges, which is validated by using Newton–Raphson root-finding method presented by Shao and Jacobson [5] for propagation path with different ground conductivities; we found our approximate method could predict the field peak and waveform rise time with satisfactory accuracy. The ground conductivity has little effect on the lightning-radiated ELF/VLF field peak at the intermediate ranges when it is larger than 0.01 S/m. However, Earth’s curvature has much more effect on the field propagation at the intermediate ranges than the finite conductivity. For example, the lightning-produced field peak of ELF/VLF frequency propagating over a spherical earth is just about 30%–40% of that propagating over a planar earth at a distance of 1500 km and 75%–80% for a distance of 500 km. For the planar earth, the field peak value (, V/m) nearly yields a propagation distance (, km) dependence of ; however, for spherical earth, the field peak value (, V/m) yields a propagation distance (, km) dependence of . Therefore, for the lightning-radiated VLF field propagation at intermediate ranges of hundreds to thousands of kilometers, we should pay more attention to the effect of Earth’s curvature; for example, the current moment peak value predicted from the measured far field peak will be underestimated when using a far-field-current relationship at the assumed planar earth.

Additional Points

Key Points. A new approximate method for lightning-radiated ELF/VLF ground wave propagation over intermediate ranges is presented. Lightning-radiated ELF/VLF electric field peak value at the intermediate ranges yields a propagation distance () dependence of . We should pay more attenuation to the effect of earth curvature when determining the lightning discharge parameters.

Conflicts of Interest

The authors declare that they have no conflicts of interest.

Acknowledgments

This work was supported in part by the National Key Research and Development Program of China (2017YFC1501505) and the Research and Engineering Demonstration of Comprehensive Lightning Protection System for Distribution Network Mode (YNKJQQ00000274) and in part by the Postgraduate Research & Practice Innovation Program of Jiangsu Province (KYCX17_0882).

References

  1. J. Wait, “Radiation from a vertical electric dipole over a stratified ground,” Transactions of the IRE Professional Group on Antennas and Propagation, vol. 1, no. 1, pp. 9–11, 1953. View at Publisher · View at Google Scholar · View at Scopus
  2. J. R. Wait, “Radiation from a vertical antenna over a curved stratified ground,” Journal of Research of the National Bureau of Standards, vol. 56, no. 4, pp. 237–244, 1956. View at Publisher · View at Google Scholar
  3. J. Wait, “On the excitation of electromagnetic surface waves on a curved surface,” IRE Transactions on Antennas and Propagation, vol. 8, no. 4, pp. 445–448, 1960. View at Publisher · View at Google Scholar · View at Scopus
  4. J. R. Wait, “Recent analytical investigations of electromagnetic ground wave propagation over inhomogeneous earth models,” Proceedings of the IEEE, vol. 62, no. 8, pp. 1061–1072, 1974. View at Publisher · View at Google Scholar · View at Scopus
  5. X.-M. Shao and A. R. Jacobson, “Model simulation of very low-frequency and low-frequency lightning signal propagation over intermediate ranges,” IEEE Transactions on Electromagnetic Compatibility, vol. 51, no. 3, pp. 519–525, 2009. View at Publisher · View at Google Scholar · View at Scopus
  6. Q. Zhang, X. Jing, J. Yang, D. Li, and X. Tang, “Numerical simulation of the lightning electromagnetic fields along a rough and ocean-land mixed propagation path,” Journal of Geophysical Research, vol. 117, no. D20, 2012. View at Publisher · View at Google Scholar · View at Scopus
  7. Q. Zhang, J. Yang, D. Li, and Z. Wang, “Propagation effects of a fractal rough ocean surface on the vertical electric field generated by lightning return strokes,” Journal of Electrostatics, vol. 70, no. 1, pp. 54–59, 2012. View at Publisher · View at Google Scholar · View at Scopus
  8. Q. Zhang, W. Hou, T. Ji, L. He, and J. Su, “Validation and revision of far-field-current relationship for the lightning strike to electrically short objects,” Journal of Atmospheric and Solar-Terrestrial Physics, vol. 120, pp. 41–50, 2014. View at Publisher · View at Google Scholar · View at Scopus
  9. Q. Zhang, T. Ji, and W. Hou, “Effect of frequency-dependent soil on the propagation of electromagnetic fields radiated by subsequent lightning strike to tall objects,” IEEE Transactions on Electromagnetic Compatibility, vol. 57, no. 1, pp. 112–120, 2015. View at Publisher · View at Google Scholar · View at Scopus
  10. G. N. Watson, “The diffraction of electric waves by the earth,” Proceedings of the Royal Society A: Mathematical, Physical and Engineering Sciences, vol. 95, no. 666, pp. 83–99, 1918. View at Publisher · View at Google Scholar
  11. G. N. Watson, “The transmission of electric waves round the Earth,” Proceedings of the Royal Society A: Mathematical, Physical and Engineering Sciences, vol. 95, no. 673, pp. 546–563, 1919. View at Publisher · View at Google Scholar
  12. A. N. Sommerfeld, “Propagation of waves in wireless telegraphy,” Annals of Physics, vol. 81, pp. 1135–1153, 1926. View at Google Scholar
  13. B. Van Der Pol, “Theory of the reflection of the light from a point source by a finitely conducting flat mirror, with an application to radiotelegraphy,” Physica, vol. 2, no. 1-12, pp. 843–853, 1935. View at Publisher · View at Google Scholar
  14. K. A. Norton, “The propagation of radio waves over the surface of the earth and in the upper atmosphere,” Proceedings of the IRE, vol. 25, no. 9, pp. 1203–1236, 1937. View at Publisher · View at Google Scholar · View at Scopus
  15. D. A. Hill and J. R. Wait, “Ground wave attenuation function for a spherical earth with arbitrary surface impedance,” Radio Science, vol. 15, no. 3, pp. 637–643, 1980. View at Publisher · View at Google Scholar · View at Scopus
  16. T. S. M. Maclean and Z. Wu, Radio Propagation over Ground, Chapman & Hall, London, U.K, 1993.
  17. M. A. Uman, The Lightning Discharge, Academic, San Diego, California, 1987.
  18. J. C. P. Miller, The Airy Integral, Cambridge University Press, New York, 1946.
  19. J. R. Wait, “The ancient and modern history of EM ground-wave propagation,” IEEE Antennas and Propagation Magazine, vol. 40, no. 5, pp. 7–24, 1998. View at Publisher · View at Google Scholar · View at Scopus
  20. V. Cooray, “The lightning flash,” in Power and Energy Series, vol. 34, London, U.K, IET, 2003. View at Google Scholar
  21. W. Sollfrey, Exact Solution for the Propagation of Electromagnetic Pulses Over a Highly Conducting Spherical Earth, CA: RAND Corporation, Santa Monica, 1968.
  22. S. A. Cummer, Lightning and ionospheric remote sensing using VLF/ELF radio atmospherics [Ph. D. thesis], Stanford University, 1997.
  23. W. Hu and S. A. Cummer, “An FDTD model for low and high altitude lightning-generated EM fields,” IEEE Transactions on Antennas and Propagation, vol. 54, no. 5, pp. 1513–1522, 2006. View at Publisher · View at Google Scholar · View at Scopus
  24. C. E. R. Bruce and R. H. Golde, “The lightning discharge,” Journal of the Institution of Electrical Engineers-Part II: Power Engineering, vol. 88, no. 6, pp. 487–505, 1941. View at Google Scholar
  25. D. L. Jones, “Electromagnetic radiation from multiple return strokes of lightning,” Journal of Atmospheric and Terrestrial Physics, vol. 32, no. 6, pp. 1077–1093, 1970. View at Publisher · View at Google Scholar · View at Scopus
  26. V. Cooray, M. Fernando, T. Sörensen, T. Götschl, and A. Pedersen, “Propagation of lightning generated transient electromagnetic fields over finitely conducting ground,” Journal of Atmospheric and Terrestrial Physics, vol. 62, no. 7, pp. 583–600, 2000. View at Publisher · View at Google Scholar · View at Scopus
  27. V. Cooray, “On the accuracy of several approximate theories used in quantifying the propagation effects on lightning generated electromagnetic fields,” IEEE Transactions on Antennas and Propagation, vol. 56, no. 7, pp. 1960–1967, 2008. View at Publisher · View at Google Scholar · View at Scopus
  28. V. Cooray, “Propagation effects due to finitely conducting ground on lightning-generated magnetic fields evaluated using Sommerfeld’s integrals,” IEEE Transactions on Electromagnetic Compatibility, vol. 51, no. 3, pp. 526–531, 2009. View at Publisher · View at Google Scholar · View at Scopus
  29. F. Delfino, R. Procopio, and M. Rossi, “Lightning return stroke current radiation in presence of a conducting ground: 1. Theory and numerical evaluation of the electromagnetic fields,” Journal of Geophysical Research, vol. 113, no. D5, 2008. View at Publisher · View at Google Scholar · View at Scopus
  30. F. Delfino, R. Procopio, M. Rossi, F. Rachidi, and C. A. Nucci, “Lightning return stroke current radiation in presence of a conducting ground: 2. Validity assessment of simplified approaches,” Journal of Geophysical Research, vol. 113, no. D5, 2008. View at Publisher · View at Google Scholar · View at Scopus
  31. K. A. Norton, “The calculation of ground-wave field intensity over a finitely conducting spherical earth,” Proceedings of the IRE, vol. 29, no. 12, pp. 623–639, 1941. View at Publisher · View at Google Scholar · View at Scopus
  32. S. A. Cummer, U. S. Inan, and T. F. Bell, “Ionospheric D region remote sensing using VLF radio atmospherics,” Radio Science, vol. 33, no. 6, pp. 1781–1792, 1998. View at Publisher · View at Google Scholar · View at Scopus