Abstract

The electrical rehabilitation treatments of repair mortar were performed with tetrabutylammonium bromide salt (TBAB) at an electrical current density of 5 A/m2, using two electrolytes (0.1 M NaOH and 0.1 M Na3BO3 solutions), and for two time periods (1 and 4 weeks), respectively. The average organic cation-based inhibitor’s concentration in cement mortars before and after this treatment was quantified using the UV-Vis spectroscopy. The experimental results reveal that the EICI treatment with 0.1 M Na3BO3 was more effective in injecting the inhibitor and in improving the chloride penetration resistance and compressive strength of the mortar, relative to using 0.1 M NaOH as electrolyte. In this case, after the 4-week EICI treatment, [TBA+] contents were 2.3 % and 2.4% by mass of cement mortar for uncontaminated and salt-contaminated mortars, respectively. After the 4-week EICI treatment, the apparent diffusion coefficients of chloride anion in cement mortar were decreased by 40% from 1.52 × 10−10 m2/s. The EICI treatment was able to halt the chloride-induced corrosion of the steel rebar by promoting its passivation. The 2-week EICI treatment using sodium hydroxide and sodium borate solutions decreased the corrosion current density of the rebar by 77.8% and 78.5%, respectively, approximately two months after the treatment.

1. Introduction

For reinforced concrete structures such as highway bridges, the chloride-induced corrosion of rebar has been a major problem with serious economic and safety implications [1]. Chloride, often originated from marine environments [2] or deicing applications [3], can initiate the rebar corrosion once its concentration exceeds a threshold level. The threshold chloride contents in published literature are scattered over a wide range of values, attributable to the variability in measurement methods and the numerous factors that affect steel corrosion in concrete, such as the pH of concrete pore solution, the electrochemical potential of the steel, and the physical condition of the steel/concrete interface [46]. In normal circumstances, the threshold chloride content typically varies from 0.2% to 0.5% by weight of cement [7, 8].

The durability and serviceability of concrete (or mortar) and the embedded rebar can be improved by limiting the amount of undesirable species or incorporating the amount of beneficial species in concrete [911]. However, species dissipation relying solely on natural diffusion is too slow to be effective or practical. Furthermore, the concentration of an ionic species can no longer be reduced via diffusion once a threshold level is reached, due to such mechanisms as species binding. As such, engineers have developed various approaches to enforce the transport of species under applied physical fields.

Among the methods to preserve or rehabilitate reinforced concrete structures, corrosion inhibitors are the most versatile due to the possibility of application at any time along the service life of the structure. Corrosion inhibitors can be added to the fresh concrete, dissolved into the water used for mixing [10, 1214], or can be applied on the surface of the hardened concrete [11, 1416]. In the latter case, the solution containing the inhibitor has to penetrate through the microstructure of hardened concrete towards the rebar.

Electrical injection of corrosion inhibitor (EICI) emerged recently as a promising solution to rebar corrosion in concrete structures [1723]. Pan et al. [18] conducted a laboratory investigation to identify available organic cation-based inhibitors for EICI and a subsequent numerical investigation to examine the effect of various factors (inhibitor type, external current density, and treatment time) on the efficiency of EICI into concrete. Liu and Shi [19] presented a comprehensive review on the state of the knowledge about EICI, which covered both laboratory and numerical studies. Kubo et al. [21] reported “a site trial of (EICI) applied to a 40-year-old carbonated high-speed railway viaduct in Tokyo.” Sánchez and Alonso [20] reported that the injection of nitrite (an anion-based inhibitor) was facilitated by using a nontraditional configuration featuring an external cathode (instead of anode) to the rebar.

As an organic corrosion inhibitor, tetrabutylammonium bromide (TBAB) is expected to mitigate the corrosion of steel by forming an adsorbed film onto the metallic substrate and thus acting as a barrier to limit the access of chloride and oxygen to the steel surface. In other words, it is a cathodic inhibitor [24, 25]. A [TBA+] concentration as low as 5 mM on steel can effectively inhibit the corrosion of steel in a typical chloride-contaminated mortar (pore solution of pH 13 with 3.0 wt.% NaCl) [18]. The inhibition function of [TBA+] generally increases with its concentration, and a concentration above 10 mM can be expected to form a reliable protective film on the steel surface. The apparent diffusion coefficient of [TBA+] ions in an ordinary Portland cement mortar was reported by Pan et al. [18] to be 1.2 × 10−11 m2/s. By using the two-dimensional finite element model, the concentration evolution of the TBAB inhibitor and chloride were predicted in concrete. To reach a 54 mM [TBA+] concentration at the critical location on steel rebar embedded in 2-inch thick concrete, the treatment time (under an electric field of 5 A/m2 in NaOH electrolyte) would be 16 weeks.

Repair mortar is commonly used to rehabilitate reinforced concrete structures or components that exhibit a relatively high level of distress. The mortar is often applied to the bridge or building structure once the damaged concrete is removed and corroded rebar is cleaned [9, 26, 27]. While the application of EICI treatment has been proven effective in enforcing corrosion inhibitors into preexisting concrete structure, little knowledge is available in the published domain regarding its effect on the property of repair mortar or on the corrosion of the embedded steel. Research is also needed in identifying an effective external electrolyte for reducing the treatment time. In this context, this work aims to address such knowledge gaps and shed more light on this promising technology of electrochemical rehabilitation.

2. Materials and Methods

2.1. Materials

Tetrabutylammonium bromide was obtained from Sigma Aldrich (USA). The cement mortars used ASTM Type I Portland Cement (Vietnam Portland PC30) [28]. The fine aggregate used was river sand sieved to allow a maximum aggregate size of 2 mm before water-saturating, proportioning, and admixing. The steel rebar, purchased from Vietnam Hoa Phat Steel Co. Ltd. (Hung Yen, Vietnam), was low carbon steel wire rod (diameter of 6.0 mm, JIS G3505-1996, SWRM6), with the following chemical composition: C (≤0.08%), Mn (≤0.6%), P (≤0.045%), and S (≤0.045%).

Steel rebar was embedded in cement mortar, with a mortar cover of 25 mm (Figure 1). To simulate salt-contaminated repair mortar, the cement mortar was made with the weight ratio of cement : sand : water : sodium chloride of 1 : 1.75 : 0.45 : 0.005. Some mortars were made without any sodium chloride added, to simulate uncontaminated repair mortar. Note that the thickness of repair mortar is assumed to be 25 mm (1′′) in this case, while in practice the repair mortar could be up to 3 inches thick. The repair mortar in this work features a water/cement ratio (w/c) of 0.45, while in practice the repair mortar could feature a w/c of 0.4 or lower.

After mixing, the fresh mixture was poured into polypropylene plastic molds to form Φ 100 mm × 50 mm cylindrical samples. The sample without added sodium chloride was also fabricated. The steel reinforced cement mortar specimens were demolded after 24 h and then cured in a wet chamber (relative humidity in excess of 95%, temperature of 25°C) for 28 days, before being subjected to the electrochemical tests.

2.2. EICI Experimental Setup

The EICI treatment was performed by using a constant current with 0.1 M NaOH or 0.1 M Na3BO3 solutions containing 25 mM TBAB as the electrolyte and stainless-steel 304 mesh as the external anode. The solution was replaced every 2 to 3 days to maintain alkalinity.

For duplication of each test, 10 steel reinforced mortars were connected in series. Each steel rod contained inside the mortar was connected to a negative terminal of a power supply so that the steel reinforcement acted as a cathode. At the same time, the stainless-steel mesh was connected to the positive terminal of the power supply, which acted as the anode. The electrical current density delivered on the steel rod surface was controlled at 5 A/m2. This treatment lasted one to four weeks, based on the experimental design.

2.3. Quantifying Inhibitor Concentration in Cement Mortars

The ultraviolet- (UV-) visible absorbance spectroscopy is a proven technology for accurately detecting organic chemicals in aqueous solutions [29, 30]. In this study, Spectroscopy CINTRA 40 (USA) was used.

At the end of the EICI treatment (after one or four weeks), the mortar specimens were cut into slices and later powdered. The powder was then screened through a 300 μm sieve, oven-dried at 80°C overnight, and cooled to room temperature. Five grams of dry mortar powder was added to 50 mL of the distilled water solution and then sonicated for 1 hour before the solution was subjected to UV-Vis spectroscopy. The pH of this solution was about 11.

By testing four standard alkaline aqueous solutions (pH 11) of TBAB (5 mM to 20 mM), a calibration curve was established to correlate the optical density at the characteristic peak (Figure 2) and the inhibitor concentration. The calibration curve was then used to determine the TBAB concentration in cement mortar samples after EICI treatments. As shown in Figure 3, the calibration curves established with these standard solutions of 1 mM NaOH (pH 11) showed a strong linear correlation between the natural logarithm of the TBAB concentration and optical density (with high -square value).

2.4. Electrochemical Characterization of Rebar in Cement Mortar

Approximately 2 months after the EICI treatment ended, the electrochemical response of the rebar was measured to evaluate the effectiveness of the treatment and the ability of the rebar to be repassivated. The untreated mortar specimens were used as controls. Electrochemical measurements were conducted using a three-electrode system. The steel rebar in the cement mortar served as the working electrode, while the counter electrode and the reference electrode used were a platinum mesh and a saturated calomel electrode (SCE), respectively. To resolve the effect of the EICI test on the corrosion of steel rebar, the potentiodynamic weak polarization method was employed.

In the potentiodynamic weak polarization test, the steel was polarized around its open circuit potential (−30 mV to 30 mV versus OCP) by a direct current (DC) signal at a scan rate of 0.2 mV/s. Polarization resistance () is defined by the slope of the potential current density plot at the corrosion potential. Corrosion current density () is calculated from , assuming  mV or  mV, depending on the active or passive state of the rebar. Corrosion activity of rebar could be defined simply by using its OCP value following ASTM C 876 Standard (when the OCP > −0.125, the probability of no corrosion > 90%).

2.5. Testing Compressive Strength of Cement Mortar

The compressive strength test was carried out by breaking cylindrical mortar specimens (56 mm in diameter and 56 mm in length) in a hydraulic universal testing machine (Model WE-1000B, Jinhua Jinshi) using a loading rate of 0.6 MPa/s with the load and displacement data were automatically recorded. The mortar cylinders had the rebar inside, which was cut off at the end. The cylinders were each surface-ground and then the ends were polished with fine silicon carbide paper to ensure a uniform surface finish (and thus a uniformly distributed load) before being subjected to the compressive strength test. The ultimate compressive strength then was calculated by dividing the load at failure by the cross-sectional area resisting the load. The untreated specimens, also cured for 28 days after casting, were subjected to the identical procedure. The test results are the average of specimens made from the same batch mixture.

2.6. Electromigration Test

To test the chloride permeability of cement mortars, electromigration experiments were performed using the two half-cells as shown in Figure 4.

The polypropylene plastic cells feature a disc-shaped mortar specimen that separates the chloride anion source (3% NaCl) and the destination solution (4.3% NaNO3). The ~20 mm thick mortars discs were cut from the center of either EICI-treated mortars or the untreated control mortar (uncontaminated sample). The exposed rebar surfaces were sealed using an epoxy resin. Each of the two half-cells contained one platinum electrode with an exposed surface area of 1 cm2. Once the mortar disc, electrolytes, and electrodes were in place, a 20-volt DC electric field was maintained across the disc through the two platinum electrodes in the two compartments. During the test, readings of open circuit potential (OCP) of the calibrated Ag/AgCl chloride sensor in the destination solution were taken periodically, using a mercury/mercurous sulfate electrode as the reference electrode.

The Ag/AgCl sensor was used to monitor the evolution of free chloride anion (Cl) concentration in the destination solution, as its OCP data was compared against a standard calibration curve correlating potential readings with known Cl concentrations.

The method used to calculate the apparent diffusion coefficient of Cl in cement mortars is described as follows: under an externally imposed electric field with an intensity of , the mobility of ions (, the average velocity of ions per unit of electric field) is related to the diffusion coefficient through the Nernst-Einstein equation [31]:where is charge number, is Faraday constant, is gas constant, and is absolute temperature.

The chloride ion mobility can be calculated from the time required for the chloride front to penetrate a depth of the specimen [32]:

Therefore, the diffusion coefficient of Cl in cement mortars can be estimated using the following equation:

2.7. Morphological Study

The surface morphology of cement mortar samples, before and after EICI treatment, was studied using Field Emission Scanning Electron Microscopy (FESEM). The mortar surface was coated with a very thin carbon layer to avoid the charging effect caused by the nonconductive nature of epoxy coatings and to get high resolution material. The mortar surface morphology was evaluated using a FE-SEM S4800 (Hitachi, Japan) system, which offers an ultrahigh resolution at relatively low voltage.

3. Results and Discussion

3.1. [TBA+] Content by Time of EICI Treatment

Figures 5 and 6 present the UV-Vis spectra of cement mortar samples after EICI treatment in 0.1 M sodium hydroxide and sodium borate solutions, respectively.

As can be seen in Figure 5, when using sodium hydroxide solution, the [TBA+] content in cement mortar (at distance of 10 mm from rebar) increased with the time of EICI treatment, for both uncontaminated and contaminated samples. For the contaminated mortar, after one week of treatment, [TBA+] level was 1.37% by mass of cement mortar. This content reached 2.54% after four weeks of EICI treatment.

For samples treated in sodium borate electrolyte (Figure 6), similar results are obtained after one week of treatment. However, extending the time of treatment did not increase [TBA+] content for both contaminated and uncontaminated samples.

Data obtained from the UV-Vis spectra indicated that EICI-treated samples were found to contain the inhibitor concentration [TBA+], as shown in Tables 1 and 2, reported by weight of the mortar. As can be seen in Table 1, the increasing content of [TBA+] during the treatment in sodium hydroxide solution can be explained by the development of microcracks, as reported by Buenfeld and Broomfield [33]. The alkaline sodium borate electrolyte, acting as a buffer solution, may help to keep the mortar free from the development of microcracks due to the EICI treatment, whereas even though the 0.1 M NaOH solution had the higher pH value, the large amounts of hydroxide ions might be driven out of the mortar and into the electrolyte during the long EICI process. An acidic electrolyte might result in etching of the mortar surface and in the production of chlorine gas (for Cl contaminated samples).

Data from Table 2 indicated that extending the time of treatment did not increase [TBA+] content. The higher mortar compressive strength after 4-week treatment in sodium borate electrolyte may be related to the physicochemical binding of [TBA+] with cement hydrates, which also decreased ionic permeability of the mortars. These two mechanisms help explain the lower [TBA+] content observed (Figures 7 and 8).

3.2. Effect of EICI on the Compressive Strength of Mortars

The strength of concrete originates from the strength of the hardened cement paste, which in turn originates from the hydration products. The major portion of the hydration products is in the form of a rigid gel (Calcium Silicate Hydrate (C-S-H) gel). It is believed that C-S-H gel is responsible for the strength and cohesion of concrete structures.

The results of compressive strength tests for the cement mortars before and after EICI treatment in sodium hydroxide and sodium borate solutions are shown in Figures 7 and 8, respectively. As can be seen in these figures, the EICI treatment improved the compressive strength of the mortar.

As can be seen in Figures 7 and 8, the EICI treatment improved the compressive strength of the mortar. In comparison to the electrolyte solution, for contaminated samples, the compressive strengths obtained by treatment in sodium borate solution were higher than those from the sodium hydroxide solution (up to a 92% strength increase). Thus, the higher mortar strength after EICI test might be also attributable to the presence of inhibitor in the mortar.

Different from the 0.1 NaOH solution, the 0.1 M Na3BO3 solution (pH 9) is a pH-buffered electrolyte, which could maintain alkalinity during the long time of EICI treatment, which prevents the electrolyte from becoming too acidic during the test. The observed strength changes may be attributed to the interactions of anions (OH or versus Cl) transported in the mortar (via diffusion or electromigration) with cement hydrates, which merits further investigation.

3.3. Effect of EICI on the Mortar Permeability

Figure 9 shows the chloride concentrations in the anolyte (destination solution) as a function of time during the electromigration test for mortars with or without EICI treatment. As can be seen in this figure, after EICI treatment in both of the NaOH and Na3BO3 solutions, the value of increased. The calculated value thus was decreased by 38%, from 1.0 × 10−10 m2/s (without EICI treatment) to 6.2 × 10−11 m2/s (after 4 weeks of EICI treatment in NaOH solution).

Regarding the value for control sample (without EICI treatment), it is much higher than the value of 7.3 × 10−11 m2/s, reported by Nguyen et al. [34], which was obtained for the mortars as-prepared without rebar inside. In this study, mortar discs (with rebar inside) were sliced into ~20 mm width slice, along the 100 mm length of the steel reinforced mortar. Therefore, the method preparing mortar discs for electromigration test might produce microcracks inside the discs.

Transport of ionic and molecular species in mortar is mainly through the pore solution. Thus, by EICI treatment, [TBA+] cations may chemically and physically react with cement hydrates and lead to a less permeable microstructure of cement mortars.

The FESEM test revealed that the [TBA+] not only led to denser cement mortar but also changed the morphology of cement hydration products. Figures 10(a)10(d) show the FESEM images of cement mortars before and after EICI treatment. As shown in Figures 10(c) and 10(d), after EICI treatment, the cement mortars featured denser and more compact microstructure, which is likely attributed to the chemical and physical binding of [TBA+] to the C-S-H gel and other cement hydrates. These physicochemical changes in the mortars after the EICI treatment are likely responsible for the observed increases in their compressive strength (as seen in Figure 7).

3.4. Effect of EICI on Corrosion State of Steel Rebar

Tables 3 and 4 present the corrosion potential (), polarization resistance (), and corrosion current () values deduced from the weak polarization tests for samples with or without EICI treatment in sodium hydroxide solution, for uncontaminated and contaminated samples, respectively. As can be seen in these tables, the presence of chloride in cement mortar increased significantly the corrosion current of rebar (up to 8.6 times current increase). Tables 5 and 6 present also the corrosion potential (), polarization resistance (), and corrosion current () values deduced from the weak polarization tests for samples with or without EICI treatment in sodium borate solution, for uncontaminated and contaminated samples, respectively. It can be observed from these tables that, after EICI treatment, the corrosion potentials of all samples were more positive and it was possible to passivate the steel.

Figures 11 and 12 summarize the polarization resistance values of steel rebar embedded in chloride-contaminated cement mortar before and after EICI treatment in sodium hydroxide and sodium borate solutions, respectively. Regarding the values, except the uncontaminated samples after EICI treatment in sodium hydroxide solution, increased after EICI treatment. The higher increase was obtained with contaminated samples; thus the EICI treatment was more effective for chloride-contaminated mortar. Regarding the values shown in Tables 36, for chloride-contaminated cement mortars, after 2 weeks of EICI treatment by both of the electrolytes, decreased by about 78%. However, for uncontaminated cement mortars, after 2 weeks of EICI treatment, increased. Kubo et al. [21] also reported an increase of after EICI for the real carbonated reinforced concrete located in Tokyo city. In their work, the EICI treatment was carried out during 1 week at a constant current density of 5 A/m2 using the ethanolamine solution. After EICI test, increased by 88.9% from the value of - mA/cm2 (before EICI test). In these cases, the short time EICI treatment (1-2 weeks) might harm the uncontaminated reinforced mortar. This is likely attributed to the alternation of concrete microstructure and composition of mortar pore solution by the externally applied electric field. On the other hand, for contaminated samples treated by NaOH and Na3BO3 solutions, the inhibition efficiencies after EICI treatment for 4 weeks are 73.5% and 43%, lower than those after treatment for 2 weeks, 77.9% and 78.5%, respectively. Thus, the long time EICI treatment (4 weeks) might harm the contaminated reinforced mortar.

4. Conclusions

The main findings of this investigation include the following:(i)EICI treatment was more effective in injecting organic inhibitor when using sodium hydroxide solution as electrolyte. In this case, after 4-week EICI treatment, [TBA+] content was 2.0% and 2.5% by mass of cement mortar, for uncontaminated and chloride-contaminated samples, respectively.(ii)The potentiodynamic weak polarization tests showed that EICI treatment halted chloride-induced corrosion of the rebar. After 2 weeks of EICI treatment using 0.1 M NaOH and 0.1 M Na3BO3 solutions, the values of decreased by 77.8% and 78.5%, respectively.(iii)The electromigration test showed that EICI treatment improved the chloride penetration resistance of the mortar, as indicated by the reduced apparent diffusion coefficients of chloride anion, . The calculated values thus were decreased by 38% from 1.0 × 10−10 m2/s. The FESEM test revealed that the [TBA+] not only led to denser cement mortar but also changed the morphology of cement hydration products.(iv)Under the investigated conditions, the EICI treatment significantly improved the compressive strength of cement mortars. This benefit was greater when using sodium borate solution (up to 92% strength increase).