Enhanced Particle Swarm Optimization-Based Feeder Reconfiguration Considering Uncertain Large Photovoltaic Powers and Demands
Table 5
Optimal results after the feeder reconfiguration using the proposed method.
| Scenario | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
| Voltage magnitude (p.u.) | | | | | | | | | V1 | 1.050 | 1.050 | 1.050 | 1.050 | 1.046 | 1.050 | 1.037 | 1.040 | V13 | 1.013 | 1.024 | 1.008 | 1.009 | 1.009 | 1.004 | 1.004 | 0.994 | V26 | 1.036 | 1.032 | 1.038 | 1.030 | 1.050 | 1.026 | 1.050 | 1.050 | V44 | 0.994 | 1.014 | 1.012 | 1.016 | 0.978 | 0.998 | 1.015 | 1.014 | V61 | 1.050 | 1.047 | 1.029 | 1.023 | 1.050 | 1.050 | 1.030 | 1.050 | V70 | 1.025 | 1.050 | 1.050 | 1.050 | 1.016 | 1.035 | 1.050 | 1.046 | Reactive power (kVAr) | | | | | | | | | Q13 | 109.686 | 185.963 | 81.792 | 82.204 | 111.298 | 54.847 | 145.300 | 56.510 | Q26 | 358.888 | 321.407 | 376.783 | 302.842 | 415.400 | 266.856 | 419.470 | 411.446 | Q44 | 130.073 | 56.783 | 33.835 | 87.807 | 49.378 | 55.037 | 76.380 | 105.918 | Q61 | 541.639 | 545.250 | 392.784 | 345.034 | 532.708 | 530.894 | 404.858 | 532.886 | Real power at swing bus (kW) | | | | | | | | | P1 | 1209.57 | 1149.71 | 1223.55 | 1324.58 | 928.005 | 1415.21 | 702.954 | 885.934 | P70 | 1081.67 | 1726.06 | 1974.25 | 1959.51 | 1016.86 | 1356.16 | 1893.88 | 1508.39 | Loss (kW) | 93.979 | 78.674 | 92.627 | 93.126 | 111.735 | 101.945 | 84.322 | 86.471 | Aggregating loss = 92.875 kW |
|
|