Effect of Neutral Grounding Protection Methods for Compensated Wind/PV Grid-Connected Hybrid Power Systems

Table 1

Minimization of faulted phase currents at fault location X the on wind/PV GCS due to the SCF for different fault resistances.

Fault resistance (Rf) (Ω)Maximum magnitude of fault current (Amp)Current Minimization (%)
SCF
Phase APhase BPhase C

1526359765767−3.35
40.58338238343791−60.85
48312535833544−72.12
60280132703239−88.59