Effect of Neutral Grounding Protection Methods for Compensated Wind/PV Grid-Connected Hybrid Power Systems
Table 2
A comparison between solid grounding and Peterson coil grounding of 58.6 H inductance on the wind/PV GCS under various fault conditions.
| Fault type | Maximum magnitude of fault current at fault location X (Amp) | Current minimization (%) | Wind/PV GCS with solid grounding | Wind/PV IGs with Peterson coil grounding | Phase A | Phase B | Phase C | Phase A | Phase B | Phase C |
| SCF | 5011 | 6176 | 5832 | 2698 | 4251 | 3985 | −45.28 | SLG fault | 2096 | — | — | 2616 | — | — | 19.88 | DLG fault | 5119 | 4782 | — | 3208 | 3338 | — | −43.26 |
|
|