Effect of Neutral Grounding Protection Methods for Compensated Wind/PV Grid-Connected Hybrid Power Systems

Table 4

Minimization of fault currents at busbar Z on the wind/PV GCS due to the SCF for different values of Peterson coil.

Fault inductance (Lf) (H)Maximum magnitude of fault current with the SCF (Amp)Current minimization (%)
Phase APhase BPhase C

1335649804801−3.69
10306147004495−9.87
30279641163850−25.46
58.6246635653439−44.85
65240834943338−47.79