Number | Materials | Specs & type | Unit | Quantity | Remarks |
|
1 | Modules | 300 Wp | Each | 50001 | Ploy crystal |
2 | Mount structures | Steel structure, 150 MWp | Set | 13360 | Fixed, 28° |
3 | Combiner box | 16 to 1 | Each | 1500 | 15 A fuse isolating |
4 | Integrative inverter | 500 kW AC | Set | 300 | Isolating transformer excluded |
5 | 22 kV box-type transformer | S11-1000/500/5000 kVA 22 ± 2 × 2.5%/0.315/0.315 kV | Each | 150 | |
6 | Arc suppression earthing transformer | 400 kVA/22 kV/0.4 kV, arc suppression coil 1200 kVA | Each | 6 | Dry type |
7 | SVG | 22 kV, −10 ~ +10 MVar | Each | 6 | Step-down type |
8 | Switchgear | Ir = 1250, 2500 A, Ib = 31.5 kA (4 s), (3 s) | Each | 40 | |
9 | 220 kV main transformer | SFZ11-50000/220, 220 ± 8 × 1.25%/22 kV | Set | 6 | 220 kV main transformer |
10 | 220 kV main transformer spacing interval | Outgoing line spacing interval and PT | | 2 | — |
11 | Breaker | type: LW36-220, breaker, Ie = 2000 A, Ib = 50 kA | | 6 | // |
12 | Double earthing isolator | type:GW4-220D(W) (double), 1250 A-125 kA | | 6 | // |
13 | Current transformer | 10P40/10P40/10P40/10P40/0.5S/0.2S, 2 × 600/5 A | | 36 | // |
14 | Single earthing isolator | GW4-220D (W) (single), 2000 A-125 kA | | 6 | // |
15 | Secondary equipment line protection and surveillance | Item | 1 | | |
16 | Civil engineering building | Support equipment foundation, the fittest | Item | 1 | |
17 | Cable | AC/DC type, fiber optic | Set | 1 | Roll bundle double 100 |
18 | Monitoring system | SCADA/PLCs | Set | 1 | Mbps industrial Ethernet network structure |
19 | Substation | AIS (air-insulated switchgear) | Set | 1 | 220 kV line grid POI |
|