Research Article

Multiple DGs for Reducing Total Power Losses in Radial Distribution Systems Using Hybrid WOA-SSA Algorithm

Table 5

Performance of WOA-SSA compared with those of the standard case, WOA, and SSA on an IEEE 13-bus RDN with multiple DGs.

DG no.ParticularsBase case without DGAlgorithms
WOASSAWOA-SSA

2Candidate buses645, 675645, 675611, 675
Optimal DG size (kW)438.9
2090.454
1794.687
2007.456
361.804
2024.676
Total DG size (kW)2529.3543802.1432386.48
Total power losses (kW)110.94874.87174.8574.838
% power loss reduction32.5%32.5%32.6%
Minimum voltage (p.u.), bus0.97288, 6110.99202, 6340.99293, 6340.99294, 634
Maximum voltage (p.u.), bus1.04, 6751.0394, 6321.0387, 6321.0385, 632
Mean voltage (p.u.)1.00371.01151.01131.0113
Standard deviation voltage (p.u.)0.0206860.0140660.0135670.013665
Computational time (S)450506440

3Candidate buses680, 611, 675645, 646, 675611, 645, 675
Optimal DG size (kW)4705.369
1434.894
2039.296
2877.887
2928.977
1982.26
1673.064
665.587
2022.381
Total DG size (kW)8179.5597789.1244361.032
Total power losses (kW)110.94874.83874.85274.832
% power loss reduction32.6%32.5%32.6%
Minimum voltage (p.u.), bus0.97288, 6110.99257, 6340.9922, 6340.99276, 634
Maximum voltage (p.u.), bus1.04, 6751.039, 6321.0389, 6321.0389, 632
Mean voltage (p.u.)1.00371.01141.01131.0112
Standard deviation voltage (p.u.)0.0206860.0137570.0134270.013658
Computational time (S)475550539

4Candidate buses646, 692, 611, 675652, 611, 645, 675645, 646, 634, 675
Optimal DG size (kW)32.418
8.923
2879.988
2013.935
631.618
664.226
646.792
2004.942
2786.184
3093.839
1591.05
1921.799
Total DG size (kW)4935.2643947.5789392.872
Total power losses (kW)110.94874.93774.83472.762
% power losses reduction32.5%32.6%34.4%
Minimum voltage (p.u.), bus0.97288, 6110.99285, 6340.99295, 6340.99008, 634
Maximum voltage (p.u.), bus1.04, 6751.0388, 6321.0387, 6321.0341, 632
Mean voltage (p.u.)1.00371.01131.01131.0099
Standard deviation voltage (p.u.)0.0206860.0136090.0135580.012129
Computational time (S)542550540

5Candidate buses632, 684, 611, 634, 675634, 633, 632, 611, 675611, 684, 634, 692, 675
Optimal DG size (kW)3124.516
4176.683
2663.978
1.041
2036.525
4020.34
3095.887
1498.569
3793.034
2007.206
1252.741
720.198
1922.402
265.501
2042.348
Total DG size (kW)12002.74314415.0366203.19
Total power losses (kW)110.94874.84574.83974.834
% power losses reduction32.5%32.6%32.6%
Minimum voltage (p.u.), bus0.97288, 6110.99259, 6340.99291, 6340.99252, 634
Maximum voltage (p.u.), bus1.04, 6751.039, 6321.0387, 6321.039, 632
Mean voltage (p.u.)1.00371.01141.01131.0114
Standard deviation voltage (p.u.)0.0206860.0137450.0135740.013781
Computational time (S)626658614

6Candidate buses652, 680, 645, 633, 671, 675646, 680, 632, 671, 684, 675645, 652, 633, 684, 671, 675
Optimal DG size (kW)1760.35
982.198
2423.365
3418.675
3279.92
1991.147
3087.157
1820.051
887.208
1812.839
1620.26
2025.412
1704.998
2942.587
3221.933
818.585
188.281
2032.203
Total DG size (kW)13855.65511252.92710908.587
Total power losses (kW)110.94874.87274.86974.864
% power loss reduction32.5%32.5%32.5%
Minimum voltage (p.u.), bus0.97288, 6110.99306, 6340.99269, 6340.99261, 634
Maximum voltage (p.u.), bus1.04, 6751.0386, 6321.0389, 6321.039, 632
Mean voltage (p.u.)1.00371.01131.01141.0114
Standard deviation voltage (p.u.)0.0206860.0134960.013690.013731
Computational time (S)677692659