(a) Cooling characteristics of the heat pump |
| (°C) | 0 | 6 | 12 | 18 | Power | COP | Power | COP | Power | COP | Power | COP |
| (°C) | | | | | | | | | 5 | 17.43 | 2.66 | 19.64 | 2.70 | 21.85 | 2.78 | 24.05 | 2.84 | 10 | 17.49 | 2.83 | 19.33 | 2.87 | 21.19 | 2.90 | 23.03 | 2.93 | 20 | 15.82 | 3.43 | 17.40 | 3.50 | 17.92 | 3.56 | 21.56 | 3.63 | 29 | 14.31 | 3.80 | 15.92 | 3.85 | 17.52 | 3.90 | 19.13 | 3.95 | 32 | 14.24 | 3.98 | 15.68 | 4.03 | 17.13 | 4.08 | 19.57 | 4.13 | 38 | 13.32 | 4.30 | 14.66 | 4.33 | 15.99 | 4.36 | 17.33 | 4.40 |
|
|
(b) Heating characteristics of the heat pump |
| (°C) | 35 | 40 | 45 | 50 | Power | COP | Power | COP | Power | COP | Power | COP |
| (°C) | | | | | | | | | −4 | 18.72 | 2.52 | 18.22 | 2.80 | 17.72 | 3.08 | 17.21 | 3.36 | 0 | 22.37 | 2.71 | 21.77 | 3.00 | 21.17 | 3.29 | 20.57 | 3.58 | 4 | 26.02 | 2.90 | 25.32 | 3.20 | 24.63 | 3.50 | 23.93 | 3.80 | 10 | 30.27 | 3.37 | 29.46 | 3.69 | 28.66 | 4.00 | 27.85 | 4.32 | 20 | 39.22 | 4.24 | 38.17 | 4.60 | 37.12 | 4.96 | 36.07 | 4.32 | 29 | 43.71 | 4.82 | 42.55 | 5.20 | 41.39 | 4.58 | 40.23 | 4.96 |
|
|