Critical Analysis and Application of Net-Metering Practice in MEPCO
Table 14
Voltage level comparison for all cases.
| Bus ID | Case 1: when Bus22 load ON/solar OFF | Case 2: when Bus22 load ON/solar ON | Case 3: when Bus22 load OFF/solar ON |
| Bus1 | 100% | 100% | 100% | Bus2 | 99.36% | 99.39% | 99.41% | Bus3 | 99.18% | 99.21% | 99.23% | Bus4 | 97.69% | 97.72% | 97.74% | Bus5 | 98.78% | 98.81% | 98.83% | Bus6 | 98.89% | 98.92% | 98.94% | Bus7 | 99% | 99.03% | 99.05% | Bus8 | 98.66% | 98.69% | 98.72% | Bus9 | 97.58% | 97.61% | 97.63% | Bus10 | 97.95% | 98% | 98.04% | Bus11 | 99.03% | 99.08% | 99.12% | Bus12 | 99.14% | 99.19% | 99.23% | Bus13 | 98.78% | 98.83% | 98.87% | Bus14 | 97.83% | 97.88% | 97.92% | Bus15 | 97.7% | 97.75% | 97.79% | Bus16 | 98.8% | 98.86% | 98.9% | Bus17 | 99.03% | 99.08% | 99.13% | Bus18 | 98.91% | 98.96% | 99.01% | Bus19 | 97.94% | 97.99% | 98.03% | Bus20 | 99.06% | 99.15% | 99.23% | Bus21 | 97.78% | 98.18% | 98.76% | Bus22 | 97.55% | 98.3% | 99.1% |
|
|