Test Verification of the Standard Compilation of “Energy-Saving Monitoring for Refrigeration Storage System” in Beijing
Table 1
Comparison of the temperature measurement position in storage.
(a) |
| Collection interval (5 min) | Average value of all measuring points (°C) | Average value of central regional (°C) | Deviation (°C) |
| Working temperature of cold storage | −17.41 | −17.36 | −0.05 | Highest temperature of cold storage | −14.87 | −14.87 | 0 | Lowest temperature of cold storage | −18.68 | −18.53 | −0.15 |
|
|
(b) |
| Collection interval (10 min) | Average value of all measuring points (°C) | Average value of central regional (°C) | Deviation (°C) |
| Working temperature of cold storage | −17.42 | −17.37 | −0.05 | Highest temperature of cold storage | −15.13 | −14.89 | −0.24 | Lowest temperature of cold storage | −18.62 | −18.47 | −0.15 |
|
|