Research Article
Test Verification of the Standard Compilation of “Energy-Saving Monitoring for Refrigeration Storage System” in Beijing
Table 8
Statistical table of energy consumption coefficient for different seasons and cold storages.
| Storage number | Design of storage temperature | Volume (m3) | Energy consumption coefficient in winter (kWh/(m3·24h)) | Energy consumption coefficient in summer (kWh/(m3·24h)) | Calculated value of energy consumption coefficient index (kWh/(m3·24h)) | Conclusion |
| 1 | −18°C | 296 | 0.288 | 0.368 | 0.45 | Qualified | 2 | −18°C | 204 | / | 0.643 | 0.45 | Unqualified | 3 | −18°C | 4847 | 0.289 | 0.362 | 0.33 | Unqualified | 4 | −18°C | 131747 | 0.110 | 0.213 | 0.27 | Qualified | 5 | −18°C | 84602 | / | 0.191 | 0.27 | Qualified | 6 | Mix | 72320 | / | 0.379 | 0.27 | Unqualified | 7 | 4°C | 775 | / | 0.109 | 0.22 | Qualified |
|
|