Applying Hybrid PSO to Optimize Directional Overcurrent Relay Coordination in Variable Network Topologies
Table 1
Primary/backup relay pairs and the fault currents in a fixed network topology.
| P/B relay pairs | Near-end fault current (A) | Far-end fault current (A) | Primary relay no. | Backup relay no. | Primary relay | Backup relay | Primary relay | Backup relay |
| 1 | 6 | 3230 | 3230 | 995 | 995 | 8 | 9 | 6080 | 1160 | 2990 | 553 | 8 | 7 | 6080 | 1880 | 2990 | 78* | 2 | 1 | 5910 | 993 | 3550 | 393 | 9 | 10 | 2480 | 2480 | 1160 | 1160 | 2 | 7 | 5910 | 1880 | 3550 | 746 | 3 | 2 | 3550 | 3550 | 2240 | 2240 | 10 | 11 | 3880 | 2340 | 2480 | 1140 | 6 | 5 | 6100 | 1200 | 3230 | 626 | 6 | 14 | 6100 | 1870 | 3230 | 78# | 13 | 8 | 2980 | 2980 | 986 | 986 | 14 | 9 | 5190 | 1160 | 1870 | 151# | 7 | 5 | 5210 | 1200 | 1890 | 181# | 14 | 1 | 5190 | 993 | 1870 | 986* | 7 | 13 | 5210 | 985 | 1890 | 994* | 4 | 3 | 3780 | 2240 | 2400 | 1050 | 11 | 12 | 3700 | 3700 | 2340 | 2340 | 5 | 4 | 2400 | 2400 | 1200 | 1200 | 12 | 13 | 5890 | 985 | 3700 | 433 | 12 | 14 | 5890 | 1870 | 3700 | 821 |
|
|
through DOCRs fault current flow reverse direction.
#Passing through DOCRs fault current fall below their pickup current.
|