Research Article

Predictive Models of Current, Voltage, and Power Losses on Electric Transmission Lines

Table 2

Predicted power losses for a 330 kV single circuit of the typical transmission network.

Length of line in km Power losses (in MW) for a load of 100 MW
Power losses (in MW) for a load of 200 MW
Power losses (in MW) for a load of 300 MW

10 0.0500 0.1800 0.4300
20 0.1000 0.3598 0.8594
50 0.2500 0.8983 2.1438
100 0.5000 1.7927 4.2724
200 0.9953 3.5694 8.4839
300 1.4892 5.3301 12.6354