Protection for DC Distribution System with Distributed Generator
Table 3
The action situation of each CB during F1–F5.
| Fault type | Percentage of fault location | Rectifier blocked time (s) | The action of breakers (time for receiving trip instruction) | CB2 | CB3 | CB4 | CB5 | CB6 | CB7 |
| F1 | 10% | 2.0022 | +(2.0082) | # | +(2.0012) | # | # | # | 50% | 2.0016 | +(2.0120) | # | +(2.0010) | # | # | # | 100% | 2.0010 | +(2.0200) | # | +(2.0008) | # | # | # |
| F2 | 10% | 2.0010 | # | # | # | +(2.0010) | # | # | 50% | 2.0016 | # | # | # | +(2.0010) | # | # | 100% | 2.0024 | # | # | # | +(2.0018) | # | # |
| F3 | 10% | 2.0010 | # | # | # | # | +(2.0010) | # | 50% | 2.0014 | # | # | # | # | +(2.0010) | # | 100% | 2.0024 | # | # | # | # | +(2.0010) | # |
| F4 | 10% | 2.0010 | # | # | # | # | # | +(2.0010) | 50% | 2.0016 | # | # | # | # | # | +(2.0010) | 100% | 2.0024 | # | # | # | # | # | +(2.0014) |
| F5 | — | 2.0010 | # | +(2.0008) | +(2.0008) | # | # | # |
|
|
Note: results noted “+” are on behalf of the action of CB and results noted “#” are on behalf of the inaction of CB.
|