Stepped Fault Line Selection Method Based on Spectral Kurtosis and Relative Energy Entropy of Small Current to Ground System

Table 12

EMD relative energy entropy.

Fault line / EMD relative energy entropy Entropy multiple ResultsRight?
S1 S2 S3 S4

Overhead line S2201.91124.51435.18574.93352.36 > 2S2Y
2000.80323.85545.97644.89814.80 > 2S2Y
150°202.02734.42645.74864.38122.18 > 2S2Y
2000.97194.12696.87806.25984.25 > 2S2Y

Hybrid line S3200.76171.12094.80992.84811.47 < 2S3Y
2000.67140.95014.77892.96951.12 < 2S3Y
150°201.08061.59685.30134.00031.48 < 2S3Y
2000.79271.35015.06422.72251.70 < 2S3Y

Cable line S4200.55020.94285.42574.25431.71 < 2S4Y
2000.20290.75322.04433.79423.71 > 2S2N
150°200.27060.38614.88854.08311.43 < 2S3N
2000.30371.58144.29055.53915.21 > 2S2N